WIRE FOR FLOOR ACCESS

The X1 Series Elevator Module provides 10 Form C (SPDT) 1 Amp relays for controlling 

access to 10 floors. The three relay terminals are labeled for normally open (NO) and 

normally closed (NC) operation. The center terminal is the common. See figures. These 

allow you to connect the device wiring to the 

relay for floor access control.

  Warning:

 Before wiring for floor 

access, check with elevator service 

company for their desired relay 

operation for controlling the floors. 

1. 

Wire the number of controlled floors 

to the elevator module. To wire 

for floor access control, use the 10 

terminals on the elevator module and 

label them carefully for the elevator 

service company.

2. 

Allow extra wire so that the elevator 

service company has enough length 

to attach to the elevator control 

center. 

3. 

Ensure the wires are in a logical 

location for the elevator service 

technician to find.

X1 ELEVATOR CONTROLLER QUICK START GUIDE  |     DIGITAL MONITORING PRODUCTS 

2

Onboard Outputs

Use these terminals for local outputs or elevator alarms such 

as sounders, lights, or sirens. These are 12 VDC outputs.

Aux Output 1 & 2 (O1 & O2)

Attach the negative wire of the device here.

12V+ (12V)

Attach the positive wire of the device here.

+AC/DC-

+BAT-

R1 W1 G1

B1

LC BC

R2 W2 G2 B2 LC BC

DS RX CI

G

01

02 12V

NC

C

NO

01 02 12V

X1 Elevator Controller

WIRE OPTIONAL INPUTS AND OUTPUTS

Onboard Inputs

Door Switch (DS) - Normally Closed

This terminal is not typically used for elevator access.
Connect a door contact or door position switch to indicate 

status of the elevator, whether it is open or closed. 

Request to Exit (RX) - Normally Open

This terminal is not typically used for elevator access.
Connect a motion sensing device or a mechanical switch to 

provide RX capability to the controller. 

Custom Input (CI) - Normally Open

This input triggers a custom action. 

Ground (G)

This terminal is the ground for the inputs.

+AC/DC-

+BAT-

R1 W1 G1

B1

LC BC

R2 W2 G2 B2 LC BC

DS RX CI

G

01

02 12V

NC

C

NO

DS RX CI

G

X1 Elevator Controller

NC  1  NO

Normally Open

Common

Normally Closed

PWR
DATA

0 1

2

3

4

5

6

7

8

9

  

ADDR

6

1

7

8

9

10

2

3

4

5

NC  1  NO

NC  2  NO

NC  3  NO

NC  4  NO

NC  5  NO

NC  6  NO

NC  7  NO

NC  8  NO

NC  9  NO NC  10  NO

NC  1  NO

NC  1  NO

Normally Open

Normally Closed

Top 4-Wire Connector

to X1 Elevator Controller

X1 Elevator Module

Summary of Contents for X1 Series

Page 1: ...EADER The X1 Series provides direct 12 VDC output to the reader on the RED terminal connection The elevator service company supplies traveling cable wires for the reader Document which numbered conductors are connecting to which terminals on the elevator controller Terminal Name Wiegand Function OSDP Function R1 R2 12V DC W1 W2 Data 1 B 485 G1 G2 Data 0 A 485 B1 B2 12V ground DC LC LED Control N A...

Page 2: ... as sounders lights or sirens These are 12 VDC outputs Aux Output 1 2 O1 O2 Attach the negative wire of the device here 12V 12V Attach the positive wire of the device here AC DC BAT R1 W1 G1 B1 LC BC R2 W2 G2 B2 LC BC DS RX CI G 01 02 12V NC C NO 01 02 12V X1 Elevator Controller WIRE OPTIONAL INPUTS AND OUTPUTS Onboard Inputs Door Switch DS Normally Closed This terminal is not typically used for e...

Page 3: ...re Wi Fi Connection If not connecting over Ethernet the Elevator Controller will connect over Wi Fi after power up For installing the Wi Fi Antenna follow the QR code at the end of this guide to see the full X1 Series Elevator Module Installation and Programming Guide LT 2463 Note You can connect over Ethernet or Wi Fi but not both at the same time Ethernet Port PoE Headers Cell Header Standoff Lo...

Page 4: ...ttings PROGRAM IN DEALER ADMIN Go to Dealer Admin dealer securecomwireless com to program the controller TEST THE CONTROLLER Make sure that the Reader LEDs are on and the Elevator Controller s Power LED is on If connected to Wi Fi the Wi Fi LED is on solid If connected to network the Network Port light is blinking For cell and all communication methods check that the elevator controller is communi...

Reviews: