background image

 

PART 2 

OPERATION 

 

 

2.1) 

START-UP & ADJUSTMENTS 

 
For the start-up of your heating unit, please refer to the 
instruction  manual  supplied  with  it.  The  start-up  of  a 
system using a power venter is exactly the same as a 
system  without  a  power  venter.  The  power  venter  is 
merely replacing a chimney. 
 
 

2.1.1)  Draft adjustment 

 
The power venting system shall be adjusted by reading 
the  flue  draft  upstream  of  the  draft  regulator  and 
adjusting  this  regulator  with  the  draft  setting  specified 
below.  These  specifications  correspond  to  the heating 
unit instruction manuals. 
 
 

TABLE 3 

Draft adjustment 

Heating unit model 

Draft (" W.C.) 

AME, HME, AM(i), AM(i)T, AMP, OLS, 
OSR, OMP, HMT, HML and HM(i)-
1.35 USGPH and less 

-0.035 

HMD and HM(i)-1.50 USGPH and 
more 

-0.050 

LO-1MQH, LO-1M3M, FBR-1, MBP-U, 
CCC, MBP, BRF, CMO32, CMO50, 
30RB, 32E2, 50E2, IB-30, IB32-R and 
IB50-O 

-0.020 

LO-2M, BFF, MBP-2 and MBP-F 

-0.040 

 
 

2.2) 

VERIFICATIONS  AND  TESTS  AFTER 
START-UP 

 

 
The  following  tests  must  be  performed  after  the  start-
up to ensure safe, reliable and trouble free operation. 
 
 

2.2.1)  Ignition test 

 
The  installer  must  verify  if  the  ignition  of  the  burner  is 
smooth  when  the  heating  unit  operation  is  interrupted 
by  means  of  the  thermostat,  limit  control or  the power 
venter proving switch. If the ignition is not smooth, the 
burner should be readjusted as discussed earlier. 
 
 

 

2.2.2)  Proving switch test 

 
This  test  must  be  performed  to  verify  the  normal 
operation  of  the  venting  system  proving  switch.  Block 
the  discharge  of  the  power  venter  while  the  unit  is 
operating.  Once  the  discharge  is  completely  blocked, 
the  unit  must  stop.  After  removal  of  the  blockage, the 
unit  must  ignite  smoothly.  Should  the  proving  switch 
not  work  properly,  you  must  change  it.  This  proving 
switch  is  not  field  adjustable  and  must  be  replaced 
when working improperly. 
 
 

2.2.3)  Post-purge delay test 

 
To  test,  simply  let  the  unit  run  for  a  minimum  of  5 
seconds  and  then  stop  the  cycle.  The  burner  should 
stop  but  the  power  venter  should  continue  to  operate 
for another 5 minutes. 
 
 

2.2.4)  Back-flow damper interlock 

switch test 

 
Using  a  pair  of  pliers,  hold  the  shaft  of  the  damper  in 
place so the damper is blocked in the closed position. 
Then,  try  to  start  the  burner.  The  burner  should  not 
come  on  until  the  damper  is  released  from  its 
completely closed position. 
 
 
 

 
 
 
 
 
 
 

Summary of Contents for SMH-1-BR

Page 1: ...ied service technician Save these instructions for future reference Printed in Canada Printed on 100 recycled paper SIDEWALL VENTER Models SMH 1 DE SMH 6 DE SMH 3 DE SMH 4 DE SMH 5 DE SMH 1 BR SMH 4 B...

Page 2: ......

Page 3: ...reech of the heating unit and the power venter inlet This distance is the linear sum of all vertical and horizontal connecting pipes with a maximum of 4 90o elbows See Figure 1 Therefore the maximum e...

Page 4: ...ed between two buildings where their use is common to both buildings The vent terminal shall be installed such a way that the flue gases do not jeopardize people overheat combustible structures or ent...

Page 5: ...1 50 SWV 2M 2S SMH 4 DE Beckett or Riello HMS 027 to 035 6 0 65 to 0 85 SWV 1M 2S SMH 1 DE Beckett or Riello HMS 041 to 062 6 1 00 to 1 50 SWV 2M 2S SMH 4 DE Beckett or Riello AMP 075 to 105 5 0 50 to...

Page 6: ...inside wall as closely as possible to the location where the vent pipe enters this wall Secure the junction box to the wall with two screws ensuring that the pressure switch is vertical If the wall i...

Page 7: ...specified in Figures 5A to 5M With this arrangement the command to the power venting system will come from the heating unit through its operational control to the power venter motor When a steady stat...

Page 8: ...st The installer must verify if the ignition of the burner is smooth when the heating unit operation is interrupted by means of the thermostat limit control or the power venter proving switch If the i...

Page 9: ...m the vent before operation To access the blower wheels remove the fan motor assembly cover and remove the blower wheels by unscrewing the attachment to the blower 3 1 3 Pressure switch The pressure s...

Page 10: ...DNS 0225 Rev A DNS 0226 Rev A FIGURE 1 SMH system General arrangement FIGURE 2 Main system dimensions...

Page 11: ...11 DNS 0229 Rev A DNS 0227 Rev A DNS 0228 Rev A FIGURE 3 Location of the SMH system on the wall Installation on a COMBUSTIBLE wall FIGURE 4A Installation on a NON COMBUSTIBLE wall FIGURE 4B...

Page 12: ...12 DNS 0230 Rev C DNS 0397 Rev C FIGURE 5A AMI AMT IM and OLS 2 speeds Beckett or Riello AMT SM and OLS 2 speeds Beckett FIGURE 5B...

Page 13: ...13 DNS 0231 Rev C DNS 0232 Rev C FIGURE 5C AMI and HE 1 speed Beckett FIGURE 5D AMI and HE 1 speed Riello...

Page 14: ...14 DNS 0407 Rev C FIGURE 5E AMT SM and OSR 2 speeds Riello...

Page 15: ...15 FIGURE 5F AMP and OMB Riello...

Page 16: ...16 FIGURE 5G AMP and OMB Beckett DNS 0622 Rev A...

Page 17: ...17 FIGURE 5H FIGURE 5I DNS 0238 Rev B LO 1MQH LO 2M FBR 1 LO 1M3M MBP MBP F MBP 2 CCC and MBP U BRF and BFF DNS 0239 Rev B...

Page 18: ...18 FIGURE 5J FIGURE 5K DNS 0233 Rev D DNS 0234 Rev D FIGURE 5J HMT HML HMI and HMD with triple aquastat Beckett or Riello HMR HML HMT HMI and HMD with double aquastat Beckett...

Page 19: ...19 FIGURE 5L DNS 0235 Rev B DNS 0240 Rev C AME and HME Beckett FIGURE 5M Water heater CMO32 CMO50 30RB 32E2 50E2 IB 30 IB32 R and IB50 O Beckett...

Page 20: ...0 For SMH 4 SMH 5 and SMH 6 12 Cover support insulation B00733 13A Cover support B00705 For SMH 1 and SMH 3 13B Cover support B01074 For SMH 4 SMH 5 and SMH 6 14 Gasket outlet pipe B01150 Brown 1 15 G...

Reviews: