DeZURIK
APCO CSD-800 Slanting Disc Check Valves
July 2017
Page 17
D12012
Troubleshooting
Condition
Possible Cause
Corrective Action
Valve leaks excessively from
one side of the disc to the other.
Foreign matter caught between
disc and seat.
Fully open valve to remove
object.
Seat ring and/or disc ring are
worn or damaged.
Replace seat ring and/or disc
ring.
Valve leaks at flange joint.
Loose flange bolting.
Tighten flange bolting.
Blown flange gasket.
Replace flange gasket.
Misalignment or damage to field
piping and supports.
Adjust misalignment or repair
piping or supports.
Damaged flange face/s or
improper flange connections.
Repair flange, replace valve
body or adjust flange
connections.