APPENDIX A - FACTORY MUTUAL RESEARCH (FMR)

APPROVAL DESCRIPTION

APPROVAL

Models U7652B (relay output) and U7652C (relay or 4-20 ma output) with aluminum or stainless steel enclosure
and 1/2-inch NPT conduit entries (M25 conduit entry may be used in non-North American applications).  For 18-
32 vdc operation through an approved control panel that provides separate circuits for power and alarm initia-
tion.

• Automatic Fire Alarm Signaling Performance verified per FM3260.

• Explosionproof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per FM 3615.

• Dust-ignitionproof for Class II/III, Div. 1, Groups E, F, and G Hazardous (Classified) Locations per FM 3615.

• Non-incendive for Class I, Division 2, Groups A, B, C and D (T4A);  Class II/III, Division 2, Groups F and G

(T4A) Hazardous (Classified) Locations per FM 3611.

• Ambient Temperature Limits –40°C to +75°C.

• Enclosure Rating NEMA/Type 4X per NEMA 250.

• Performance verified Optical Integrity (

oi

).

• The following performance criteria was verified by FMR using IR Module DE 5400-001 and UV Module

DE1888:

Response Characteristics

Angle of View

–45 to +45 off centerline in vertical and horizontal planes.

False Alarm Immunity

• Direct Sunlight

• A 150 watt incandescent lights at 2 ft. (0.6 m).

• Two 60 watt fluorescent at 2 ft. (0.6 m).

• A 500 watt halogen lamp at 4 ft. (1.2 m).

• The radiation produced by a Miller Dial-Arc 250-P arcwelder at 10 ft. (3.0 m), set at 50 amps with 1/8 inch

Type 601 welding rod.

• Vibration immunity for vertical displacement of 0.02 inches (0.5 mm) at a frequency of 10 to 30 Hz for 4 hours.

• Radio frequency interference (RFI) immunity at 12 inches to 155 MHz and 450 MHz with radiation power levels

of 5.0 Watts.

Options

Model Q9001G Swivel Mounting Bracket.

Time Delay

Fuel

Size

Distance

Average Response Time

0.5 sec.

Gasoline

1 ft x 1 ft (0.3 m x 0.3 m)

50 ft (15 m)

within 2 sec.

3 sec.

Gasoline

1 ft x 1 ft (0.3 m x 0.3 m)

50 ft (15 m)

within 10 sec.

0.5 sec.

JP-4

2 ft x 2 ft (0.6 m x 0.6 m)

100 ft (30.5 m)

within 2 sec.

0.5 sec.

JP-4

4 ft x 4 ft (1.2 m x 1.2 m)

150 ft (45.7 m)

within 2 sec.

0.5 sec.

JP-4

10 ft x 10 ft (3.0 m x 3.0 m)

150 ft (45.7 m)

within 2 sec.

Summary of Contents for U7652

Page 1: ...tions 95 8385 06 Unitized UV IR Flame Detector U7652 Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829 8750 3 01 95 8...

Page 2: ...7 Figure 7 U7652B Wiring Terminal Configuration 7 Figure 8 Wiring Terminal Configuration for U7652C with Auxiliary Relay 7 Figure 9 Wiring Terminal Configuration for U7652C with 4 to 20 ma Output 8 F...

Page 3: ...ouch the connector circuit board or electronic components 4 Alarm and extinguishing devices should be disconnected before performing the manual oi test DESCRIPTION The U7652 UV IR Flame Detector is an...

Page 4: ...ormally de energized no fire Energizes upon detection of fire Field programmable for either latching or non latching operation Fault relay has SPST normally open contacts Normally energized no fault D...

Page 5: ...is 10 degrees and were set for a 0 5 second time delay Response is dependent on the type of fuel the temperature of the fuel and the time required for the fire to build As with all fire tests results...

Page 6: ...erence by EMI and RFI It will not respond to a 5 watt walkie talkie at a dis tance of greater than 1 foot VIEWING WINDOWS Keep the detector viewing windows as free of con taminants as possible in orde...

Page 7: ...IREMENTS Use 16 to 22 gauge 1 5 to 0 5 mm2 cable A minimum input voltage of 18 vdc must be present at the detector Use cable that is suitable for the installation environ ment harsh environments requi...

Page 8: ...SWIVEL CONDUIT SEAL A1478 Figure 3 Vertical Mounting B1437 TERMINAL BLOCK AUXILIARY RELAY OPERATION W4 LATCH NON LATCH W1 ALARM RESPONSE W3 oi TEST W2 CONNECTOR SCREWS 3 MOTHERBOARD ASSEMBLY Figure 4...

Page 9: ...LT RELAY IS SHOWN DE ENERGIZED BUT IS NORMALLY ENERGIZED WITH POWER APPLIED AND NO FAULTS PRESENT 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 FIRE FAULT CON 1 CON 2 AUX AUX Figure 8 Wiring Terminal Configurat...

Page 10: ...CON 1 CON 1 CON 2 CON 2 SPARE FAULT RELAY 0 47 F 400 VOLT CAPACITOR Figure 10 A Typical System Using U7652B Detectors FAULT RELAY IS SHOWN DE ENERGIZED BUT IS NORMALLY ENERGIZED WITH POWER APPLIED AND...

Page 11: ...used pour the conduit seals and allow them to dry 7 Re install the junction box cover ensuring that the 9 pin D connectors are properly mated between the cover and the circuit board inside the enclo s...

Page 12: ...e unit is programmed for non latch ing operation the Fire relay will become de ener gized and the LEDs will turn off when the UV IR source is removed If the unit is programmed for latching operation i...

Page 13: ...und faults power supply transients and lightning strikes All Det Tronics systems are designed with extensive protec tion circuitry however damage can still occur The following field test procedure has...

Page 14: ...background Background radiation as such does not cause a problem Radiation UV or IR radiation is indicated with the detector in most applications unless both UV and by steady illumination of the flick...

Page 15: ...proper operation is observed If abnormal operation is evident start with the sensor exchange first then the detector cover assembly and finally the detector mother board assembly Always remove system...

Page 16: ...e sensor housing Hand tighten the sensor housing into the base until the O ring is fully seated 8 Re install the cover locking device if used 9 Inspect the viewing windows and oi rings and clean if ne...

Page 17: ...to the detector terminal blocks 8 Apply a small amount of lubricant to each of the six screws on the junction box cover Line up the D connector on the junction box cover with the connector on the mot...

Page 18: ...sure that they are properly seated in the groove on the hous ing It is imperative that these O rings be properly installed and in good condition Failure to maintain these rings can allow water to ente...

Page 19: ...cond ENCLOSURE MATERIAL Copper free aluminum red or 316 stainless steel with stainless steel mounting bracket TEMPERATURE RATING Operating 40 F to 167 F 40 C to 75 C Storage 40 F to 185 F 40 C to 85 C...

Page 20: ...See Figures 5 and 6 MTBF 36 183 hours SHIPPING WEIGHT Approximate Pounds Kilograms Aluminum housing 6 0 2 7 Stainless steel housing 14 0 6 3 REPLACEMENT PARTS The electronic module is not designed to...

Page 21: ...R Long Range Test Lamp RECOMMENDED SPARE PARTS oi ring for UV detector 1 per 10 units oi ring for IR detector 1 per 10 units O rings for UV and IR detectors 2 per 10 units UV module with LEDs 1 per 10...

Page 22: ...ollowing performance criteria was verified by FMR using IR Module DE 5400 001 and UV Module DE1888 Response Characteristics Angle of View 45 to 45 off centerline in vertical and horizontal planes Fals...