Technical Data
Replacement
A. Disconnect the Microinverter from the PV Module, in the order shown below:
1. Disconnect the AC by turning off the branch circuit breaker.
2. Disconnect the AC connector of the microinverter.
3. Cover the module with an opaque cover.
4. Disconnect the PV module DC wire connectors from the Microinverter.
5. Remove the Microinverter from the PV array racking.
B. Remove the opaque cover, Install a replaced Microinverter to the bracket.
Remember to observe the flashing LED light as soon as the new Microinverter is
plugged into the DC cables.
C. Connect the AC cable of the replacement Microinverter.
Follow the procedure to replace a failed Microinverter
WARNING
:
Be sure to verify the voltage and current specifications of your PV module
match with those of the Microinverter. Please refer to the datasheet or user manual.
WARNING
:
You must match the DC operating voltage range of the PV module with
the allowable input voltage range of the Microinverter.
WARNING
:
The maximum open circuit voltage of the PV module must not exceed
the specified maximum input voltage of the inverter.