- 31 -
5.9 Generator Port Use Setup Menu
Generator input rated power:
allowed Max. power from diesel
generator.
GEN connect to grid input:
connect the diesel generator to the
grid input port.
Smart Load Output:
This mode u�lizes the Gen input connec�on
as an output which only receives power when the ba�ery SOC
and PV power is above a user programmable threshold.
e.g. Power=500W, ON: 100%, OFF=95%:
When the PV power
exceeds 500W, and ba�ery bank SOC reaches 100%, Smart Load
Port will switch on automa�cally and power the load connected.
When the ba�ery bank SOC < 95% or PV power < 500w, the
Smart Load Port will switch off automa�cally.
Mode
OFF
ON
Generator Input
SmartLoad Output
Micro Inv Input
On Grid always on
GEN connect to Grid input
Ml export to Grid cutoff
GEN PORT USE
52.00Hz
100%
95%
Power
Rated Power
AC Couple Fre High
500W
5000W
PORT
Set1
Smart Load OFF Ba�
• Ba�ery SOC at which the Smart load will switch off.
Smart Load ON Ba�
• Ba�ery SOC at which the Smart load will switch on. Also, the PV input power should exceed the se�ng value (Power)
simultaneously and then the Smart load will switch on.
On Grid always on:
When click "on Grid always on" the smart load will switch on when the grid is present.
Micro Inv Input:
To use the Generator input port as a micro-inverter on grid inverter input (AC coupled), this feature will
also work with "Grid-Tied" inverters.
*
Micro Inv Input OFF: when the ba�ery SOC exceeds se�ng value, Microinveter or grid-�ed inverter will shut down.
*
Micro Inv Input ON: when the ba�ery SOC is lower than se�ng value, Microinveter or grid-�ed inverter will start to
work.
AC Couple Fre High:
If choosing“Micro Inv input”, as the ba�ery SOC reaches gradually se�ng value (OFF), During the
process, the microinverter output power will decrease linear. When the ba�ery SOC equals to the se�ng value (OFF),
the system frequency will become the se�ng value (AC couple Fre high) and the Microinverter will stop working.
MI export to grid cutsoff: Stop expor�ng power produced by the microinverter to the grid.
*
Note: Micro Inv Input OFF and On is valid for some certain FW version only.