Det-Tronics U7652 Instructions Manual Download Page 13

When manual 

oi

is selected, the detector is tested

either by pressing and holding the manual 

oi

button

(if installed) or by shining a W867 Test Lamp into the
detector viewing windows.  The “Startup and
Checkout Procedure (Manual 

oi

Test)” section of this

manual explains this procedure.  For problems
encountered during the manual 

oi

test, refer to Table

6 -  Manual 

oi

Troubleshooting.

AUTOMATIC 

oi

SELECTED

The Automatic 

oi

feature (if selected) tests the detec-

tor approximately once each minute, checking the
cleanliness of the optical surfaces, sensor sensitivity,
and proper functioning of the electronic circuitry.
Proper operation of the detector is indicated by simul-
taneous blinking of both the UV and IR sensor LEDs
every 5 seconds.  If a problem is detected for three
consecutive automatic 

oi

tests, a fault signal is gen-

erated.  If the detector passes three consecutive
automatic 

oi

tests, the fault signal will then be

cleared.  If a detector fault is indicated, observe the
detector LEDs as well as the status of the detector
relays, then refer to Tables 1 and 7 for status and
troubleshooting information.

Perform the “Startup and Checkout Procedure
(Manual 

oi

Test)” in this manual to verify the proper

operation of the Fire relay and LEDs.

FIELD TESTING UV/IR DETECTORS

Det-Tronics UV/IR flame detectors contain sensitive
electronic components (ICs, transistors, etc.) that can
be damaged by electrostatic discharge (ESD).
Common causes of damage include improper han-
dling during installation/service, ground faults, power
supply transients, and lightning strikes.  All Det-
Tronics systems are designed with extensive protec-
tion circuitry, however, damage can still occur. 

The following field test procedure has been devel-
oped to test Det-Tronics UV/IR flame detectors for
ESD-damaged components: 

1.

Disable (bypass) all automatic fire extinguishing
and shutdown equipment prior to testing.  If the
detector is part of a Det-Tronics controller-based
system, simply move the controller key switch to
the Test mode.  

11

95-8385

Condition

Indication

Corrective Action

Normal operation with

Fault relay de-energized

Check the operation of the power source and the 

manual 

oi

test not 

LEDs not blinking

continuity of the detector wiring.  If the detector appears

initiated

to be “dead” with power applied, remove power and

(Manual 

oi

Selected)

replace the motherboard.

Manual 

oi

Test 

Fire relay did not energize

The other sensor has failed to respond.

and the LEDs of only one

• Check the cleanliness of the viewing window and 

sensor are illuminated

repeat the test.

• If the sensor fails to respond again, replace the sensor 

module.

• If the sensor still does not respond, replace the 

motherboard.

Manual 

oi

Test 

Fire relay did not energize

Both sensors have failed to respond.

and the LEDs of neither

• Check input power and external wiring.

sensor are illuminated

• Check the cleanliness of both viewing windows.

If the detector still does not respond:
• If using a test lamp, check the battery, window, etc. to 

be sure that the test lamp is working properly.

• If using the manual 

oi

switch, check the switch for 

proper operation and wiring.

If the detector still does not respond, replace the 
motherboard.

Table 6—Manual 

oi

Troubleshooting

Summary of Contents for U7652

Page 1: ...tions 95 8385 06 Unitized UV IR Flame Detector U7652 Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829 8750 3 01 95 8...

Page 2: ...7 Figure 7 U7652B Wiring Terminal Configuration 7 Figure 8 Wiring Terminal Configuration for U7652C with Auxiliary Relay 7 Figure 9 Wiring Terminal Configuration for U7652C with 4 to 20 ma Output 8 F...

Page 3: ...ouch the connector circuit board or electronic components 4 Alarm and extinguishing devices should be disconnected before performing the manual oi test DESCRIPTION The U7652 UV IR Flame Detector is an...

Page 4: ...ormally de energized no fire Energizes upon detection of fire Field programmable for either latching or non latching operation Fault relay has SPST normally open contacts Normally energized no fault D...

Page 5: ...is 10 degrees and were set for a 0 5 second time delay Response is dependent on the type of fuel the temperature of the fuel and the time required for the fire to build As with all fire tests results...

Page 6: ...erence by EMI and RFI It will not respond to a 5 watt walkie talkie at a dis tance of greater than 1 foot VIEWING WINDOWS Keep the detector viewing windows as free of con taminants as possible in orde...

Page 7: ...IREMENTS Use 16 to 22 gauge 1 5 to 0 5 mm2 cable A minimum input voltage of 18 vdc must be present at the detector Use cable that is suitable for the installation environ ment harsh environments requi...

Page 8: ...SWIVEL CONDUIT SEAL A1478 Figure 3 Vertical Mounting B1437 TERMINAL BLOCK AUXILIARY RELAY OPERATION W4 LATCH NON LATCH W1 ALARM RESPONSE W3 oi TEST W2 CONNECTOR SCREWS 3 MOTHERBOARD ASSEMBLY Figure 4...

Page 9: ...LT RELAY IS SHOWN DE ENERGIZED BUT IS NORMALLY ENERGIZED WITH POWER APPLIED AND NO FAULTS PRESENT 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 FIRE FAULT CON 1 CON 2 AUX AUX Figure 8 Wiring Terminal Configurat...

Page 10: ...CON 1 CON 1 CON 2 CON 2 SPARE FAULT RELAY 0 47 F 400 VOLT CAPACITOR Figure 10 A Typical System Using U7652B Detectors FAULT RELAY IS SHOWN DE ENERGIZED BUT IS NORMALLY ENERGIZED WITH POWER APPLIED AND...

Page 11: ...used pour the conduit seals and allow them to dry 7 Re install the junction box cover ensuring that the 9 pin D connectors are properly mated between the cover and the circuit board inside the enclo s...

Page 12: ...e unit is programmed for non latch ing operation the Fire relay will become de ener gized and the LEDs will turn off when the UV IR source is removed If the unit is programmed for latching operation i...

Page 13: ...und faults power supply transients and lightning strikes All Det Tronics systems are designed with extensive protec tion circuitry however damage can still occur The following field test procedure has...

Page 14: ...background Background radiation as such does not cause a problem Radiation UV or IR radiation is indicated with the detector in most applications unless both UV and by steady illumination of the flick...

Page 15: ...proper operation is observed If abnormal operation is evident start with the sensor exchange first then the detector cover assembly and finally the detector mother board assembly Always remove system...

Page 16: ...e sensor housing Hand tighten the sensor housing into the base until the O ring is fully seated 8 Re install the cover locking device if used 9 Inspect the viewing windows and oi rings and clean if ne...

Page 17: ...to the detector terminal blocks 8 Apply a small amount of lubricant to each of the six screws on the junction box cover Line up the D connector on the junction box cover with the connector on the mot...

Page 18: ...sure that they are properly seated in the groove on the hous ing It is imperative that these O rings be properly installed and in good condition Failure to maintain these rings can allow water to ente...

Page 19: ...cond ENCLOSURE MATERIAL Copper free aluminum red or 316 stainless steel with stainless steel mounting bracket TEMPERATURE RATING Operating 40 F to 167 F 40 C to 75 C Storage 40 F to 185 F 40 C to 85 C...

Page 20: ...See Figures 5 and 6 MTBF 36 183 hours SHIPPING WEIGHT Approximate Pounds Kilograms Aluminum housing 6 0 2 7 Stainless steel housing 14 0 6 3 REPLACEMENT PARTS The electronic module is not designed to...

Page 21: ...R Long Range Test Lamp RECOMMENDED SPARE PARTS oi ring for UV detector 1 per 10 units oi ring for IR detector 1 per 10 units O rings for UV and IR detectors 2 per 10 units UV module with LEDs 1 per 10...

Page 22: ...ollowing performance criteria was verified by FMR using IR Module DE 5400 001 and UV Module DE1888 Response Characteristics Angle of View 45 to 45 off centerline in vertical and horizontal planes Fals...

Page 23: ...Printed in USA Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829 8750...

Reviews: