background image

2.7

INSTALLATION OF
ACCESSORIES

WARNING

E

LECTRICAL SHOCK HAZARD

Turn OFF electrical power at the fuse box or ser-
vice panel before making any electrical connec-
tion and ensure that a proper ground connection
is made before connecting line voltage.
Failure to do so can result in death or bodily injury.

2.7.1

Humidifier and humidistat
connection

Fan Control Board terminals HUM1 (directly connected
internally to C on terminal block) and HUM2 (directly con-
nected internally to G on terminal block) are provided for
direct connections to the low-voltage control of a humidi-
fier through a standard humidistat (refer to Figure 11).

Figure 11: Standard humidistat connections

These terminals are energized with 24 VAC when

G thermostat signal is present. Alternately, the 24 VAC
signal may be sourced from the W1 and C terminal block
connections when electric heaters are used as a primary
heating source (refer to Figure 12).

Figure 12: Thermostat connections

2.7.2

Electronic Air Cleaner (EAC)
connections

Fan Control Board terminals AUX1 (directly connected
internally to C on terminal block) and AUX2 (directly con-
nected internally to G on terminal block) are provided for
direct connections to the low-voltage control of an elec-
tronic air cleaner. These terminals are energized with 24
VAC when G thermostat signal is present (refer to Figure
13).

Figure 13: Electronic air cleaner connections

2.7.3

Dehumidify capability with standard
humidistat connection

Latent capacities for systems using this unit are bet-
ter than average systems. If increased latent capacity is
an application requirement, the field wiring terminal block
provides a connection terminal (DH) for use of a standard
humidistat. The furnace control will detect the humidistat
contact opening on increasing humidity and reduce its
airflow to approximately 80% of nominal cooling mode
airflow. This reduction will increase the system latent
capacity until the humidity falls to a level which causes
the humidistat contact to close its contacts.
When the contact closes again, the airflows comes back
to 100% of the cooling airflow selected.

2.7.4

Use of a heat pump

When using a heat pump, a thermostat with dual fuel
option or a fossil fuel kit is required that prevents the op-
eration of the electric elements and the heat pump at the
same time. Refer to the instructions provided with the
thermostat or the “Fossil Fuel” kit for the proper wiring of
the furnace and the heat pump.
The simultaneous operation of the electric elements and
the heat pump will cause overheating of either unit. The
safety controls of the appliances will shut down the el-
ements or heat pump, since they are not designed to
function in this fashion.

3

OPERATION

3.1

START-UP

Before starting up the unit, be sure to check that the fol-
lowing items are in compliance:

1. The electrical installation and ventilation are con-

form;

2. The blower access door is in place and the blower

rail locking screws are well tightened;

3. The blower speed adjustments for heating and air

conditioning are appropriate and in accordance
with to the specifications in this manual;

4. The thermostat of the room is in heating mode and

is set higher than the ambient temperature;

5. The breakers on front panel are set on the “ON”

position.

To start the unit, turn the main electrical switch on.

3.2

USE OF MANUAL FURNACE
CONTROLS ON ADVANTAGE
FURNACE

When there is a demand for heat, the pilot light (L-1)
comes on. Refer to the wiring diagram.
When the “HI/LO” switch is put into the “LO” position, it
will shut down approximately half the elements.

However, it is important to put the switch back to the

8

Summary of Contents for SUPREME SUP A240V12 Series

Page 1: ...its controls Call a qualified service technician USE THE INFORMATION IN THIS MANUAL FOR THE IN STALLATION AND SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWN...

Page 2: ...mostat 9 3 3 6 Electric heating mode Communicating thermostat 9 3 3 7 Heat pump heating mode Modlating thermostat outdoor unit single stage 9 3 3 8 Heat pump heating mode Modulating thermostat outdoor...

Page 3: ...alified service technician immedi ately to assess the damage and to replace all criti cal parts that were in contact with water c Do not store gasoline or any other flammable sub stances such as paper...

Page 4: ...ample it is recommended to install the unit on a cement base 2 5 cm to 5 0 cm 1 to 2 thick In addition the heater should also be located close to the center of the air distribution system 2 2 CLEARANC...

Page 5: ...pted ground to minimize the risk of bodily harm A ground terminal is supplied with the control box for that purpose A connector is supplied on the ground terminal to ground an added accessory In the e...

Page 6: ...mode is comfort able and economical Generally speaking on a single stage thermostat a reading of the current must be taken with an ammeter as follows 1 Move the anticipator to its highest setting rend...

Page 7: ...d to operate prop erly with system components with which it is installed To successfully configure a system see information printed on circuit board label located next to select pins move the 6 select...

Page 8: ...t up cool down in conjunction with the airflow 3 0 0 No delay option Used for servicing unit or when a thermostat is utilized to perform delay func tions 4 ENH enhanced selection provides a 30 second...

Page 9: ...control will detect the humidistat contact opening on increasing humidity and reduce its airflow to approximately 80 of nominal cooling mode airflow This reduction will increase the system latent cap...

Page 10: ...o Y Y2 and R to O b Furnace delivers single stage cooling airflow 3 3 3 Cooling mode two stage First stage low cooling Thermostat closes cir cuits R to G R to O and R to Y1 Furnace delivers low stage...

Page 11: ...ir temperature from the supply air tempera ture If the temperature rise exceeds the temperature spec ified in Table 2 by 5 F 2 8 C move the AC HP CFM ADJUST black wire to high HI position If the exces...

Page 12: ...nt changes Dirty filters have an adverse ef fect on the performance of the central heating system 4 2 MOTOR LUBRICATION Do not lubricate the blower motor since it is permanently lubricated 5 FURNACE I...

Page 13: ...ected cooling delays Cooling 2 stages with Electric Heat Continous Fan G ON Fan ON at the selected continous fan CFM Fan switch ON OFF Fan OFF Thermostat calls for 1st stage Heat W1 ON Fan ON at 50 of...

Page 14: ...DH ON Compressor ON Fan ON after delays at 80 of the selected Cooling CFM OFF Compressor OFF Fan OFF after selected cooling delays Thermostat calls for 1st stage Heat Heat pump heating mode Y1 G ON Co...

Page 15: ...5 3 7 4 3 1 5 3 7 Electrical element 6 240V 208V Kw 4 3 1 5 3 7 Blower motor Consumption 240V 208V Amp Max 2 3 2 7 2 3 2 7 2 3 2 7 2 3 2 7 2 3 2 7 2 3 2 7 5 2 6 0 5 2 6 0 5 2 6 0 5 2 6 0 5 2 6 0 Heati...

Page 16: ...sides the back and below KOE Identical on the 2 sides Identique sur les 2 cot s KOE A 35mm 44mm 1 3 8 1 3 4 B 29mm 7 8 A B Identique sur les 2 cot s au dos et en dessous DNS1455 rev C 927mm 36 1 2 559...

Page 17: ...s 24VAC input to Y1 only Y Y2 not powered CONTINUOUS FAN CFM1 CFM1 CFM1 AC HP SIZE A C size CONTINUOUS FAN CONTINUOUS FAN CONTINUOUS FAN Selection TONS YELLOW wire position YELLOW wire position YELLOW...

Page 18: ...to Y1 only Y Y2 not powered CONTINUOUS FAN 24 VAC R input on G only CFM1 CFM1 CFM1 AC HP SIZE A C size CONTINUOUS FAN CONTINUOUS FAN CONTINUOUS FAN Selection TONS YELLOW wire position YELLOW wire pos...

Page 19: ...ON OFF DELAY Adjustment ON Delay OFF Delay WHITE wire position Time CFM Time 0 90 0 sec 100 90 sec 30 90 30 sec 100 90 sec 0 0 0 sec 0 sec ENH 30 sec 70 150 sec DELAY PROFILE FOR ELECTRIC HEATING MODE...

Page 20: ...Figure 16 Electrical diagram SUPREME Advantage ECM ELECTRICAL DIAGRAM DIAGRAMME LECTRIQUE ADVANTAGE AVANTAGE ECM 19...

Page 21: ...rev E 31 12 15 16 17 11 6 8 9 18 19 20 21 22 13 14 7 10 REV DESCRIPTION A C DATE PAR A Nouveau dessin 21963 2015 03 24 F H B Changement disjoncteur CQC 22327 2015 05 19 F H C Ajoute support de filtre...

Page 22: ...upreme 15kw 21 B04284 Electrical sequencer kit Supreme 10kw 22 B04350 02 Top door 23 B04349 Bottom door assembly 24 B04357 01 Blower assembly Supreme 10 25kw 1 2hp ECM 25 B04357 02 Blower assembly Sup...

Reviews: