background image

max = 48 m (160 ft)

Preliminary checks

Take the PRESFLO

®

 out of 

the packaging and check the 
following:
- check for damage, 
- check the RATINGS correspond 
with those required, 
- that the cable bushings and 
screws are in place,
- that PRESFLO

®

’s inlets and 

outlets are clean and free of any 
packaging materials,
- that the check valve moves 
smoothly.

Hydraulic connections

the joint in two pieces allows ra-
pid connection to the sy-
stem.

 

DO NOT apply se-

alant inside the 2-piece 
joint  because  it  already 
has an internal o-ring.

Orientation

PRESFLO

®

 can be installed at 

any angle depending on the flow 
direction, as indicated in the 
diagrams.

Position

PRESFLO

®

 can either be fitted 

directly to the pump outlet or 
anywhere along the delivery 
line. Never install taps between 
the pump and PRESFLO

®

. Do 

not install a non-return valve 
between PRESFLO

®

 and the taps, 

meanwhile it is possible, although 
not necessary, to install a non-
return valve on the suction piping 
of the pump.

Installation

Attention

The pressure applied 

by the water column above 
PRESFLO

®

 must not exceed that 

of the pump start-up pressure 
(Pm). If, for example, PRESFLO

®

 

is installed at a height 20 metres 
(65 ft) below that of the highest 
tap in the system, the pressure 
detected by PRESFLO

®

 will be 

approximately 2 bar (30 psi).
A model with Pm = 2.5 – 35 psi 
bar should, therefore, be installed 
in order to guarantee that the 
pump is started when a tap is 

turned on.

Attention

The maximum pressure 
produced by the pump 

must be at least  0.5 bar (7 psi) 
higher than the start-up pressure 
(Pm). If the pressure produced by 
the pump is too low, PRESFLO

®

 

will stop the pump and indicate a 
‘dry running’ error message.

First start-up

Priming the pump

For instructions on how to 
prime (fill) the pump, see the 
pump manual.

Attention

PRESFLO

®

 is fitted with a 

check valve: do not use the 
PRESFLO

®

’s outlet to fill the 

pump for priming.

Switching the pump on  

The red (Power On) LED lights 
up; PRESFLO

®

 

instantly detects 
that there is no 
pressure within the system and 
starts the pump 
(the green ‘Pump 
On’ LED lights up).
If, within 15 secon-
ds of starting up, 
PRESFLO

®

 does not detect the 

correct priming of 
the pump, it stops the pump 
and indicates a ‘dry running’ 
error message.
 

Attention

When the pump is started for 
the first time, it may have to 
be run for longer in order to 

complete the priming 
procedure.

Press the STOP/RE-

START button 

to restart the  
pump and 
complete the 
priming procedure.

NOTE 1 - DRY RUNNING 

=  there is no flow and the pressure is lower 

than that of the pump start-up pressure (Pm). It occurs when there is no 
water. After 15 seconds PRESFLO

®

 stops the pump and indicates an ERROR 

message. PRESFLO

®

 AUTOMATICALLY tries to resume NORMAL SERVICE 

at intervals of increasing time (1, 15, 30, 60 minutes and successively once 
every hour - 24 H for AU/NZ - ). If PRESFLO

®

 detects any pressure and/or 

flow, NORMAL SERVICE is resumed, otherwise, the pump is stopped again 
until the next attempt is made. A MANUAL attempt to resume NORMAL 
SERVICE can be made at any time. 

NOTE 2 - FREQUENT START-UP 

= the repeated stopping and starting of 

the pump at intervals of less than 1 minute from each other. This occurs 
when the flow rate is less than 2 litres/min. This may cause damage to the 
pump. In event of small leaks (dripping), PRESFLO

®

’s water accumulator 

guarantees that the pump starts/stops at time intervals of over 1 minute 
(less than 60 starts/hour) and that FREQUENT START-UP errors do not occur. 
In the event of a major leak or extended use at excessively low flow rates 
(less than 2 litres/min), the pump may be started/stopped as often as once 
every few seconds, putting the pump at risk of damage. In this case, after 
about 40 minutes, PRESFLO

®

 stops the pump for the following 30 minutes 

(in order to let it cool down) and indicates an ERROR message. If the time 

interval between the starts-stops is more than 10 seconds (and therefore 
poses less of a risk to the pump), PRESFLO

®

 will allow the pump to be 

used for more than 30 minutes. Once that enough time has passed to allow 
the pump to cool down it is restarted AUTOMATICALLY. The pump may be 
restarted MANUALLY any time.

NOTE 3 - OVERCURRENT 

= electric absorption of the pump (in Ampere) 

exceeding the max. allowed (I max). By means of the configuration, it is 
possible to set the max. current allowed (I max). During the start-up phase 
of the pump PRESFLO

®

 allows for a few seconds the current to exceed the 

Imax value. If the absorptions remain above the set Imax value, PRESFLO

®

 

stops the pump to avoid damaging the motor and signals an anomaly. 
PRESFLO

®

 will not automatically restart the pump. The pump may be 

MANUALLY restarted at any moment. Should the problem persist an anomaly 
will again be signalled. The manual restart can be repeated several times 
since PRESFLO

®

 does not limit the number of attempts.

NOTE 4 - SHUT-OFF FLOW RATE 

= Flow rate (Qa) of around 2 litres/min 

(0,5 gpm) below which PRESFLO

®

 stops the pump.  

Motor

Line

Nut

Seal

Cable bushing

Attention!

 The cable 

bushings and circuit board 
cover must be properly 
assembled and secured 
in order to guarantee IP 
65 grade protection of the 
electrical components. 

Electrical con-
nections

The electrical 
connections 
should be made 
as indicated in the 
diagram which 
can also be found 
on the inside of 
the circuit cover.

Summary of Contents for PRESFLO MULTI

Page 1: ...nic components PRESFLO can only be used with single phase pumps Working area Flow rate Pressure Shut off flow rate Start up pressure Qa Pm Safety regulations Before installing or using PRESFLO read this manual carefully and thoroughly The pump should be installed and serviced by qualified per sonnel responsible for making the hydraulic and electrical connections in compliance with the relevant reg...

Page 2: ...It occurs when there is no water After 15 seconds PRESFLO stops the pump and indicates an ERROR message PRESFLO AUTOMATICALLY tries to resume NORMAL SERVICE at intervals of increasing time 1 15 30 60 minutes and successively once every hour 24 H for AU NZ If PRESFLO detects any pressure and or flow NORMAL SERVICE is resumed otherwise the pump is stopped again until the next attempt is made A MANUA...

Page 3: ... turned on PRESFLO detects a flow the assembly pressure is normally higher than the START UP pressure but it may also be lower Press briefly or hold down the pump is stopped and put OUT OF SERVICE For instruc tions on how to reactivate the pump see point 3 The taps are turned off Sif there is no flow for a few seconds the pump is stopped NORMAL SERVICE the pump is running PRESFLO has detected that...

Page 4: ...be adjusted continuously from 4 to 12 A trimmer B 4 When you finish adjustment close the cover CODE V Hz I max B V00103101 230 50 60 16 A SN 1506003 1 2 3 6 5 4 8 7 Exploded view of spare parts Attention when orde ring spare parts always state the position n from the diagram below and the product code number found in the pressure flow regulator technical data table Article Version Dimensions Off F...

Reviews: