Inverter hanging plate installa�on
- 08 -
3.3 Ba�ery connec�on
Chart 3-2 Cable size
For safe opera�on and compliance, a separate DC over-current protector or disconnect device is
required between the ba�ery and the inverter. In some applica�ons, switching devices may not
be required but over-current protectors are s�ll required. Refer to the typical amperage in the
table below for the required fuse or circuit breaker size.
Model
3.6/5Kw
Wire Size
3AWG
Cable(mm )
2
25
Torque value(max)
5.2Nm