devireg

®

 316 is a thermostat for DIN rail attachment and has

a height of 52 mm. 

devireg

®

 316 is applied for control of

room temperature, floor temperature, ventilation, cooling or
as thermostat used for control of heat in gutters, etc.

Installation:

The installation must be permanent (

devireg

®

 316 must be

placed after the switch). The sensing unit can be extended
up to 50 m with 1.5 mm

2

 installation cable without affecting

the accuracy of the thermostat.
Never place the sensing unit parallel to high-voltage cables,
as undesirable signals may be induced.

Night set-back (    ):

By bridging clamps 4 and 6 via an external clock, e.g.

devitime

 301, the thermostat can be set to reduce the

temperature at night (adjustable between 0ºC to +8°C).

Hysteresis (Diff):

It is possible to adjust the hysteresis between 0,2°C and 6°C.

If the temperature is set at 18°C and the hysteris at 3°C the

thermostat will switch on at 18°C and off at 21°C.

Difference (Diff):

The heating system is connected when the reference
temperature is between the regulated maximum and
minimum temperature values. See description of
temperature regulation II. When the temperature falls below
the set value the thermostat relay is activated and the yellow
light goes on.
When the temperature goes above the max. regulation the
relay is disconnected and both lights go off.

Galvanic seperation:

The thermostat is designed so that the sensor circuit is
seperated galvanically from the heigh current part, which
means that the sensor part is regarded as a low current part.

Note!!!

When 

devireg

®

 316 is used as a gutter thermostat there

must be a connection between clamps 9 and 10. The outdoor
sensor must be mounted thus it is not exposed to direct
sunlight.

Summary of Contents for devireg 316

Page 1: ...devireg 316 Installation Instructions ...

Page 2: ...ff Itispossibletoadjustthehysteresisbetween0 2 Cand6 C If the temperature is set at 18 C and the hysteris at 3 C the thermostatwillswitchonat18 Candoffat21 C Difference Diff The heating system is connected when the reference temperature is between the regulated maximum and minimum temperature values See description of temperature regulation II When the temperature falls below the set value the the...

Page 3: ...commended for control of room temperature Temperature regulation II In this case the thermostat is to be used as a difference thermostat for regulation of snow and ice melting systems The range of the thermostat is decided by adjusting the temperature range 10 C to 50 C requested max temperature and the temperature range 10 C to 5 C requested min temperature If the heating system has to be connect...

Page 4: ...Cooling Heating ...

Page 5: ...asuring of sensor with ohmmeter should give a stable resistance compared to the ambient temperature see technical data chart If the sensor access is short circuited the indicator should turn off and the thermostat should be switched off If not the thermostat is defect When the mains voltage is disconnected the relay contact must be open Control of functioning If heat is not turned on by activating...

Page 6: ...C to 50 C 10ºC to 5 C NTC 15 kOhm at 25ºC 10 C 66 kOhm 0 C 42 kOhm 25 C 15 kOhm 50 C 6 kOhm Temperature range Working temperature Voltage Breaking power Night set back adjustable Differens adjustable Cap class Regulation range I range II Sensor type Sensing value Technical data ...

Page 7: ...ded in english or local language with the ISO code for your country in the upper left corner of the front page of the installation instruction in order to release the warranty The obligation of will be to repair or supply a new unit free of charge to the customer whitoutsecondary charges linked to repairing the unit In case of defective devireg thermostats reserves the right to repair the unit fre...

Page 8: ...nted to Name Phone Warranty Certificate Address Postalcode Please Observe In order to obtain the Warranty the following mustbecarefullyfilledin Seeotherconditions ontheoverleaf SuppliersStamp 08095512 02 02 ElectricalInstallationby Typeofthermostat Installationdate Productioncode ...