30.1.20
Instruction manual dynamic switching accelerator SPEEDY V. 3.1
15
Deutschmann Automation GmbH & Co. KG
SPEEDY switching modes
5.4
Switching mode 3
Switching mode 3 was developed specifically for twin solenoids (actuating elements). If input 1
has no signal, output 2 is switched. If input 1 receives a signal, output 2 is deactivated first. After
deactivation, there is a pause **. Output 1 is then activated.
The situation is different if the signal at input 1 is cancelled. Output 1 is deactivated first, followed
by a pause **, after which (not before) output 2 is switched back on. Input 2 determines the dura-
tion of the pause **. The duration of the overexcitation pulse is set at inputs 3 and 4.
Picture 4:
Switching mode 3
Input 1
Output 1
Output 2
0 VDC
0 VDC
+UB
+24 VDC
+UB
0 VDC
Input 3
Input 4
Pulse
0 VDC
0 VDC
1 ms
+24 VDC
0 VDC
2 ms
0 VDC
+24 VDC
5 ms
+24 VDC
+24 VDC
10 ms
Input 2
Pause **
0 VDC
Pulse x 2
+24 VDC
Pulse x 1
** Pause: Period between de-energisation of solenoid 1 and energisation of solenoid 2 or vice
versa. It results from the overexcitation time (pulse) multiplied by 2 or 1.