- Control mains voltage on clamps 5 and 6.

- Tighten up load clamps 1 to 3.

- Measure the resistance in the heating cable and

calculate the output:

From the calculated output the heating cable type
can be determined by looking it up in your •
catalogue.

- If sensor wire clamps no. 11 and 12 are removed the

red indicator lamp should light up and the thermostat
should switch on. If not the thermostat is defect.

- Measuring of sensor with ohmmeter should give a

stable resistance compared to the ambient
temperature - see technical data chart.

- If the sensor access is short-circuited the indicator

should turn off and the thermostat should be switched
off. If not, the thermostat is defect.

- When the mains voltage is disconnected the relay

contact must be open.

Control of functioning:

If heat is not turned on by activating the thermostat,
check the RCD and fuses before contacting an
authorized electrician.

Trouble-shooting chart:

Reserved for the electrician!

P=       =               W (at 230 V)

52900

R

U

2

R

Trouble-shooting

Control of functioning:

Summary of Contents for devireg 316

Page 1: ...devireg 316 Installation Instructions ...

Page 2: ...ff Itispossibletoadjustthehysteresisbetween0 2 Cand6 C If the temperature is set at 18 C and the hysteris at 3 C the thermostatwillswitchonat18 Candoffat21 C Difference Diff The heating system is connected when the reference temperature is between the regulated maximum and minimum temperature values See description of temperature regulation II When the temperature falls below the set value the the...

Page 3: ...commended for control of room temperature Temperature regulation II In this case the thermostat is to be used as a difference thermostat for regulation of snow and ice melting systems The range of the thermostat is decided by adjusting the temperature range 10 C to 50 C requested max temperature and the temperature range 10 C to 5 C requested min temperature If the heating system has to be connect...

Page 4: ...Cooling Heating ...

Page 5: ...asuring of sensor with ohmmeter should give a stable resistance compared to the ambient temperature see technical data chart If the sensor access is short circuited the indicator should turn off and the thermostat should be switched off If not the thermostat is defect When the mains voltage is disconnected the relay contact must be open Control of functioning If heat is not turned on by activating...

Page 6: ...C to 50 C 10ºC to 5 C NTC 15 kOhm at 25ºC 10 C 66 kOhm 0 C 42 kOhm 25 C 15 kOhm 50 C 6 kOhm Temperature range Working temperature Voltage Breaking power Night set back adjustable Differens adjustable Cap class Regulation range I range II Sensor type Sensing value Technical data ...

Page 7: ...ded in english or local language with the ISO code for your country in the upper left corner of the front page of the installation instruction in order to release the warranty The obligation of will be to repair or supply a new unit free of charge to the customer whitoutsecondary charges linked to repairing the unit In case of defective devireg thermostats reserves the right to repair the unit fre...

Page 8: ...nted to Name Phone Warranty Certificate Address Postalcode Please Observe In order to obtain the Warranty the following mustbecarefullyfilledin Seeotherconditions ontheoverleaf SuppliersStamp 08095512 02 02 ElectricalInstallationby Typeofthermostat Installationdate Productioncode ...

Reviews: