Exhaust and Outdoor Airflow Setup
The SelectAire Plus™ system has sensors and controls that are self-balancing for exhaust and
outdoor air flow rates. The unit set points are set at the factory based on the information entered at
the time of order and each unit is tested to confirm that the flow rate is properly controlled.
A special outdoor airflow monitoring system in the SelectAire Plus™ system measures and controls
the outdoor air flow rates in each mode of operation. Flow rates are factory set and confirmed by
measurement. The unique zone pressurization control feature helps to ensure the space is
negatively pressurized properly by sensing and controlling the exhaust airflow. Desert Aire
SelectAire Plus™ units can be equipped with several exhaust airflow modes.
The system should be checked to ensure that the static pressure encountered in the installation are
not exceedingly high as this would limit the effectiveness of the fan or damper systems. This is done
by following the procedures for airflow setup below.
Outdoor Airflow Setup
A standard SelectAire Plus™ unit has the ability to monitor and control the outside airflow rate in all
occupied modes. Each unit is preset with the flow rate specified at the time of order for each mode of
operation. When setting up the unit, the capability for each mode should be confirmed.
•
Unoccupied Mode Outdoor Air Setup (Units with Low Exhaust Option Only)
In certain installations that are equipped with a Low Exhaust duct or similar device that
exhausts air constantly, there may be a desire to introduce some outdoor air during
unoccupied mode. The SelectAire Plus™ system allows Unoccupied Outdoor Air damper
position. This allows some outdoor air into the space to relieve during unoccupied mode to
prevent the slamming of doors or infiltration from unfiltered areas. Setup in this mode is
done based on pressure in the zone.
1. Use controller display under SERVICE MENU AIRFLOW SETTINGS
AIRFLOW SETUP and use the down arrow until the OA SETUP – UNOCC
screen is shown. Set the Override to “On”.
2. Ensure that any Low Exhaust fan or device is operating in Unoccupied Mode.
3. Read the zone pressure on the display. The recommended pressure is -0.05”
W.C. Should the pressure be lower than this, the Unocc OA Setpoint setting can
be increased.
•
Outdoor Air Setup for All Other Modes
Each outdoor air mode should be confirmed
1. Use controller display under SERVICE MENU AIRFLOW SETTINGS
AIRFLOW SETUP and use the down arrow until OA SETUP – OCCUPIED is
shown. Set the Override to “On”.
2. Let the unit control loop stabilize. You will see the damper position modulate. The
control loop may take up to 5 minutes to fully stabilize. At that time Current OA
Summary of Contents for SelectAire Plus SP Series
Page 2: ...2 ...
Page 12: ...12 Desert Aire SP Manual ...
Page 76: ...76 Figure 41 Filter Drier Assembly Desert Aire SP Manual ...
Page 101: ...101 Desert Aire SP Manual ...
Page 102: ...102 Desert Aire SP Manual ...
Page 103: ...103 Desert Aire SP Manual ...
Page 104: ...104 Desert Aire SP Manual ...
Page 105: ...105 Desert Aire SP Manual ...
Page 106: ...106 Desert Aire SP Manual ...
Page 109: ...109 Desert Aire SP Manual ...