Table 15 – CFM C30-2-V - 0381124C
Dipswitch
Max ESP
1st stage
2nd stage
Temp.
Settings
"w.c.
heating
heating
rise °F
S4-3=OFF
A
1.6
413
590
45
S4-4=OFF
S4-3=ON
B
1.6
392
561
50
S4-4=OFF
S4-3=OFF
C
1.6
336
480
55
S4-4=ON
S4-3=ON
D
1.6
280
400
65
S4-4=ON
Dipswitch
Max ESP
1st stage
2nd stage
FAN ON
Settings
"w.c.
cooling
cooling
(G)
S3-1=OFF
A
1.0
800
1 000
440
S3-2=OFF
S3-1=ON
B
1.6
640
800
350
S3-2=OFF
S3-1=OFF
C
1.6
480
600
265
S3-2=ON
S3-1=ON
D
1.6
320
400
175
S3-2=ON
Table 16 – CFM C45-2-V - 0381125C
Dipswitch
Max ESP
1st stage
2nd stage
Temp.
Settings
"w.c.
heating
heating
rise °F
S4-3=OFF
A
1.6
480
685
58
S4-4=OFF
S4-3=ON
B
1.6
510
730
55
S4-4=OFF
S4-3=OFF
C
1.6
420
600
65
S4-4=ON
S4-3=ON
D
1.6
350
500
80
S4-4=ON
Dipswitch
Max ESP
1st stage
2nd stage
FAN ON
Settings
"w.c.
cooling
cooling
(G)
S3-1=OFF
A
1.0
800
1000
440
S3-2=OFF
S3-1=ON
B
1.6
640
800
350
S3-2=OFF
S3-1=OFF
C
1.6
480
600
265
S3-2=ON
S3-1=ON
D
1.6
320
400
175
S3-2=ON
Table 17 – CFM C60-2-V - 0381209C
Dipswitch
Max ESP
1st stage
2nd stage
Temp.
Settings
"w.c.
heating
heating
rise °F
S4-3=OFF
A
1.0
685
985
55
S4-4=OFF
S4-3=ON
B
1.0
820
1175
45
S4-4=OFF
S4-3=OFF
C
1.0
755
1085
50
S4-4=ON
S4-3=ON
D
1.0
720
1035
50
S4-4=ON
Dipswitch
Max ESP
1st stage
2nd stage
FAN ON
Settings
"w.c.
cooling
cooling
(G)
S3-1=OFF
A
1.0
1115
1400
700
S3-2=OFF
S3-1=ON
B
1.0
955
1200
600
S3-2=OFF
S3-1=OFF
C
1.0
800
1000
500
S3-2=ON
S3-1=ON
D
1.0
635
800
400
S3-2=ON
Table 18 – CFM C75-2-V - 0381210C
Dipswitch
Max ESP
1st stage
2nd stage
Temp.
Settings
"w.c.
heating
heating
rise °F
S4-3=OFF
A
1.0
820
1180
56
S4-4=OFF
S4-3=ON
B
1.0
834
1200
55
S4-4=OFF
S4-3=OFF
C
1.0
840
1210
55
S4-4=ON
S4-3=ON
D
1.0
810
1160
57
S4-4=ON
Dipswitch
Max ESP
1st stage
2nd stage
FAN ON
Settings
"w.c.
cooling
cooling
(G)
S3-1=OFF
A
1.0
1120
1400
435
S3-2=OFF
S3-1=ON
B
1.0
960
1203
375
S3-2=OFF
S3-1=OFF
C
1.0
800
1000
310
S3-2=ON
S3-1=ON
D
1.0
640
800
250
S3-2=ON
Table 19 – CFM C105-2-V - 0381315C
Dipswitch
Max ESP
1st stage
2nd stage
Temp.
Settings
"w.c.
heating
heating
rise °F
S4-3=OFF
A
1.0
1130
1590
58
S4-4=OFF
S4-3=ON
B
1.0
1280
1800
51
S4-4=OFF
S4-3=OFF
C
1.0
1170
1640
56
S4-4=ON
S4-3=ON
D
1.0
1100
1545
60
S4-4=ON
Dipswitch
Max ESP
1st stage
2nd stage
FAN ON
Settings
"w.c.
cooling
cooling
(G)
S3-1=OFF
A
1.0
1440
1800
900
S3-2=OFF
S3-1=ON
B
1.0
1275
1600
800
S3-2=OFF
S3-1=OFF
C
1.0
1120
1400
700
S3-2=ON
S3-1=ON
D
1.0
960
1200
600
S3-2=ON
Table 20 – CFM C120-2-V - 0381316B
Dipswitch
Max ESP
1st stage
2nd stage
Temp.
Settings
"w.c.
heating
heating
rise °F
S4-3=OFF
A
1.0
1400
2000
53
S4-4=OFF
S4-3=ON
B
1.0
1780
2540
42
S4-4=OFF
S4-3=OFF
C
1.0
1580
2260
47
S4-4=ON
S4-3=ON
D
1.0
1300
1860
57
S4-4=ON
Dipswitch
Max ESP
1st stage
2nd stage
FAN ON
Settings
"w.c.
cooling
cooling
(G)
S3-1=OFF
A
1.0
1600
2000
1000
S3-2=OFF
S3-1=ON
B
1.0
1440
1800
900
S3-2=OFF
S3-1=OFF
C
1.0
1270
1600
800
S3-2=ON
S3-1=ON
D
1.0
1115
1400
700
S3-2=ON
8.3
DELAY TO FAN OFF
The fan delay to off can be adjust using dipswitch S7-3 and
S7-4.
27