DL9110 / DL9118
Operating Instructions
- 30 -
6.4 Line Impedance
Supply Voltage
195V – 253V, 45Hz – 65Hz
328V - 440V, 45Hz – 65Hz
Nominal Test Current
3A
Display Range
0.01
Ω
- 2000
Ω
Measuring Range
0.1
Ω
- 1999
Ω
Resolution
0.01
Ω
maximum
Accuracy
±5% ±5 digits
PFC Range
0kA – 26kA
6.5 RCD
Supply Voltage
195V – 253V, 45Hz – 65Hz
Nominal Test Currents
10mA, 30mA, 100mA, 300mA,
500mA
Test Current Accuracy
-0% +10% at I
∆
n and 5I
∆
n
-10% +0% at ½ I
∆
n
Trip Time Ranges
0ms – 2000ms, ½ I
∆
n
0ms – 300ms, I
∆
n General
0ms – 500ms, I
∆
n Selective
0ms – 40ms, 5I
∆
n
Trip Time Accuracy
±5% ±2 digits
Ramp Current Range
½ I
∆
n to 1.1 I
∆
n
Trip Current Measurement
Accuracy
10%
6.6 Voltage/Frequency Measurement
Display Range
0V – 440V
Voltage Measuring Range
0V – 440V
Resolution
1V
Accuracy
±5% ±2 digits
Frequency Range
45Hz – 65Hz
Frequency Accuracy
±1Hz