background image

 

 

Push Button Minute Timer 

 

 

 

 

D: Setting Advanced Timer Mode 

 
The advanced timer mode provides an optional advanced warning to the user that the lights will shortly turn off automatically. 
 
When the advance timer is enabled, at time out the lights are dimmed to 50% over a 4 second period and are held at this 50% 
level for 5 minutes. After this 5 minutes, the lights are turned off automatically. 
 
 

Step 1 

Enter into the timer 

Setup Mode - See PART A

 

 

Step 2 

Click the push button 

4 times 

 
 

 

Step 3 

The LED Indicator will 

blink 4 times 

 

Note: To cancel/exit do nothing for 30 seconds 
 
 

 

Step 4 

To enable the advanced timer mode 
Push and hold the button until the lamps(s) turn ON 
 
To disable the advanced timer mode 
Push and hold the button until the lamps(s) turn OFF (default) 
 
Note: To cancel/exit do nothing for 30 seconds 
 

 

Step 5 

Click once to save & exit 
 
Note that during this Advanced Timer 5 minute warning period:- 
• The LED indicators will blink at a faster rate 
• A tap of the push button will restore the load to 100%  
   ON and the timer will restart 
• A long press of the push button will turn the load OFF. 

 

 

 

 

 

 

Summary of Contents for LEDsmart+ MultiMate MMTM/PB

Page 1: ...Setup Functions Guide MMTM PB www glg lighting Push Button Minute Timer Programmable between 1 minute and 30 minutes with built in multi way control...

Page 2: ...mer Setup Functions Function See Part Setting the Timeout period A Setting Maximum Brightness B Setting Advanced Timer Features C Setting Off State LED Feature D Converting from minute to hour timer E...

Page 3: ...o be adjusted as required Go to the relevant setup function instructions A2 Timer has been powered up via mains 240Vac for MORE THAN 15 MINUTES Step 1 Press and hold the button for 30 seconds Note Thi...

Page 4: ...othing for 30 seconds Step 4 To set the time out interval push and hold the button and count the number of blinks Each blink of the indicator adds 1 minute to the minute timer Step 5 When the number o...

Page 5: ...ep 1 Enter into the timer Setup Mode See PART A Step 2 Click the push button 3 times Step 3 The LED Indicator will blink 3 times Note To cancel exit do nothing for 30 seconds Note If more than one dim...

Page 6: ...tep 2 Click the push button 4 times Step 3 The LED Indicator will blink 4 times Note To cancel exit do nothing for 30 seconds Step 4 To enable the advanced timer mode Push and hold the button until th...

Page 7: ...n the timer is off follow the steps below Step 1 Enter into the timer Setup Mode See PART A Step 2 Click the push button 5 times Step 3 The LED Indicator will blink 5 times Note To cancel exit do noth...

Page 8: ...Enter into the timer Setup Mode See PART A Step 2 Click the push button 6 times Step 3 The LED Indicator will blink 6 times Note To cancel exit do nothing for 30 seconds Step 4 To change operation to...

Page 9: ...s connected to the dimmer will now turn OFF b If the MultiMate function is currently Enabled lamps s connected to the dimmer will now turn ON Note To cancel exit do nothing for 30 seconds Step 4 To En...

Page 10: ...Button Minute Timer 10 H Resetting to Factory Default Step 1 Enter into the timer Setup Mode See PART A Step 2 Click the push button 10 times Step 3 The timer will automatically exit Setup Mode once r...

Page 11: ...ment to Gerard Lighting Gerard Lighting Pty Ltd Gerard Lighting reserves the right to alter the specifications designs or other features of any items and to discontinue any items at any time without n...

Page 12: ...hing of connected lighting loads from multiple locations without any additional wiring No strapper wires dedicated remote switch wiring or control bus is required HOW MULTIMATE WORKS MultiMate product...

Page 13: ...higher value Refer to the product installation guide for details Solution 2 Fit a load bypass device order code MMBP Solution 3 In extreme cases both the MMBP and a raised minimum level may be needed...

Page 14: ...own transformer to building High resistance terminations on active feeds and or neutral returns and Neutral returns from a common active feed having significantly different run lengths back to the swi...

Page 15: ...mable LED load may be used on the same circuit as non dimmable loads In this case when the dimmer level is higher than a threshold the relay is operated to switch the non dimmable load s on and the di...

Reviews: