I NS TA LLAT IO N M A N U A L
9. Appliance-specific information
!CAUTION
The appliance-specific instructions as described in this section prevail over the instructions in the other sections! If
in doubt follow the instructions in section 9 or contact your supplier.
9.1 Smoke control area United Kingdom
The DG Fire Ivar 10 H
2
O has not been recommended as a suitable for use in smoke control areas when burning
wood.
9.2 Air slide valve and flue gas exhaust
9.2.1 Air slide valve
When installing and maintaining the appliance, please check the operation of the air slide valve (see Appendix 2,
fig. 6). It is possible that steel grit entered the air slide valve during transport. If the air slide valve does not move
smoothly it must be cleaned. For this purpose, the air slide valve must be disassembled. The suspended air slide
valve is spring-mounted using a bolt and a spring, which are located below the cover plate.
When mounting the air slide valve, please proceed as follows (see Appendix 2, fig. 6):
Caution!
If an outside air connection has been mounted, it must first be removed, before the air slide valve can be mounted
(for removing the outside air connection: see section 9.5.1.1).
Ø
Remove the vermiculite plates from the bottom (see section 9.3.1).
Ø
Then remove the little square plate located in a recess below the vermiculite bottom plates.
Ø
Loosen the allen screw using the socket head wrench.
Caution!
As soon as the bolt has been loosened, the air slide valve will fall down. Make sure you catch the air slide valve!
Ø
Check the air slide valve and clean it if necessary.
In order to replace the air slide valve, proceed as described for removal, only in reverse order.
9.2.2 Flue gas exhaust
The flue gas exhaust has a 150 mm diameter connection. The connection can be achieved by means of a fixed
pipe of 150 mm.
9.3 Interior lining
9.3.1 Vermiculite
The fire's vermiculite plates are located on the bottom and against the rear and side walls of the appliance
(see Appendix 2, fig. 5).
In the following situations the vermiculite plates must be taken out:
•
When disassembling the air slide valve (see section 9.2.1).
•
When replacing the vermiculite plates.
The bottom plates are removed first and the rear plates are removed last.
The insertion of the vermiculite plates takes place in reverse order.
!Caution
Make sure that the vermiculite plates are placed back in their original position! The back plate, for instance, must
be placed with the small, not countersunk, holes towards the front.
EN
Summary of Contents for Ivar 10 H2O, Store
Page 21: ...21 N e d e r l a n d s INSTALLATIEHANDLEIDING NL...
Page 22: ...22 N e d e r l a n d s INSTALLATIEHANDLEIDING NL...
Page 41: ...41 E n g l i s h INSTALLATION MANUAL EN...
Page 42: ...42 E n g l i s h INSTALLATION MANUAL EN...
Page 61: ...61 D e u t s c h INSTALLATIONS ANLEITUNG DE...
Page 62: ...62 D e u t s c h INSTALLATIONS ANLEITUNG DE...
Page 81: ...81 F r a n a i s MANUEL D INSTALLATION FR...
Page 82: ...82 F r a n a i s MANUEL D INSTALLATION FR...
Page 89: ...89 52c 0273 2...
Page 90: ...90 52c 0268 1 2 4x 52c 0274 1 2 3 4 4 3...
Page 91: ...91 52c 0264 1 2 3 52c 0271 1 2 3 6 5...
Page 92: ...92 52c 0262 8x 1 8x 2x 2 3 4 7...
Page 93: ...93 52c 0265 2x 4x 1 2 3 52c 0266 2x 4x 1 2 3 8 2 8 1...
Page 94: ...94 52c 0261 6x 1 2 3 4 52c 0263 10 9...
Page 95: ...95 52c 0269 1 2 4x 11...