Trouble Shooting

 

The Inverter displays LED lights and/or screen displays to monitor the normal operation and fault 

conditions of the system. The occurrence of a problem within the system will usually be indicated by 
the  Inverter.  The  Inverter  user  manual  contains  a  trouble  shooting  chapter  which  will  explain  these 
lights and displays.

 

 

Please  Read  the  Trouble  Shooting  Chapter  carefully  and  then  precisely  follow  the  Instructions 

Given.  If  these  fail,  please  call 

9726879009 

immediately  and  we  can  assist  to  Locate  a  Qualified 

Technician to Resolve your Problem

PROBLEM 

POSSIBLE CAUSE 

RESOLUTION 

In day Hours with 
Good Solar 
Radiation. 

i) 

Array Voltage   Absent. 

ii) 

Array  is  at  extremely  Low/ 
High Voltage Condition. 

iii) 

Array breaker trip/off position

.

 

  Check Array Supply. 

  Check  Array  Supply  Low/High 

Voltage Condition. 

  Switch  On  Array  Breaker,  If  It 

Trip Contact us. 

Inverter is 
Supplying Power 
to Load But 
Power Import & 
Export is not 
Working. 

i) 

Grid Voltage absent. 

ii) 

Grid  is  Extremely Low/High  Voltage 

Condition. 

iii) 

Grid Breaker Trip/Off position. 

iv) 

Grid Contactor is not working. 

v) 

Grid Frequency is not in range. 

vi) 

No Sync-Conditions. 

  Check input Voltage, Check Grid 

& System Fuses. 

  Check  Grid  Supply  Low/High 

Voltage Condition. 

  Switch  on  Grid  Breaker,  If  It 

Trips Again, Contact us. 

  Check Grid Contactor coil Fuse. 

  Check  Grid  Frequency  Low  / 

High Condition. 

  Check Phase Rotation. 

Output Under 
Voltage 

i) 

  Output Short Circuit. 

ii) 

  Inverter Control Card Failed. 

iii) 

Driver Card Failed. 

iv) 

Driver Control Failed. 

v) 

   Filter Capacitor Failed. 

vi) 

No Feed Forward Signal. 

vii) 

Hall Device Failed. 

viii) 

IGBT Module Failed. 

  Check load is Proper or Not. 

  To  Reset  the  Fault  Press  Reset 

Switch on Front Mimic Display. If 
Fault Repeats Contact us. 

Output Over 
Voltage 

i) 

Loss of Control Feedback. 

ii) 

Inverter Control Card Faulty. 

  To  Reset  the  Fault  Press  Reset 

Switch on Front Mimic Display. If 
Fault Repeats Contact us. 

Inverter Over 
Temperature 

i) 

High Ambient Temp. 

ii) 

Output Overload. 

iii) 

Inverter Cooling Fan Failed. 

iv) 

Temp. Sensor Failed. 

v) 

   Inverter Control Card Failed. 

vi) 

Ventilation Inputs Blocked.  

  Check 

Room 

Ventilation 

is 

Proper or Not. 

  Reduce the Load. 

  Contact us. 

  Contact us. 

  Contact us. 

  Clean 

Ventilation 

Input 

by 

Blower Fan. 

DC Over Voltage 

i) 

Reverse Power Flow 

ii) 

Synchronization Failed. 

iii) 

Inverter Control Card Failed. 

  To  Reset  the  Fault  Press  Reset 

Switch on Front Mimic Display. If 
Fault Repeats Contact us. 

Wound 
Component OT 

i) 

High Ambient Temp. 

ii) 

Output overload 

iii) 

Wound  component  Cooling  fan 
Failed. 

iv) 

Temp. Sensor Failed. 

v) 

Inverter Card Failed. 

vi) 

Ventilation Inputs Blocked. 

  Check 

Room 

Ventilation 

is 

Proper  or Not. 

  Reduce the Load. 

  Contact us. 

  Contact us. 

  Contact us. 

  Clean 

Ventilation 

Input 

by 

Blower Fan. 

 

 

Summary of Contents for Solar

Page 1: ...Solar Power Owner s Manual DEVDEEP ELECTRICALS Roof Top Grid Connected Solar PV System ...

Page 2: ...uctions 5 Operating Safety Instructions 5 Trouble Shooting 6 Maintenance of Solar PV System Equipments 7 Important Reminder 8 Warranty 8 AccreditedInstallerDetails 9 Expected System Performance 9 Actual System Performance 9 Maintenance and Fault Log 10 Inverter Details 11 Array Details 11 Disclaimer 12 Table of Contents ...

Page 3: ...r DEVDEEP SOLAR strongly recommend that you avoid climbing onto the roof and use the services of a qualified professional who is trained in occupational health and safety procedures Shading of the solar panels will affect efficiency and performance Plant and tree growth that may cause shading at various times of the year should be monitored and dealt with as required Likewise leaves bird droppings...

Page 4: ...ion 3 Depending on Local Regulations Your Solar system may be connected to the grid on a Net Metering System With Net Metering only the Electricity not First consumed by the House will be Exported to the Grid If you have an Old Electro Mechanical Meter with the spinning disk this will need to be replaced with a Bi Directional Meter able to record the electricity you both import and export Your Ele...

Page 5: ...d if necessary call 9726879009 Immediately and we will diagnose your problem and send a technician to resolve it if necessary Operating Safety Instructions Do not Attempt to Service the system unless you are Fully Qualified to do so To service any Electrical connection you have MUST be a Licensed Electrician All Service work must be carried out in strict compliance with all Local and National Elec...

Page 6: ...Breaker If It Trips Again Contact us Check Grid Contactor coil Fuse Check Grid Frequency Low High Condition Check Phase Rotation Output Under Voltage i Output Short Circuit ii Inverter Control Card Failed iii Driver Card Failed iv Driver Control Failed v Filter Capacitor Failed vi No Feed Forward Signal vii Hall Device Failed viii IGBT Module Failed Check load is Proper or Not To Reset the Fault P...

Page 7: ...ture at the highest point of Tilt This minimum space is required to avoid shadow of one row of solar structure to fall on the row behind it There must not be any obstacles near to PV Module installation area So that shadow will affect the generation Do not step or walk on the Modules or else the warranty of the modules will be void During the generation hours there should not be any shadow reflect...

Page 8: ...s Manual in a Safe and Easily Locatable Place Together with all other documentation supplied with your system Warranty In the case of a service being required please make available all the documentation to the service technician Note that the manufacturers warranties may be voided if the system is serviced or interfered with by an unqualified person Your solar electric system comes with the follow...

Page 9: ...System Performance to be completed by accredited installer 1 Size of Solar Array in Kilowatts kW 2 Maximum AC output of Inverter in Kilowatts kW 3 Elevation angle Expected loss 4 Shading of solar array Expected loss 5 Expected Average Daily output of Solar Array in Kilowatt hours kWh 6 Location of Inverter 7 Location of PV array s Actual System Performance to be completed by owner Date of connecti...

Page 10: ... and Fault Log Please do not climb above 2 meters to maintain solar modules without observing all OH S regulations Use only clean water to clean solar modules no detergents or solvents Date Problem Remedy Electrician ...

Page 11: ...Model Size Array Details Module type Model SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN SN VOC ARRAY 1 VDC VOC ARRAY 2 VDC VMP ARRAY 1 VDC VMP ARRAY 2 VDC ...

Page 12: ...ectly This manual provides guidelines for Operation Maintenance DEVDEEP SOLAR is not responsible for any damages caused by using or installing our products be it Personal Injury Damage of Property Prosecution from a result of using our products legal fees or loss of earnings and whether the DEVDEEP SOLAR product was fitted correctly as per this Maintenance Guide or not DEVDEEP SOLAR www devdeepele...

Reviews: