ME 200 E ENG
- 28 -
ADVANCED PROGRAMMING
It allows to program independent thresholds
To access the ADVANCED PROGRAMMING menu, refer to the
PROGRAMMING
paragraph, choice 4.
CHANNEL 1 is proposed, as enabled default,
to disable the channel set the value of the first
display to 0 with the keys
and press
to confirm.
For the activated channels, the following values are then proposed, modifiable
with the keys
, to be confirmed with the key
.
P: PRE-ALARM, default 140
A: ALARM (Usually used for network
disconnection), default 160
FAN A is proposed in relation with the setted
channel (for example FAN A CHANNEL 1
F1A, FAN A CHANNEL 2
F2A), default
enabled, to disable the fan control, set the
value of the first display to 0 with the keys
and press
to confirm.
If enabled:
L: FANS SHUTDOWN, default 90
H: FANS INTERVENTION, default 100
FAN B is proposed in relation with the setted
channel (for example FAN B CHANNEL 1
F1B, FAN B CHANNEL 2
F2b)
default enabled, to disable the fan-n control,
set the value of the first display to 0 with the
keys
and press
to confirm.
If enabled:
L: FANS SHUTDOWN, default 90
H: FANS INTERVENTIN, default 100