4

RLE

!

Product Ratings

RLE-D1-ST: 

120-277 V AC, 50/60 Hz, 145 W (max), 1.21 A (max)

RLE-H1-ST: 

120-277 V AC, 50/60 Hz, 214 W (max), 1.79 A (max)

RLE-P1-ST:

 120-277 V AC, 50/60 Hz, 428 W (max), 3.56 A (max)

RLE-D1-HV: 

347-480 V AC, 50/60 Hz, 148 W (max), 0.43 A (max)

RLE-H1-HV: 

347-480 V AC, 50/60 Hz, 217 W (max), 0.63 A (max)

RLE-P1-HV:

 347-480 V AC, 50/60 Hz, 434 W (max), 1.25 A (max)

INSTALLATION INSTRUCTIONS

1: Verify Optic Type

Use optic type specified in the project plan — WIDE or NARROW. 

Hint:

 

The optic type is printed on the fixture label 

(Illustration 1)

.

2: Add Tracking Labels to Sticker Book

Detach plastic bag from fixture, then remove product and controller 

barcode label assembly from bag and affix to sticker book, as depicting  

the intended installation location of the fixture 

(Illustration 2)

.

 

3: Rotate Light Bars

a.  Rotate the lightbars into position as specified in the project plan 

(Illustration 3)

Note:

 

Ensure at the light bar release buttons are secured within  

           the appropriate detents.

Note:

 

Refer to Appendix B for typical lightbar positioning examples.

4: Install Fixtures

Note:

 

Fixture must be positioned at least 0.2m (8 in) from the ceiling.

Note:

 Fastening hardware supplied by installer.

Option 2a: Aircraft Cable – RLE-D1/H1

a.  Refer to the sticker book to confirm the correct location and 

placement of the fixture. 

b.  Secure aircraft cable to a beam or truss.

c.  Connect cable to fixture housing using aircraft cable hanging 

hardware

 

(Illustration 4e)

d.  Use a box level to level the fixture.

Hint:

 

For aisle illumination, verify that fixture is oriented correctly 

(Illustration 4f)

.

Option 2b: Aircraft Cable – RLE-P1

a.  Refer to the sticker book to confirm the correct location and 

placement of the fixture. 

b.  Secure aircraft cable to a beam or truss.

c.  Connect cable to fixture housing using aircraft cable hanging 

hardware

 

(Illustration 4g)

d.  Use a box level to level the fixture.

Hint:

 

For aisle illumination, verify that fixture is oriented correctly 

Illustration 4h)

.

5: Make Electrical Connections

Suitable for cords 1.5mm

2

 –2.5mm

2

 

Do not connect or disconnect while under load.

e.  Remove (2x) Phillips

®

 screws retaining the wiring compartment 

access panel

 (Illustration 5a).

f.  Extract the internal three-wire bundle from wiring compartment 

(Illustration 5b)

 

and identify the wire leads

 (Illustration 5c).

g.  Connect external wiring to internal wire bundle using supplied 

WAGO splicing connectors

 (Illustration 5d).

h.  Use supplied cable gland or suitable IP-rated wiring connector 

(supplied by installer) to route power cable through access panel 

(Illustration 5e)

.

i.  Replace wiring compartment access panel and tighten screws to  

8 kgf-cm

 

(Illustration 5f)

.

6: Verify Sticker Book

To prevent issues during commissioning, ensure that the placement 

of the bar code label in the sticker book corresponds to the fixture’s 

physical location in the facility.

GETTING STARTED

Summary of Contents for RLE Series

Page 1: ...he light source contained in this luminaire shall only be replaced by the manufacturer or his service agent or similarly qualified person Do not apply paint lubricants or other coatings to fixture sus...

Page 2: ...ontroller Serial Label PPHHHHHH SCN GA 00 X DC SN Item XXX XX XX X XXX YYWW FFF BBBB PPHHHHHH XXXXXXXX XXX XX XX X XXX XX SUF OPT Place Controller Label Here Controller Serial Label PPHHHHHH SCN GA 00...

Page 3: ...3 RLE INSTALLATION INSTRUCTIONS Illustrations RLE cont 5a 5b N L 4g 4h...

Page 4: ...cable to a beam or truss c Connect cable to fixture housing using aircraft cable hanging hardware Illustration 4e d Use a box level to level the fixture Hint For aisle illumination verify that fixture...

Page 5: ...ion Fixture Optic Light Bar Setting RLE D1 NARROW 10 10 RLE H1 P1 NARROW 20 0 20 Highbay Racked Application widely spaced fixtures Fixture Optic Light Bar Setting RLE D1 NARROW 20 20 RLE H1 P1 NARROW...

Page 6: ...the short edge of the fixture 2 Apply Sensor Mask to Optic One at a time remove the adhesive backing Carefully place each mask decals along either side of the sensor optic as shown above Do not cover...

Page 7: ...then extract the module from the fixture housing 2 Install Replacement Control Module a Insert the replacement module and rotate it 1 8 turn clockwise while lightly pushing down until there is an aud...

Page 8: ...rporated Subject to change without notice DOC 001706 00 Rev A 09 19 Importador mexicano Energetika Sustentable y Ecol gica S A de C V Avenida Patriotismo 12 Int 2 201 Hip dromo Cuauht moc C P 06100 Te...