DeVilbiss MG5-OLSTAT-3A User Manual Download Page 7

7

Compressors are shipped without oil.  A small amount
of oil may be present in the pump upon receipt of the
air compressor. This is due to plant testing and does
not mean that the pump contains the correct amount
of oil. Do not attempt to operate this air compressor
without first adding oil to the crankcase. Serious
damage can result from even limited operation un-
less filled with oil and broken in correctly. Make sure
to closely follow initial start-up procedures.

Place unit on a level surface. Remove oil fill plug and slowly add a
compressor oil such as Castrol Heavy Duty 30 weight until it is even
with the top of the oil fill hole. (It must not be allowed to be lower than
3/8" -- 6 threads down -- from the top at any time.) When filling the
crankcase, the oil flows very slowly into the pump. If the oil is added
too quickly, it will overflow and appear to be full. 

Crankcase oil

capacity is 16 fluid ounces.

 Replace oil fill plug and tighten.

NOTE

Drain and refill the compressor pump crankcase
after the first 100 hours of operation.

Additional Regulators and Controls

Since the air tank pressure is usually greater than that which
is needed, a separate regulator is usually employed to control
the air pressure ahead of any individual air driven device.

Separate air transformers which combine the function of air
regulation, moisture and dirt removal should be used 

where

applicable.

This procedure is required:

1. Before the air compressor is put into service.
2. When the check valve is replaced.
3. When a complete compressor pump is replaced.

a. Set the pressure switch lever to the "OFF" position.
b. Connect compressor to power source. (See Wiring

Instructions).

c. Turn the regulator clockwise (or open the shut-off valve),

opening it fully, to prevent air pressure build-up in the tank.

d. Move the pressure switch lever to "ON/AUTO". The

compressor will start.

INSTALLATION AND BREAK-IN PROCEDURES (cont'd)

IMPROPER ELECTRICAL GROUNDING CAN RESULT
IN A RISK OF ELECTRICAL SHOCK. WIRING FOR THE
PRESSURE SWITCH  AND  ELECTRICAL MOTOR
SHOULD BE DONE BY A LICENSED ELECTRICIAN IN
ACCORDANCE WITH NATIONAL AND LOCAL CODES
AND ORDINANCES.

Serious damage may result if the following break-in
instructions are not closely followed.

Break-in Procedures

Wiring Instructions

Perform electrical wiring according to the following instructions:

Install the compressor outfit as close to the main power supply as
possible. This practice will avoid using long lengths of electrical
wiring for the power supply which can cause power loss and damage
to the motor. When connecting wires make sure that:

1. The amperage rating of the electrical box is adequate. Refer to the

Specification Chart in the Outfit Parts Manual for your air com
pressor outfit.

2. The supply line has the same electrical characteristics (voltage,

cycle, and phase) as motor.

Wiring must be such that full motor nameplate voltage plus or minus
10%, is available at the motor terminals during starting. Refer to local
codes for recommended wire sizes and maximum wire run; under-
sized wire causes high amp draw and overheating to the motor.

Electrical wiring must be located away from hot sur-
faces such as the compressor head, compressor
cylinder, or compressor outlet tube.

Improper electrical installation  of this product may
void its warranty and your fire insurance. Have circuit
wiring performed by qualified personnel such as a
licensed electrician who is familiar with the current
national electric code and any prevailing local electri-
cal codes.

Lubrication and Oil

Multi-Viscosity motor oils, like 10W 30, should not be
used in an air compressor. They leave carbon depos-
its on critical components, thus reducing perfor-
mance and compressor life. Use air compressor oil
only.

Voltage and Circuit Protection

Refer to your Outfit Parts Manual for the voltage and circuit
protection requirements of your compressor. Use only a fuse or
circuit breaker that is the same rating as the branch circuit the air
compressor is operated on. If the compressor is connected to a
circuit protected by fuses, use only dual element time delay fuses,
as noted in that Outfit Parts Manual.

e. Run the compressor for 30 minutes. Make sure the

regulator, or shut-off valve, is open and there is no tank
pressure build-up during this time.

f.

After 30 minutes, close the regulator by turning it
counterclockwise or close the shut-off valve by turning the
knob clockwise. The air receiver will fill to cut-out pressure
and the motor will  stop. The compressor is now ready for use.

Summary of Contents for MG5-OLSTAT-3A

Page 1: ...ve the following information Model number of your product Part number and description of the item you wish to purchase Retain Original Sales Receipt as Proof of Purchase for Warranty Repair Work TABLE OF CONTENTS SAFETY GUIDELINES 1 WARRANTY STATEMENT 2 WARNING CHART 3 4 SPECIFICATIONS 5 GLOSSARY 5 DUTY CYCLE 5 GENERAL INFORMATION 5 ON RECEIPT INSPECTION 5 DESCRIPTION OF OPERATION 6 INSTALLATION A...

Page 2: ...t Authorized Warranty Service Center that provides on site service calls for service call arrangement If the purchaser does not receive satisfactory results from the Authorized Warranty Service Center the purchaser should contact DeVilbiss Air Power Company ExCell Manufacturing Merchandise sold as reconditioned floor models and or display models Any damaged or incomplete equipment sold as is Merch...

Page 3: ...TTACHMENTS THE TANK IS DESIGNED TO WITHSTAND SPECIFIC OPERATING PRESSURES NEVER MAKE ADJUSTMENTS OR PARTS SUBSTI TUTIONS TO ALTER THE FACTORY SET OPERATING PRESSURES FOR ESSENTIAL CONTROL OF AIR PRES SURE YOU MUST INSTALL A PRESSURE REGULATOR AND PRESSURE GAUGE TO THE AIR OUTLET OF YOUR COMPRESSOR FOLLOW THE EQUIPMENT MANUFACTUR ERS RECOMMENDATION AND NEVER EXCEED THE MAXIMUM ALLOWABLE PRES SURE R...

Page 4: ...OMPONENTS REMOVED OR DAMAGE ANY ELECTRICAL WIRING OR REPAIRS RE QUIRED ON THIS PRODUCT SHOULD BE PERFORMED BY AUTHORIZED SERVICE CEN TER PERSONNEL IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES MAKE CERTAIN THAT THE ELECTRICAL CIRCUIT TO WHICH THE COMPRESSOR IS CONNECTED PROVIDES PROPER ELECTRICAL GROUNDING CORRECT VOLTAGE AND AD EQUATE FUSE PROTECTION ALWAYS WEAR ANSI Z87 1 APPROVED SAFET...

Page 5: ... 50 of one hour is DUTY CYCLE considered misuse because the air compressor is undersized for the required air demand Maximum compressor pumping time per hour is 30 minutes You have purchased an air compressor unit consisting of an aluminum 2 cylinder single stage air compressor pump with cast iron sleeves an air tank and associated controls and instru ments You will also find a Parts Manual Your a...

Page 6: ... end of each use Air Intake Filter This filter is designed to clean air coming into the pump This filter must always be clean and ventilation openings free from obstructions See Maintenance AirCompressorPump Tocompressair thepistonsmovesupand down in the cylinder On the downstroke air is drawn in through the airintakevalves Theexhaustvalveremainsclosed Ontheupstroke of the piston air is compressed...

Page 7: ...ious damage may result if the following break in instructions are not closely followed Break in Procedures Wiring Instructions Perform electrical wiring according to the following instructions Install the compressor outfit as close to the main power supply as possible This practice will avoid using long lengths of electrical wiringforthepowersupplywhichcancausepowerlossanddamage to the motor When ...

Page 8: ...g It is recommended that a flexible coupling be installed between the air discharge valve outlet and main air distribution line to allow for vibration To remove dirt oil and water install a separator in the main distribution line Install separator 5 to 6 feet from compressor to allowtheairtocooltoroomtemperaturebeforepassingthroughthe separator Additional separators or filters may be used dependin...

Page 9: ...r air leaks Even minor leaks can cause the compressor to over work resulting in premature breakdown or unsatisfactory performance 4 Check for any unusual vibration and noise 5 Check for oil leaks Correct any leaks found Compressed air from the outfit may contain water condensation and oil mist Do not spray unfiltered air at an item that could be damaged by moisture or oil mist Some air operated to...

Page 10: ...as been drained close the drain cock The air compressor can now be stored NOTE If the drain cock valve is plugged release all air pressure The valve can then be removed cleaned and reinstalled DRAIN TANK DAILY WATER WILL CONDENSE IN THE AIR TANK IF NOT DRAINED WATER WILL CORRODE AND WEAKEN AIR TANK CAUSING A RISK OF AIR TANK RUPTURE OPERATING PROCEDURES cont d 5 When You Are Finished drain tank pr...

Page 11: ...h 7 8 4 Check that the valve disc moves freely and that the spring holds the disc in the upper closed position The check valve may be cleaned with a solvent 5 Apply sealant to the check valve threads Reinstall the check valve turn clockwise DO NOT OVERTIGHTEN 6 Replace the outlet tube and tighten top and bottom tube nuts DO NOT OVERTIGHTEN Safety Valve Inspection and Replacement IF THE SAFETY VALV...

Page 12: ...URE CONTROL RELATED DEVICE IF REPLACEMENT IS NECESSARY THE SAME RATED SWITCH MUST BE USED CONTACT A DEVILBISS AIR POWER AUTHORIZED SERVICE CENTER FOR REPLACEMENT Motor Overload Protector Reset The motor has a manual thermal overload protector If the motor overheats for any reason the overload protector will shut off the motor The motor must be allowed to cool down before restarting Turn the unit o...

Page 13: ...ervice Center to check remove or re place switch Tighten fittings where air can be heard escaping Check fittings with soapy water solution DO NOT OVER TIGHTEN A defective check valve results in a con stant air leak at the pressure release valve when there is pressure in the tank and the compressor is shut off Remove and clean or replace check valve DO NOT OVER TIGHTEN See page 11 Remove and replac...

Page 14: ...R TIGHTEN See page 11 Check wiring connection inside pressure switch and motor terminal box area 1 Check fuse box for blown fuse and re place if necessary Reset circuit breaker Do not use a fuse or circuit breaker with higher rating than that specified for your particular branch circuit 2 Check for proper fuse only Buss Fusetron Type T fuses are accept able 3 Check for low voltage conditions 4 Rem...

Page 15: ...y and flywheel must be in line within 1 32 See Pulley and Flywheel Alignment section on page 12 Adjust belt tension See Belt Replace ment section on page 12 Add oil to top of fill hole in base If there is an excessive amount of pressure drop when the accessory is used adjust the regulator NOTE Adjust the regulated pressure under flow conditions while the accessory is being used See oil recommendat...

Page 16: ...DeVilbiss Air Power Company 213 Industrial Drive Jackson TN 38301 9615 General Manual Oil Lubricated Single Stage Stationary Air Compressors SERVICE RECORD ...

Reviews: