![DIEL ME 200 E Installation And Instruction Manual Download Page 79](http://html1.mh-extra.com/html/diel/me-200-e/me-200-e_installation-and-instruction-manual_2495715079.webp)
ME 200 E TAB 2
- 79 -
•
Register 17 Status fault channels CH1 to CH8: bit 0 to bit 7
0
Fault not active
1
Fault active
•
Register 18 Status relay channels:
•
Pre-alarm (bit 0), Alarm (bit 1), Fault (bit 2), Fan A (bit 3), Fan B (bit 4)
0
Relay not active
1
Relay active
•
Register 19 and Register 101: Status channels enable: CH1 to CH8: bit 0 to bit 7
0
Channel disable
1
Channel enable
•
Register 20 and Register 102: Status fan active channel Fan A 1 to Fan A 8: bit 0 to bit 7
0
Fan not active
1
Fan active
•
Register 21 and Register 103: Status fan active channel Fan B 1 to Fan B 8: bit 0 to bit 7
0
Fan not active
1
Fan active
•
Register 22 and Register 100: Function mode
0
8 Channels with FAN A and FAN B
1
8 Channels without FAN A and FAN B
4
Extended programming mode (See manual)
Notes
Defeult ip address 192.168.1.205 subnet mask 255.255.225.0 gateway 192.168.1.1.
Registers 1 to 8 and 23 to 38 format: 16 bit signed short (-32767 / +32767).
Registers 1 to 8 and 23 to 38 have scale factor 100.
Supported MODBUS-TCP standard functions:
03x Read holding register, 04x Read input register
06 Write register, 16x Write multi registers.