background image

 

 

2

 

 

 

TABLE OF CONTENTS

 

 

1.

 

SAFETY REGULATIONS .......................................... 3

 

1.1 SAFETY 

LABELING 

AND WARNING SIGNS ........................ 3 

1.2 IMPORTANT 

INFORMATION .................................................. 3 

1.3          DETECTION SYSTEMS.............................................................. 3 
1.4          DANGER OF FREEZING............................................................ 3 

2. INSTALLATION.............................................................. 4

 

2.1 

POSITIONING THE FURNACE ................................................. 4 

2.1.1 Installation 

in an enclosure ................................................. 4 

2.2 CONFIGURATIONS.................................................................... 4 

2.2.1 Upflow 

Installation ............................................................. 4 

2.2.2 Downflow 

Installation......................................................... 5 

2.3 ELECTRICAL 

SYSTEM.............................................................. 5 

2.4 

INSTALLATION OF THE THERMOSTAT............................... 5 

2.5 INSTALLATION 

OF THE BURNER.......................................... 6 

2.5.1 Nozzles ................................................................................ 6 
2.5.2 

Air and Turbulator Settings................................................. 6 

2.5.3 

Post purge delay adjustment ............................................... 6 

2.6 VENTING ..................................................................................... 6 

2.6.1 Masonry 

chimney................................................................ 7 

2.6.2 Factory 

Built Chimneys ...................................................... 7 

2.6.3 Draft 

Regulator.................................................................... 7 

2.7 

BLOCKED VENT SHUT-OFF DEVICE (BVSO) FOR 

 CHIMNEY 

VENTING ................................................................. 7 

2.8 COMBUSTION 

AIR 

SUPPLY AND VENT. .............................. 7 

2.8.1 Contaminated 

Combustion Air ........................................... 7 

2.8.2 

Burner with Outdoor Combustion Air Kit .......................... 8 

2.9 OIL 

TANK .................................................................................... 8 

2.10 DUCTING ..................................................................................... 8 
2.11 

SUPPLY AIR ADJUST. (4 SPEED MOTORS) .......................... 8 

2.12 

SUPPLY AIR ADJUST.(ECM VAR.SP. MOTORS) .................. 9 

2.13 

INSTALLATION OF ACCESSORIES........................................ 9 

2.13.1 Humidifier 

(HUM) .............................................................. 9 

2.13.2 Electronic 

Air 

Cleaner (EAC)............................................. 9 

2.13.3 

Air Conditioner (or Heat Pump) ....................................... 10 

3

 

OPERATION .............................................................. 10

 

3.1 START-UP .................................................................................. 10 
3.2 

OPERATING SEQUENCE OIL HEATING MODE................. 10 

3.3 CHECKS 

AND 

ADJUSTMENTS.............................................. 10 

3.3.1 Purging 

the oil line ............................................................ 10 

3.3.2 Pressure 

adjustment........................................................... 10 

3.3.3 Combustion Check ............................................................ 11 
3.3.4 Draft 

Regulator adjustment ............................................... 11 

3.3.5 Overfire 

pressure test ........................................................ 11 

3.3.6 

Vent Temperature Test...................................................... 11 

3.3.7 

Supply Air Temperature Rise Test.................................... 11

 

3.3.8

 

Limit Control Check ......................................................... 11

 

3.3.9 Restart 

after 

Burner Failure............................................... 11 

4

 

MAINTENANCE........................................................ 12

 

4.1 

CLEANING THE HEAT EXCHANGER

.................................. 12

 

4.2 

CLEANING THE BLOCKED VENT SHUT-OFF DEVICE 

 (BVSO)........................................................................................ 12 
4.3 CLEANING

 

OF

 

THE

 

BURNER

 

HEAD..................................... 12 

4.4 CHANGING 

THE NOZZLE ...................................................... 12 

4.5 CHANGING 

THE 

OIL FILTER ................................................ 12 

4.6 CHANGING 

THE 

AIR FILTER ................................................ 12 

5

 

FURNACE INFORMATION .................................... 13

 

 

 
 

TABLES 

 

Table 1: Blower speed adjustments (4-speed motors)........................8 

Table 2: Supply air adjustments, ECM variable speed motors, 

heating mode.............................................................................9 

Table 3: Supply air adjustments, ECM variable speed motors, 

air conditioning mode ...............................................................9 

Table 4: CFM adjustments, all modes ...............................................9 

Table 5: Delay adjustments - heating mode.......................................9 

Table 6: Technical Specifications....................................................14 

Table 7: Airflow data, models with 1/2 HP ECM motors................15 

Table 8: Airflow data, models with 1/3 HP PSC motors .................16 

Table 9: Minimum clearances from combustible materials .............16 

Table 10: Parts list with 4-speed motor (PSC).................................21 

Table 11: Parts list with variable speed motor (ECM).....................23 

 

FIGURES 

 

Figure 1: Location and dimensions of ventilation air 

openings in a closet door ................................................ 4

 

Figure 2: Upflow installation.................................................. 4

 

Figure 3: Downflow installation ............................................. 5

 

Figure 4: Horizontal installation ............................................. 5

 

Figure 5: Thermostat wiring, heating and air conditioning 

with 4-speed motor ......................................................... 5

 

Figure 6: Thermostat wiring heating and air conditioning 

with ECM variable speed motor ..................................... 6

 

Figure 7: Thermostat wiring, heating and air cond. heat 

pump with ECM v. speed motor ..................................... 6

 

Figure 8: Blower start/stop delays .......................................... 9

 

Figure 9: Furnace dimensions............................................... 17

 

Figure 10: Wiring diagram, 4-speed motor (PSC)................ 18

 

Figure 11: Wiring diagram, variable speed motor (ECM).... 19

 

Figure 12: Parts list with 4-speed motor (PSC) .................... 20

 

Figure 13: Parts list with variable speed motor (ECM) ........ 22

 

 

 

 

 
 

Summary of Contents for AMP098SD

Page 1: ...ard Sherbrooke Qc Canada J1L 1V8 Manufactured by Dettson Industries Inc Attention Do not tamper with the unit or its controls Call a qualified service technician INSTALLER SERVICE TECHNICIAN Use the information in this manual for the installation servicing of the furnace and keep the document near the unit for future reference HOMEOWNER Please keep this manual near the furnace for future reference...

Page 2: ...1 3 3 9 Restart after Burner Failure 11 4 MAINTENANCE 12 4 1 CLEANING THE HEAT EXCHANGER 12 4 2 CLEANING THE BLOCKED VENT SHUT OFF DEVICE BVSO 12 4 3 CLEANING OF THE BURNER HEAD 12 4 4 CHANGING THE NOZZLE 12 4 5 CHANGING THE OIL FILTER 12 4 6 CHANGING THE AIR FILTER 12 5 FURNACE INFORMATION 13 TABLES Table 1 Blower speed adjustments 4 speed motors 8 Table 2 Supply air adjustments ECM variable spee...

Page 3: ...hould be installed in your residence and properly maintained to warn early on of a potentially dangerous fire Also the house should be equipped with approved and properly maintained fire extinguishers Non observance of the safety regulations outlined in this manual will potentially lead to consequences resulting in death serious bodily injury and or property damage a It is the homeowner s responsi...

Page 4: ...n code for oil burning equipment ANSI NFPA 31 Installation of oil burning equipment ANSI NFPA 90B Warm air heating and air conditioning systems ANSI NFPA 211 Chimneys Fireplaces Vents and solid fuel burning appliances ANSI NFPA 70 National Electrical Code CSA C22 1 Canadian Electrical Code or CSA C22 10 Only the latest issues of these codes may be used 2 1 POSITIONING THE FURNACE WARNING Fire and ...

Page 5: ...e manner regardless of the discharge position of the furnace Refer to Figure 4 for additional details 2 3 ELECTRICAL SYSTEM CAUTION The exterior of the unit must have an uninterrupted ground to minimize the risk of bodily harm if ever an electrical problem develops A green ground screw is supplied with the control box for that purpose The appliance must be installed in accordance with the current ...

Page 6: ...instructions in this section Failure to properly vent this furnace can result in in death bodily injury and or property damage To ensure the safe and proper functioning of an oil furnace it must always be connected to a flue with sufficient draft or to an approved side wall venting system In addition it is strongly recommended to perform a complete inspection of all the existing venting systems No...

Page 7: ...FF DEVICE BVSO FOR CHIMNEY VENTING Refer to oil furnace installation codes relative to combustion and ventilation air requirements Consult Section 2 1 in this manual specifically for units installed in an enclosed space CAUTION It is imperative that this device be installed by a qualified service technician Home air exhausters are common Bathroom and kitchen fans power vented clothes dryers and wa...

Page 8: ...table as well as the air flow tables 7 and 8 based on static pressure finer filter must be installed on the oil supply line to the furnace inside the building where the unit is located This is a requirement in order for the heat exchanger warranty to remain in force Check your local codes for the installation of the oil tank and accessories Table 1 Blower speed adjustments 4 speed motors At the be...

Page 9: ... 1 2 POSITION USGPH OFF OFF A 0 70 ON OFF B 0 60 OFF ON C 0 50 ON ON D ALL 2 13 INSTALLATION OF ACCESSORIES WARNING Electrical shock hazard Turn OFF electrical power at the fuse box or service panel before making any electrical connections and ensure a proper ground connection is made before connecting line voltage Failure to do so can result in death or bodily injury 2 13 1 Humidifier HUM The 120...

Page 10: ...depends on the adjustments that were made on the electronic board that controls the blower Refer to Sections 2 11 and 2 12 as well as the CFM tables 7 and 8 for more details Note A detailed operating sequence of the oil burner is outlined in the instructions provided with the burner 3 3 CHECKS AND ADJUSTMENTS 3 OPERATION 3 3 1 Purging the oil line 3 1 START UP Open the bleed port screw and start t...

Page 11: ...s taken and make note of it Example 13 8 of CO or 2 5 of O 2 2 5 Adjust the burner air setting to obtain a CO2 reading 1 5 lower or a O2 reading 2 0 higher than the reading associated with the trace of smoke Example 12 3 of CO or 4 5 of O 2 2 3 3 8 Limit Control Check 6 This method of adjusting the burner will result in clean combustion Bacharach smoke scale between 0 and a trace and ensure the pr...

Page 12: ...o the unit 5 If ignition does not occur turn off the disconnect switch and call a qualified service technician 4 3 CLEANING OF THE BURNER HEAD When ordering replacement parts please specify the complete furnace model number and serial number Once annually remove the retention head and electrodes from the drawer assembly and remove all foreign matter if necessary Also clean the extremity of the bur...

Page 13: ...rvice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure Lb in 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Ambient temperature F Chimney draft W C Overfire draft W C Test performed by ...

Page 14: ...PSIG 155 145 135 155 145 Combustion air adjustment turbulator damper 0 1 50 0 2 1 2 25 0 1 50 0 2 AFUE From CSA B212 standard and Canadian regulation 85 6 85 3 84 0 85 6 85 3 AFUE From ASHRAE 103 standard and US regulation 85 1 85 0 83 3 85 1 85 0 Volts Hertz Phase Rated current Amps Minimum ampacity for wire sizing Amps Max fuse size Amps Control transformer VA External control power available He...

Page 15: ...2 ON 0 50 13 60 sec 13 60 sec 38 3 min D 1 ON 2 ON All 13 30 sec 100 30 sec 100 2 min No adjustment required A C size PreRun On Delay CFM Level Time ShortRun On Delay CFM Level Time Off Delay CFM Level Time All No delay No delay 100 90 sec PreRun and ShortRun are the periods of time when the blower starts at very low CFM to minimize the distribution of cool air in the system and then runs up to no...

Page 16: ...F FURNACE 1 5 08 cm 2 2 54 cm 1 5 08 cm 2 BOTTOM FURNACE 2 Ø 2 54 cm 1 3 5 08 cm 2 4 BACK FURNACE OPPOSITE SIDE OF THE BURNER 1 7 62 cm 3 2 54 cm 1 7 62 cm 3 PLENUM OR HORIZONTAL WARM AIR DUCT WITHIN 6 ft OF FURNACE 2 5 08 cm 2 5 08 cm 2 5 08 cm 2 FURNACE 2 N A 5 08 cm 2 N A FLUE PIPE AROUND FLUE PIPE 22 86 cm 9 22 86 cm 9 22 86 cm 9 FRONT FURNACE BURNER SIDE 1 45 72 cm 18 45 72 cm 18 45 72 cm 18 ...

Page 17: ...Figure 9 Furnace dimensions 17 ...

Page 18: ...Figure 10 Wiring diagram 4 speed motor PSC 18 ...

Page 19: ...Figure 11 Wiring diagram variable speed motor ECM 19 ...

Page 20: ...Figure 12 Parts list with 4 speed motor PSC 20 B50064H ...

Page 21: ...LOWER SLIDE One slide included 34 B03441 BLOWER DIVIDER 35 B03451 REAR BAFFLE 36 B03427 REAR PANEL ASSEMBLY Panel insulation and baffles included 37 B03471 REAR PANEL INSULATION 38 B03457 01 ELECTRICAL KIT BLOWER 39 L01I001 CAPACITOR 5MF 40 B01024 CAPACITOR HOLDER 41 B03456 ELECTRICAL KIT BOARD 42 R99G004 ELECTRONIC BOARD UTEC 1158 110 43 B03440 ELECTRICAL BOX 44 L01F009 TRANSFORMER 120 24Volt 40V...

Page 22: ...Figure 13 Parts list with variable speed motor ECM 22 B50074H ...

Page 23: ...0513 BLOWER SLIDE One slide included 33 B03441 BLOWER DIVIDER 34 B03451 REAR BAFFLE 35 B03427 REAR PANEL ASSEMBLY Panel insulation and baffle included 36 B03471 REAR PANEL INSULATION 37 B03242 ELECTRONIC KIT BLOWER 38 B03243 ELECTRICAL KIT BLOWER 39 B03456 ELECTRICAL KIT BOARD 40 R99G003 ELECTRONIC BOARD UTEC 1168 41 B03440 ELECTRICAL BOX 42 L01F009 TRANSFORMER 120 24Volt 40VA 43 B03438 SUPPORT EL...

Reviews: