Smoke Alarm - SMSZB-120 – Technical manual
Develco Products A/S
Olof Palmes Allé 40
http://develcoproducts.com
DK-8200 Aarhus N
15
4.2.6
Time – Cluster id 0x000A
The Time cluster is a general cluster for time it is based on a UTC time in seconds since 0 hrs 0 mins 0 sec on 1st
January 2000. Refer to
[Z2]
for ZigBee specification of the time cluster.
The device will use this clusters as a client – provided that a suitable Time Server is available on the network
(most likely on the Gateway)
4.2.6.1
Attribute
Id#
Name
Type
Range
Man/Opt
Relevance and ref.
0x0000 Time
UTCTime
(Uint32)
Type range
M
The module will periodically
update its clock by
synchronizing through this
cluster
0x0001
TimeStatus
8 bit bitmap
00000xxx
M
4.3
Temperature Sensor Device – EP 0x26
4.3.1
Temperature Measurement – Cluster id 0x0402
The temperature measurement cluster is described in ZigBee Cluster Library Specification section 4.4
4.3.1.1
Attribute
Id#
Name
Type
Range
Man/Opt
Relevance and ref.
0x0000
MeasuredValue
Sint16 MinValue
to
MaxValue
M
0x0001
MinMeasuredValue
Sint16 0
M
0x0002
MaxMeasuredValue
Sint16 5000
M
4.3.1.1.1
MeasuredValue
Default reporting is set to
Min reporting interval: 60 sec
Max reporting interval: 600 sec
Reportable Change: 0.1 °C
If the temperature value is stable it will be send every 10 minutes.
If the temperature changes more than 0.1 °C it will be reported but not faster than every 1 minute since last
reporting value.