General
• Proper air distribution is vital to coil performance. Air flow anywhere on the coil face should not vary by
more than 20%.
• The drain pan and associated piping (drain line and trap) should be installed so that there is no standing
water in the drain pan and that no blow-through occurs.
• Fluid and air velocities should be maintained within our recommended values.
% Ethylene
Glycol by
Volume
0
10
20
30
40
50
60
Freeze Point
32°F
25°F
16°F
3°F
-13°F
-34°F
-55°F
% Propylene
Glycol by
Volume
0
10
20
30
40
50
60
Freeze Point
32°F
26°F
19°F
8°F
-7°F
-28°F
-55°F
Figure 27 – Freeze Points (may vary from product to product)
2.14 Packaged Condenser Hail Guard and Pre-Filter Assembly Instructions
Optional Hail Guard and Pre-Filters are available for use over the packaged condenser coil.
2.14.1 Packaged Condenser Hail Guard
Hail Guard netting will arrive mounted to the surface of the packaged condenser units. The guard netting will
be attached with black clips. These clips are permanently mounted to the unit and will not need to be
removed for maintenance. A moveable tab opens in the up direction and closes in the down position. When
removing the netting open all of the clips and slide the hail guard off away from the coil. When reinstalling the
hail guard, align the hail guard grommets over the open clips and slide the clips to the closed position. The
condenser coils are not the same size so be sure to use the correct guard with each condenser coil.
Figure 28 – Hail Guard netting and mounting clips
Summary of Contents for SelectAire Plus SP Series
Page 2: ...2 ...
Page 12: ...12 Desert Aire SP Manual ...
Page 76: ...76 Figure 41 Filter Drier Assembly Desert Aire SP Manual ...
Page 101: ...101 Desert Aire SP Manual ...
Page 102: ...102 Desert Aire SP Manual ...
Page 103: ...103 Desert Aire SP Manual ...
Page 104: ...104 Desert Aire SP Manual ...
Page 105: ...105 Desert Aire SP Manual ...
Page 106: ...106 Desert Aire SP Manual ...
Page 109: ...109 Desert Aire SP Manual ...