Dettson OMF154L20A Installation Instructions And Homeowner'S Manual Download Page 9

 

 

9

 

provided with the burner, the fresh-air supply kit or the side-
wall venting kit. 

 

2.9 OIL

 

TANK 

WARNING

 

 

Fire and explosion hazard. 

 

Use only approved heating type oil in this furnace. 
DO NOT USE waste oil, used motor oil, gasoline or 
kerosene. 

 

Use of these will result in death, bodily injury and/or 
property damage. 

 

 

Check your local codes for the installation of the oil tank and 
accessories. 

 

At the beginning of each heating season or once a year, check 
the complete oil distribution system for leaks. 

 

Ensure that the tank is full of clean oil. Use No.1 or No.2 
Heating Oil (ASTM D396 U.S.) or in Canada, use No.1 or No.2 
Furnace Oil. 

 

A manual shut-off valve and an oil filter shall be installed in 
sequence from tank to burner. Be sure that the oil line is clean 
before connecting to the burner. The oil line should be 
protected to eliminate any possible damage. Installations 
where the oil tank is below the burner level must employ a two-
pipe fuel supply system with an appropriate fuel pump. A rise 
of 2.4 m (8') and more requires a two stage pump and a rise 
greater than 4.9 m (16') an auxiliary pump. Follow the pump 
instructions to determine the size of pipe needed in relation to 
the rise or to the horizontal distance. 
 

2.10 DUCTING 

WARNING 

 

Poisonous carbon monoxide gas hazard. 

 

DO NOT draw return air from inside a closet or utility 
room. Return air MUST be sealed to the furnace casing. 

 

Failure to properly seal ducts can result in death, bodily 
injury and/or property damage. 

 

Installations in certain areas or types of structures will increase 
the exposure to chemicals or halogens that may harm the 
furnace. These conditions will require that only outside air be 
used for combustion : 
a. Commercial buildings; 
b. Buildings with indoor pools; 
c. Furnaces installed near chemical storage areas. 
 
The installation must carefully be verified to ensure that the 
combustion air comes from outside. 

 
 

2.10.1 Air 

filter 

 

A properly sized air filter must be installed on the return air 
side of the unit. Refer to the Technical Specifications, table 6, 
for the correct dimensions. Also refer to Section 2.2 and the 
instructions supplied with the filter. 

 

2.11 SUPPLY

 

AIR

 

ADJUSTMENTS

 

 

(4

 

SPEED

 

MOTORS) 

On units equipped with 4-speed blower motors, the supply 
air must be adjusted based on heating/air conditioning 
output and the static pressure of the duct system. For the 
desired air flow refer to the following table as well as the 
air flow tables based on static pressure in the Technical 
Specifications section of this manual. 

 

Table 1  -  Blower speed adjustments, 4-speed motor 

 

FURNACE 

APPLICATION 

HEATING OR A/C 

OUTPUT 

RECOMMENDED 
BLOWER SPEED 

0.90 USGPH 

MED-LOW 

HEATING 

1.10 USGPH 

MED-HIGH 

3.0 TONS 

LOW 

3.5 TONS 

MED-LOW 

4.0 TONS 

MED-HIGH 

A/C 

5.0 TONS 

HIGH 

 

To effect the adjustment, the RED (for heating) and BLUE 
(for cooling and heat pump) wires can be changed on the 
motor. Also, refer to the position of the wires on the 
electronic board of the unit and consult the wiring 
diagrams. If the heating and air conditioning speeds are 
the same, the RED wire must be moved to “UNUSED 
LEADS” on the electronic board and the jumper provided 
with the BLUE wire must be used between the “HEAT” 
and “COOL” terminals. 

 

The blower start/stop delays can be adjusted by 
positioning the DIP switches on the electronic board as 
shown in the following figures. For upflow installation, the 
recommended blower ON delay is 60 seconds and blower 
OFF delay 2 minutes. 
 
 

CAUTION

 

For horizontal and downflow installations only: 

Adjust the ON delay to 30 sec. 
Adjust the OFF delay to 4 min. 
For other adjustments, proceed with tests in order to avoid 
cycling. 
 

Figure 8  -   Blower Start/Stop Delays 

Board # 1158 

 

 
 

Summary of Contents for OMF154L20A

Page 1: ...FOR THE INSTALLATION SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE Attention Do not tamper w...

Page 2: ...NEY VENTING 8 2 8 COMBUSTION AIR SUPPLY AND VENTILATION 8 2 9 OIL TANK 9 2 10 DUCTING 9 2 11 SUPPLY AIR ADJUSTMENTS 4 SPEED MOTORS 9 2 12 SUPPLY AIR ADJUSTMENTS ECM VARIABLE SPEED MOTORS 10 2 13 INSTA...

Page 3: ...urnace Dimensions 18 Figure 10 Wiring diagram 4 speed motor PSC 19 Figure 11 Wiring diagram variable speed motor ECM 20 Figure 12 Parts list with 4 speed motor PSC 21 Figure 13 Parts list with variabl...

Page 4: ...formation such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform...

Page 5: ...designed for outdoor installation It must be installed in such a manner as to protect its electrical components from water Outdoor installation will lead to a hazardous electrical condition and to pre...

Page 6: ...ground to minimize the risk of bodily harm if ever an electrical problem develops A green ground screw is supplied with the control box for that purpose The appliance must be installed in accordance...

Page 7: ...lect nozzle sizes by working back from the desired flow rate at operating pressure and not the nozzle marking 2 5 2 Air and Turbulator Settings Before starting the burner for the first time adjust the...

Page 8: ...of the cool down cycle If the test is not in line with the above call a QUALIFIED SERVICE TECHNICIAN 2 8 COMBUSTION AIR SUPPLY AND VENTILATION WARNING Poisonous carbon monoxide gas hazard Comply with...

Page 9: ...indoor pools c Furnaces installed near chemical storage areas The installation must carefully be verified to ensure that the combustion air comes from outside 2 10 1 Air filter A properly sized air f...

Page 10: ...ier on the HUM terminal It supplies 120 VAC electric power when the burner is in operation A 24 VAC signal can also be supplied from the W and C terminals on the blower electronic board to activate a...

Page 11: ...ing drawn into the suction side of the oil piping and pump Slowly close and tighten the bleed screw Once closed the flame will light up 3 3 2 Pressure adjustment The oil pressure must be adjusted acco...

Page 12: ...duct just outside the range of radiant heat from the heat exchanger 0 3 m 12 from the plenum of the main take off is usually sufficient 4 The temperature rise is calculated by subtracting the return...

Page 13: ...exchanger and combustion chamber should be inspected to determine if replacement is required 8 After the cleaning replace the heat exchanger baffles flue collar plate and oil burner 9 Readjust the bu...

Page 14: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Am...

Page 15: ...Canadian regulation 86 7 85 3 86 7 85 3 AFUE From ASHRAE 103 standard and US regulation 86 3 85 0 86 3 85 0 Volts Hertz Phase Rated current Amps Minimum ampacity for w ire sizing Amps Max fuse size Am...

Page 16: ...ShortRun On Delay CFM Level Time Off Delay CFMLevel Time A 1 OFF 2 OFF 0 90 13 90 sec 31 30 sec 50 4 min B 1 ON 2 OFF 1 10 13 60 sec 31 30 sec 38 5 min C 1 OFF 2 ON ALL 13 90 sec 31 30 sec 56 5 min D...

Page 17: ...OF FURNACE 1 5 08 cm 2 2 54 cm 1 5 08 cm 2 BOTTOM FURNACE 2 2 54 cm 1 3 5 08 cm 2 4 BACK FURNACE OPPOSITE SIDE OF THE BURNER 1 7 62 cm 3 7 62 cm 3 7 62 cm 3 PLENUM OR HORIZONTAL WARM AIR DUCT WITHIN...

Page 18: ...18 Figure 9 Furnace Dimensions...

Page 19: ...19 Figure 10 Wiring diagram 4 speed motor PSC...

Page 20: ...20 Figure 11 Wiring diagram variable speed motor ECM...

Page 21: ...21 Figure 12 Parts list with 4 speed motor PSC B500111A...

Page 22: ...WIRE CHANNEL INT 30 B03829 BLOWER DIVIDER 31 B03838 BLOWER SLIDE One blower slide included 32 B03835 02 LATERAL BAFFLE 33 B03867 01 FILTER RACK KIT 34 B03828 FLOOR 35 B03855 02 SIDE PANEL ASSEMBLY LE...

Page 23: ...23 Figure 13 Parts list with variable speed motor ECM B50112A...

Page 24: ...NNEL INT 29 B03829 BLOWER DIVIDER 30 B03838 BLOWER SLIDE One blower slide included 31 B03835 02 LATERAL BAFFLE 32 B03867 01 FILTER RACK KIT 33 B03828 FLOOR 34 B03855 02 SIDE PANEL ASSEMBLY LEFT Panel...

Reviews: