62
It is possible that there was an internal defect in the compressor or normal mechanical wear occurred
over time. Compressors longevity generally is a function of load, lubrication, electrical input conditions,
and temperatures.
There is a cause for the compressor failures that must be identified before unit is placed back into full
service. Both the identification of the cause of compressor failure and the proper cleanup of the system
must be addressed to avoid repeat compressor damage.
5.2 Recommended Duct Design
You must use proper duct design to ensure that the dehumidifier operates efficiently and without
problems. Undersized or restrictive ducts reduce the system airflow, which can cause premature
compressor failure. Use the following diagrams as a guide when you design the duct system.
Figure 35 - Recommended Duct Designs for Desert Aire Dehumidifiers
Desert Aire - SA Manual