background image

SB-6-132-G   Page 7

  5  First air drop should be at least 25' from the compressor, al-

though 50' is optimum.  This allows the compressed air to cool 

so any condensation can occur before it gets to the air filter.

  6  Shut-off valves are installed before the point of use filter.  This 

allows air to be shut off for filter maintenance.

  7  Point-of-use  filter  -  Strongly  recommended  for  eliminating 

any  remaining  contaminates.    The  DeVilbiss          CleanAir 

type air control units are most effective in providing a truly 

contaminant-free air supply.

  8  Drain valve - The daily draining of the system at each outlet 

disposes of the contaminants that build up in the air supply.

  9  Drain the compressor trap daily if equipped with a manual 

drain.

Proper maintenance of the air compressor can reduce airborne con-

taminants such as particles and oils, and reduce heat and operating 

cost.  Check air filters, oil level and perform regular maintenance 

per operators manuals.

CLEANAIR™ AIR PIPING RECOMMENDATIONS

The plumbing of your shop air lines is very important.  Correct 

installation is necessary for the proper performance of your equip-

ment – for an uncontaminated air supply and for sufficient pressure 

to your breathing apparatus and spray gun.

Correct air line piping is so important that this one factor alone 

can reduce contaminates in your air supply up to 75%.  Reducing 

contaminates to the filter also reduces the frequency of filter replace-

ment, maintenance, and of course reduces the risk of contaminates 

to the painter and paint supply.

Even the size of the pipe is critical.  Using pipe that is too small in 

diameter can cause a pressure drop.

Example:    If  an  air  compressor  delivers  100  psi  through  a  100' 

pipe 1/2" in diameter, there's greater pressure drop than if a 3/4" 

diameter pipe were used.  The chart on the back page provides 

recommended piping sizes.

AIR LINE PIPING GUIDE

  1  After leaving the air compressor, the air line should go  straight 

up as high as possible.  This helps prevent any water from 

leaving the compressor and travelling through the pipe.

  2  Horizontal pipes should slope back towards the compressor at 

least 4" per 50'.  As warm air leaves the compressor, it cools 

and thereby water vapor condenses as it travels through the 

pipe.  This water, a problem in itself, also can cause scaling 

and rust inside the piping.  The backward sloping of the pipe 

helps drain these contaminates back toward the compressor 

drain which should be drained daily.

  3  A take off should come from the top of the main air supply 

line at each air drop.  This reduces the risk of water and other 

contaminates  from  traveling  down  the  drop  into  the  water 

separator.

  4  Pipe diameter must be of sufficient size for the volume of air 

being passed as well as the length of pipe used.  This will 

minimize pressure drop.  See chart.

MINIMUM PIPE SIZE RECOMMENDATIONS CHART

Compressor 

Compressor 

Main 

Min. Pipe

Size 

Capacity 

Air Line 

Diameter

1-1/2 & 2 HP 

6 to 9 CFM 

Over 50 ft. 

 

3/4" 

3 & 5 HP 

12 to 20 CFM 

Up to 200 ft. 

 

3/4"

 

 

Over 200 ft. 

 

1"

5 to 10 HP 

20 to 40 CFM 

Up to 100 ft. 

 

3/4"

 

 

100 to 200 ft. 

 

1"

 

 

Over 200 ft. 

 

1-1/4"

10 to 15 HP 

40 to 60 CFM 

Up to 100 ft. 

 

1"

 

 

100 to 200 ft. 

 

1-1/4"

 

 

Over 200 ft. 

 

1-1/2" 

1

6

3

5

8

3

2

7

7

6

9

8

For normal 

compressed

air systems

having average

amounts of

airborne con-

taminants.

Add final

drain leg for

extremely

wet/dirty air.

Add drain leg with

blow down valve at

each station when

compressed air is

extremely wet/dirty.

Figure 13 – CleanAir™ Piping 

4

8

Summary of Contents for HAF-601

Page 1: ...turecanexceedratedoperating conditions see specifications Regulated outlet pressure must never be set higher than the maximumoperatingpressureofthe downstream air tool or equipment An outlet pressure...

Page 2: ...endepressurizationeffect replace the existing solenoid with a slow closingsolenoidvalve Onesource Auto matic Switch Co Or install an air adjusting valve at the existing solenoid valve outlet For ease...

Page 3: ...erioration Replace if necessary Note 6 The filter change indicator only operates when air is flowing It will always be green when there is no air flow HAF 505 Parts List Ind Ref Replacement Parts No P...

Page 4: ...spring but ton Diaphragm assembly can now be removed 3 Check all O rings for signs of damage Replace if necessary 4 Reassemble parts Insert stem of valve through hole in regulator body Install spring...

Page 5: ...pring or diaphragm turn adjusting knob counterclockwise to remove all spring force then remove bonnet Remove the adjusting screw assembly main spring slip ring and diaphragm assembly Inspect the dia p...

Page 6: ...ons water will not enter the float However water can get in the float if the filter bowl is washed with the drain installed or if air line contamination causes the drain mechanism to stick You can con...

Page 7: ...p Example If an air compressor delivers 100 psi through a 100 pipe 1 2 in diameter there s greater pressure drop than if a 3 4 diameter pipe were used The chart on the back page provides recommended p...

Page 8: ...w limitationsonhowlonganimpliedwarrantylasts orthelimitations or exclusion of consequential or incidental damages so the above limitations or exclusions may not apply to you ACCESSORIES HAF 407 Clean...

Reviews: