11. These furnaces SHALL NOT be installed directly
on carpeting, tile, or any other combustible material
other than wood flooring.
12. Gas furnace manufactured on or after May 1, 2017
are not permitted to be used in Canada for heating
of buildings or structures under construction.
13. A gas fired furnace for installation in a residential
garage must be installed as specified in the WARN-
ING box below:
WARNING
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in per-
sonal injury, death and/or property damage.
When the furnace is installed in a residential
garage, the burners and ignitions sources must be
located at least 18 in. (457 mm) above the floor.
The furnace must be located or protected to avoid
damage by vehicles. When the furnace is installed
in a public garage, airplane hangar, or other build-
ing having a hazardous atmosphere, the furnace
must be installed in accordance with the NFPA
54/ANSI Z223.1-2009 or CAN/CSA B149.2-2010.
Do not install the furnace on its back or hang fur-
nace with control compartment facing downward.
Safety control operation will be adversely affected.
Never connect return air duct to the back of the
furnace.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in
personal injury or death.
The operation of ex-
haust fans, kitchen ventilation fans, clothes dry-
ers, attic exhaust fans or fireplaces could create a
NEGATIVE PRESSURE CONDITION at the furnace.
Make-up air MUST be provided for the ventilation
devices, in addition to that required by the fur-
nace.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system be-
ing placed into operation could result in carbon
monoxide poisoning or death. The following steps
shall be followed for each appliance connected to
the venting system being placed into operation,
while all other appliances connected to the vent-
ing system are not in operation:
1. Seal any unused openings in venting sys-
tem;
2. Inspect the venting system for proper size
and horizontal pitch, as required in the Na-
tional Fuel Gas Code, NFPA 54/ANSI Z223.1-
2009 and these instructions.
In Canada,
refer to CAN/CSA-B149.1-2010.
Determine
that there is no blockage or restriction, leak-
age, corrosion and other deficiencies, which
could cause an unsafe condition;
3. As far as practical, close all building doors
and windows and all doors between the
space in which the appliance(s) connected
to the venting system are located and other
spaces of the building;
4. Close fireplace dampers;
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on
any exhaust fans, such as range hoods and
bathroom exhausts, so they are operating at
maximum speed. Do not operate a summer
exhaust fan;
6. Follow the lighting instructions. Place the
appliance being inspected into operation.
Adjust the thermostat so appliance is oper-
ating continuously;
7. If improper venting is observed during any
of the above tests, the venting system must
be corrected in accordance with the National
Fuel Gas Code, NFPA 54/ANSI Z223.1-2009.
In Canada, refer to CAN/ CSA-B149.1-2010.
8. After it has been determined that the appli-
ance connected to the venting system prop-
erly vents when tested as outlined above, re-
turn doors, windows, exhaust fans, fireplace
dampers and any other gas-fired burning ap-
pliance to their previous conditions of use.
9
Summary of Contents for Chinook C105-M-V
Page 24: ...Figure 10 Typical gas pipe arrangement 23...
Page 27: ...Figure 11 Wiring Diagram 26...
Page 39: ...Figure 14 Wiring Diagram Modulating t stat 38...
Page 53: ...Table 17 CFM 52...
Page 54: ...Figure 15 Dimensional Drawing 53...
Page 55: ...14 PART LIST 54...
Page 56: ...Figure 16 Exploded view 1 55...
Page 57: ...Figure 17 Exploded view 2 56...
Page 59: ...Table 19 Parts list continued 58...
Page 60: ...Table 20 Parts list MS 59...