Figure 8: 1-stage thermostat, electric heating and cooling 

application 

 

Figure 9: 2-stage thermostat, electric heating and air 

conditioning 

 

 

2.5.1-  Anticipator adjustment (if required) on thermostat 
equipped with heat anticipator adjustment 

 

Some thermostats are equipped with a heat anticipator that must 
be  adjusted  according  to  the  instructions  supplied.    This  is  to 
ensure that the heating mode is comfortable and economical. 

 

Generally speaking, on a single stage thermostat, a reading of 
the current must be taken with an ammeter as follows: 

1.  Move  the  anticipator  to  its  highest  setting,  rendering  it 

ineffective. 

2.  Remove  the  wire  from  the  W1  terminal  and  connect  an 

ammeter between the terminal and the wire. 

3.  Call for heat by raising the set point on the thermostat and 

allow the furnace to run for 3 to 4 minutes to reach its peak 
output. 

4.  Once the current has stabilized, a reading should be taken 

and the anticipator adjusted to that value.  If longer heating 
cycles  are  desired,  the  anticipator  can  be  set  to  a  higher 
value 

2.5.2-  Air ducts 

The  ducts  must  be  sized  such  a  way  as  to  accommodate  the 
specified airflow and the available static pressure.  Refer to the 
applicable local and/or national installation codes. 
 

Insulate  the  ducts  that  lead  through  non-heated  areas.    Use 
flexible  supply  and  return  air  connectors  to  avoid  the 
transmission of vibration.  To make the unit run even quieter, the 
installer should: 

a.  Use  two  elbows  between  each  outlet  and  the  supply  and 

return air plenum; 

b.  Cover the vertical sections of the supply and return air duct 

with soundproofing material; 

c.  Use baffles in short radius elbows; 

d.  Use flexible hangers to suspend the ducts. 

 
A heat pump or an air conditioner can be added to this furnace, 
in  either  the  supply  or  return  air  duct.    Carefully  follow  the 
instructions  provided  with  these  appliances  to  ensure  proper 
installation and hook-up to the electric furnace. Refrigerant and 
drainage  pipes  must  in  no  way  hinder  access  to  the  furnace 
panels. 

2.6-  SUPPLY AIR ADJUSTMENTS 

The  supply  air  must  be  adjusted  based  on  heating/air 
conditioning output and the static pressure of the duct system.  
For the desired airflow, refer to Table 1, as well as Table 3 and 
Table 4 for the airflow based on static pressure. 
 
For the adjustment of the airflow on heating mode, to obtain the 
temperature  rise  described  in  the  technical  specification  table 
(Table  2),  the  red  wire  must  be  positioned  on  the  terminal 
corresponding  to  the  LOW,  MED-LOW,  MED-HIGH  or  HIGH 
blower speed.  
 
For the adjustment of the airflow on air-cooling mode, to obtain 
a sufficient airflow (350 to 450 CFM per Ton), the blue wire must 
be positioned on the terminal corresponding to the LOW, MED-
LOW, MED-HIGH or HIGH blower speed.  

Blower  speeds  are  adjusted  in  factory  for  0.5  inch  static 
pressure. 

 

Table 1: Supply air adjustment on cooling mode

 

 

MOTOR HP 

COOLING 

CAPACITY 

(0.5 ‘’ w.c.) 

BLOWER SPEED 

(Motor 120V) 

BLOWER SPEED 

(Motor 240V) 

1/3 

1.5 

LOW 

LOW 

2.0 

MED-LOW 

LOW 

2.5 

MED-HIGH 

MED 

3.0 

HIGH 

HIGH 

1.0 

2.5 

LOW 

LOW 

3.0 

MED-LOW 

MED-LOW 

3.5 

MED-LOW 

MED-HIGH 

4.0 

MED-HIGH 

MED-HIGH 

5.0 

HIGH 

HIGH 

 

If heating and air-cooling speeds are the same, the red wire and 
the  blue  wire  can  be  connected  on  the  same  terminal  on  the 
motor. 

 

 

Summary of Contents for Supreme Advantage Series

Page 1: ...AGE PSC MOTOR Caution Do not tamper with the unit or its controls Call a qualified service technician INSTALLER SERVICE TECHNICIAN USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION AND SERVICING...

Page 2: ...emperature Rise Test 8 3 4 2 High limit verification 8 4 MAINTENANCE 8 4 1 AIR FILTER 8 4 2 MOTOR LUBRICATION 8 5 FURNACE INFORMATION 9 TABLES Table 1 Supply air adjustment on cooling mode 6 Table 2 T...

Page 3: ...Ask the technician installing your furnace to show and explain to you the following items i The main disconnect switch or circuit breaker ii The air filter and how to change it check monthly and clea...

Page 4: ...uitable ductwork 2 3 1 Upflow installation The return duct may be installed to the back the bottom on the left side or on the right side of the unit The supply duct shall be installed on the top of th...

Page 5: ...e terminal block on models over 25kW the installation must be performed with copper wire ONLY in order to comply with the Canadian electrical code The usage of an aluminum or copper wire is acceptable...

Page 6: ...the vertical sections of the supply and return air duct with soundproofing material c Use baffles in short radius elbows d Use flexible hangers to suspend the ducts A heat pump or an air conditioner c...

Page 7: ...eed adjustments for heating and air conditioning are appropriate and according to the specifications in this manual 4 The thermostat of the room is in heating mode and is set higher than the ambient t...

Page 8: ...not operate above the temperatures specified in the Technical Specifications Table 2 This is particularly important if a cooling coil or a heat pump has been installed in the ducts Hi Limit thermal p...

Page 9: ...er name and address START UP RESULTS Voltage Total current consumed by the elements Supply air temperature Return air temperature Supply air duct static pressure Return air duct static pressure Total...

Page 10: ...x 8 12 x 9 GENERAL INFORMATION 22 x 22 x 36 5 20 x 20 19 x 19 1 20 x 20 3 tons 5 tons Capacity 10 15 18 20 23 25 20 23 25 27 30 Power total 240V 208V Kw 10 7 5 15 11 3 18 13 5 20 15 23 17 3 25 18 8 2...

Page 11: ...al static pressure inche of W C Table 4 Airflow CFM SUPREME with 1HP motor SUPREME equipped with a 1 HP 120V blower motor 0 2 0 3 0 4 0 5 0 6 0 7 0 8 LOW 1 110 1 090 1 085 1 080 1 070 1 050 1 005 MED...

Page 12: ...12 Figure 12 Electrical diagram SUPREME Comfort PSC...

Page 13: ...13 Figure 13 Electrical diagram SUPREME Advantage PSC...

Page 14: ...14 Figure 14 Parts list SUPREME Comfort PSC...

Page 15: ...0 kW 23 B04356 04 Blower assembly 1hp 240V PSC Supreme 20 kW 24 Z01I036 Blower 112 9R Supreme 20 kW 25 Z01I035 Blower 112 8R Supreme 10 15 18 20 kW 26 B01889 Motor support band and legs 27 L06K004 Mot...

Page 16: ...16 Figure 15 Parts list SUPREME Advantage PSC...

Page 17: ...Blower assembly 1 3hp 120v PSC Supreme 10 15 18 20 23 25 kw 31 B04356 02 Blower assembly 1 3hp 240v PSC Supreme 10 15 18 20 23 25 kw 32 B04356 04 Blower assembly 1hp 240v PSC Supreme 20 23 25 27 30 k...

Reviews: