Dettson AMT098SD Installation Instructions And Homeowner'S Manual Download Page 7

 

 

7

 

k. 

Solvent based glue; 

l. 

Antistatic fabric softeners for clothes dryers; 

m.  Acid based masonry cleaning materials. 

2.8.2 

B

URNER WITH 

O

UTDOOR 

C

OMBUSTION 

A

IR 

K

IT 

Certain burners are designed to function with combustion air 
taken directly from the outside. Follow the instructions provided 
with the burner, the fresh-air supply kit or the side-wall venting 
kit.

 

2.9 OIL 

TANK 

WARNING

 

 

Fire and explosion hazard. 

 

Use only approved heating type oil in this furnace. 
DO NOT USE waste oil, used motor oil, gasoline or 
kerosene. 

 

Use of these will result in death, bodily injury and/or 
property damage. 

CAUTION 

 

When a 0.75 USGPH or smaller nozzle is used, a 10 micron or 
finer filter, must be installed on the oil supply line to the 
furnace inside the building where the unit is located. 

 

This is a requirement in order for the heat exchanger warranty 
to remain in force. 
Check your local codes for the installation of the oil tank and 
accessories. 

 

At the beginning of each heating season or once a year, check 
the complete oil distribution system for leaks. 

 

Ensure that the tank is full of clean oil. Use No.1 or No.2 
Heating Oil (ASTM D396 U.S.) or in Canada, use No.1 or No.2 
Furnace Oil. 
A manual shut-off valve and an oil filter shall be installed in 
sequence from tank to burner. Be sure that the oil line is clean 
before connecting to the burner. The oil line should be 
protected to eliminate any possible damage. Installations 
where the oil tank is below the burner level must employ a two-
pipe fuel supply system with an appropriate fuel pump. A rise 
of 2.4 m (8') and more requires a two stage pump and a rise 
greater than 4.9 m (16') an auxiliary pump. Follow the pump 
instructions to determine the size of pipe needed in relation to 
the rise or to the horizontal distance. 

2.10 DUCTING 

WARNING 

 

Poisonous carbon monoxide gas hazard. 

 

DO NOT draw return air from inside a closet or utility 
room. Return air MUST be sealed to the furnace casing. 

 

Failure to properly seal ducts can result in death, bodily 
injury and/or property damage. 

 

The ducting must be designed and installed according to 
approved methods, local and national codes as well as good 
trade practices.  

 

When ducting supplies air to a space other than where the 
furnace is located, the return air must be sealed and also be 
directed to the space other than where the furnace is located. 

 

2.10.1 

A

IR FILTER

 

 

A properly sized air filter must be installed on the return air 
side of the unit. Refer to the Technical Specifications, 
p.13, for the correct dimensions. Also refer to Section 2.3 
and the instructions supplied with the filter. 

2.10.2 

SUPPLY AIR ADJUSTMENT 

(4

 SPEED 

MOTOR

On units equipped with 4-speed blower motors, the supply 
air must be adjusted based on heating/air conditioning 
output and the static pressure of the duct system. For the 
desired air flow refer to the following table as well as the 
air flow tables based on static pressure in the Technical 
Specifications section of this manual. 
 

Table 1:Blower speed adjustments (heating mode, 4 

speed motor) 

HEATING 

CAPACITY 

(USGPH) 

STATIC 

PRESSURE 

(W.C.) 

RECOMMENDED 
BLOWER SPEED 

0.55 

0.25” MED-LOW 

0.55 

0.50” MED-LOW 

0.70 

0.25” MED-HIGH 

0.70 

0.50” HIGH 

 

Table 2:Blower speed adjustments (A/C mode, 4 

speed motor) 

A/C CAPACITY 

(TONS) 

RECOMMENDED 
BLOWER SPEED 

2.0 

MED-LOW 

2.5 

MED-HIGH 

3.0 

HIGH 

 

To effect the adjustment, the RED (for heating) and BLUE 
(for cooling and heat pump) wires can be changed on the 
motor. Also, refer to the position of the wires on the 
electronic board of the unit and consult the wiring 
diagrams. If the heating and air conditioning speeds are 
the same, the RED wire must be moved to “UNUSED 
LEADS” on the electronic board and the jumper provided 
with the BLUE wire must be used between the “HEAT” 
and “COOL” terminals. 

 

The blower start/stop delays can be adjusted by 
positioning the DIP switches on the electronic board as 
shown in the following figures. However, the 
recommended adjustments are 60 seconds blower ON 
delay and 2 minutes blower OFF delay. 

 

Figure 5:Blower "OFF" delay - Board #ST9103A 

 

Summary of Contents for AMT098SD

Page 1: ...Attention Do not tamper with the unit or its controls Call a qualified service technician INSTALLER SERVICE TECHNICIAN Use the information in this manual for the installation servicing of the furnace...

Page 2: ...JUSTMENTS HEATING MODE 4 SPEED MOTOR 7 TABLE 2 BLOWER SPEED ADJUSTMENTS A C MODE 4 SPEED MOTOR 7 TABLE 3 HEATING MODE 8 TABLE 4 AIR CONDITIONING MODE 8 TABLE 5 CFM ADJUSTMENT ALL MODES 8 TABLE 6 DELAY...

Page 3: ...formation such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform...

Page 4: ...so be located close to the centre of the air distribution system 2 1 1 INSTALLATION IN AN ENCLOSURE The unit can be installed in an enclosure such as a closet However 2 ventilation openings are requir...

Page 5: ...nozzle sizes by working back from the desired flow rate at operating pressure and not the nozzle marking 2 5 2 AIR AND TURBULATOR SETTINGS Before starting the burner for the first time adjust the air...

Page 6: ...k that the electrical outlet on the furnace designated to the BVSO is functional 1 Start up the burner 2 Remove the three pole plug from the BVSO outlet on the furnace 3 The burner must shut off immed...

Page 7: ...led to the furnace casing Failure to properly seal ducts can result in death bodily injury and or property damage The ducting must be designed and installed according to approved methods local and nat...

Page 8: ...24 VAC signal can also be supplied from the W and C terminals on the blower electronic board to activate a switching relay Also refer to the instructions supplied with the accessory 2 12 2 ELECTRONIC...

Page 9: ...of the oil piping and pump Slowly close and tighten the bleed screw Once closed the flame will light up 3 3 2 PRESSURE ADJUSTMENT The oil pressure must be adjusted according to the Technical Specifica...

Page 10: ...ed investigate for ductwork obstructions dirty or improper air filter improper firing caused by improper pump pressure or nozzle sizing 3 3 8 LIMIT CONTROL CHECK After operating the furnace for at lea...

Page 11: ...bly cover 3 Remove the cover 4 Remove the two screws holding the control box to the heat transfer tube assembly Sliding the control box in the appropriate direction will unlock it from the heat transf...

Page 12: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Am...

Page 13: ...stion air adjustment turbulator damper 0 3 5 1 5 25 0 3 5 1 5 25 Minimum and Maximum pump pressure PSIG 125 to 180 135 to 170 125 to 180 135 to 170 AFUE From CSA B212 standard and Canadian regulation...

Page 14: ...c 13 60 sec 38 3 min D 1 ON 2 ON All 13 30 sec 100 0 sec 100 2 min No adjustment required A C size PreRun On Delay CFM Level Time ShortRun On Delay CFM Level Time Off Delay CFM Level Time All No Delay...

Page 15: ...E XTE RNAL STATIC P RE SSURE WITH AIR FILTE R Table 10 Minimum clearances from combustible material LOCATION APP LICATION CLEARANCE S combustible ma terials RECOMMANDED ACCES S FO R SERVICE FURNACE 1...

Page 16: ...16 Figure 7 Furnace Dimensions...

Page 17: ...17 Figure 8 Wiring Diagram 4 Speed Motor PSC...

Page 18: ...18 Figure 9 Wiring Diagram Variable Speed Motor ECM...

Page 19: ...19 COMPONENTS AND REPLACEMENT PARTS...

Page 20: ...20 Figure 10 Parts List With 4 Speed motor PSC B50082E...

Page 21: ...B03589 01 SIDE PANEL INSULATION 26 B03559 01 SIDE BAFFLE 27 B03553 ELECTRICAL BOX SPACER 28 B03549 ELECTRICAL BOX 29 R02R008 HIGH LIMIT CTL205 30F 7 in 30 B03550 ELECTRICAL BOX COVER Panel only 31 B0...

Page 22: ...22 Figure 11 Parts List With variable speed motor ECM B50083E...

Page 23: ...03589 01 SIDE PANEL INSULATION 26 B03559 01 SIDE BAFFLE 27 B03553 ELECTRICAL BOX SPACER 28 B03534 ELECTRICAL BOX 29 R02R008 HIGH LIMIT CTL205 30F 7 in 30 B03550 ELECTRICAL BOX COVER Panel only 31 B031...

Page 24: ...Ne pas alt rer votre unit ou ses contr les Appeler un technicien qualifi INSTALLATEUR TECHNICIEN Utiliser les renseignements dans ce manuel pour l installation et l entretien de l appareil et garder...

Page 25: ...ALISATION OUVERTURE DE VENTILATION DANS LA PORTE DU PLACARD 4 FIGURE 2 BRANCHEMENT DU THERMOSTAT CHAUFFAGE ET CLIMATISATION UNIT AVEC MOTEUR 4 VITESSES 5 FIGURE 3 BRANCHEMENT DU THERMOSTAT CHAUFFAGE E...

Page 26: ...onduit comment le changer une fois par ann e iv Le filtre air comment le changer v rifier mensuellement et nettoyer ou changer si n cessaire g Avant d appeler pour le service prendre en note les rense...

Page 27: ...s doit tre utilis e 2 1 EMPLACEMENT MISE EN GARDE Risque d incendie ou d explosion L appareil doit tre install au niveau Ne jamais installer avec une inclinaison vers l avant Ne pas ranger ou utiliser...

Page 28: ...d origine de l appareil de chauffage central utilisez seulement du fil de cuivre r sistant la m me temp rature que les fils d origine 2 3 INSTALLATION DU THERMOSTAT L installation d un thermostat de...

Page 29: ...s avec le volet motoris Si cette fournaise ou d autres appareils ne sont pas ad quatement vacu s cela peut entra ner la mort ou des dommages corporels et ou mat riels Pour assurer un fonctionnement s...

Page 30: ...ner une flamme malpropre des odeurs dans la maison le refoulement des appareils de combustion et peut entra ner des naus es l asphyxie et ou la mort des occupants L appareil de chauffage central n ces...

Page 31: ...stribution d air conform ment aux m thodes approuv es et conforme aux codes locaux et nationaux Lorsque les conduits d alimentation d air transportent l air dans un autre espace que celui o la fournai...

Page 32: ...C 10 10 ON ON D N A 0 Table 6 Ajustement des d lais en mode chauffage SW4 Delay D lai Position interrupteurs DIP 1 2 POSITION Puissance USGPH OFF OFF A 0 70 ON OFF B 0 55 OFF ON C 0 55 ON ON D ALL Po...

Page 33: ...s et selon les sp cifications de ce manuel 8 Les d lais de d part et d arr t du ventilateur sont r gl s de fa on satisfaisante 9 Le thermostat de la pi ce est en mode chauffage et est r gl une temp ra...

Page 34: ...age central installer le r gulateur de tirage barom trique fourni avec l appareil Pour que ce r gulateur fonctionne correctement monter les goupilles pins l horizontale et le devant du r gulateur la v...

Page 35: ...e de l unit effectuer une v rification compl te de la combustion apr s chaque entretien annuel Ne pas tenter de r parer l unit ou les contr les de l appareil Appeler un technicien qualifi Avant d appe...

Page 36: ...et fixer le bo tier de commande l aide des 2 vis qui avait t enlev es l tape 4 8 Remettre en place le couvercle de l ensemble avec les vis enlev es l tape 2 9 Remettre l alimentation lectrique 4 3 NE...

Page 37: ...se du technicien de service R SULTAT DU TEST DE MISE EN MARCHE Gicleur Pression lb po 2 Ajustements du br leur Bande principale Bande fine Position de la t te CO2 Indice de fum e Bacharach Temp rature...

Page 38: ...partir du standard CSA B212 et des lois canadiennes 86 1 85 0 86 1 85 0 AFUE partir du standard ASHRAE 103 et des lois am ricaines 85 7 85 0 85 7 85 0 Volts Hertz Phase Consommation Amp Amp minimum p...

Page 39: ...19 60 sec 38 3 min C 1 OFF 2 ON 0 55 13 60 sec 13 60 sec 38 3 min D 1 ON 2 ON All 13 30 sec 100 0 sec 100 2 min Pas d ajustement requis Capacit climatisation PreRun D lai On Niveau PCM Temps ShortRun...

Page 40: ...SSE AMT098 PRESS ION STATIQ UE EXTERNE AVE C FILTRE AIR Table 10 D gagement minimum mat riaux combustibles EMPLACEMENT APPLICATION D G AGEMENTS m at riaux combustibles ACC S RE COMMAND P OUR L ENTRETI...

Page 41: ...18 Figure 7 Dimensions de la fournaise...

Page 42: ...____________________________________________________________________________________ 19 Figure 8 Diagramme lectrique Moteur 4 vitesses PSC...

Page 43: ...20 Figure 9 Diagramme lectrique Moteur vitesse variable ECM...

Page 44: ...____________________________________________________________________________________ 21 COMPOSANTES ET PI CES DE REMPLACEMENT...

Page 45: ...22 Figure 10 Liste de pi ces Avec moteur 4 vitesses PSC B50082E...

Page 46: ...olation et d flecteur 25 B03589 01 ISOLATION PANNEAU DE COTE 26 B03559 01 DEFLECTEUR LATERAL 27 B03553 ESPACEUR DE BOITE ELECTRIQUE 28 B03549 BOITE ELECTRIQUE 29 R02R008 CONTR LE HAUTE LIMITE L205 30...

Page 47: ...24 Figure 11 Liste de pi ces Avec moteur vitesse variable ECM B50083E...

Page 48: ...rend panneau et isolation et d flecteur 25 B03589 01 ISOLATION PANNEAU DE COTE 26 B03559 01 DEFLECTEUR LATERAL 27 B03553 ESPACEUR DE BOITE ELECTRIQUE 28 B03534 BOITE ELECTRIQUE 29 R02R008 CONTR LE HAU...

Reviews: