36
6.
Drive self-drilling screws through the existing clearance holes into the angle
material at a minimum of two overlapping holes per surface.
7.
Cap the screws with the rubber tip covers provided. Tighten all screws, nuts
and bolts.
Figure 28 - B-Vent support
8.
Repeat steps 2-7 to connect the rearmost heater screw to the collar.
2.10.1.6
Indoor Unit Set-up Instructions
For indoor units, follow heater manufacturer instructions for discharge gas vent piping.
2.10.1.7
Finalize Installation
Connect communication and power wiring from the unit to the heater. Be sure to keep
conduit clear of door openings. Connect gas lines per heater manufacturer
instructions. Install transition duct between SA unit and heater. Insulate transition duct.
2.10.2 Gas Heater Start-Up
Place the unit into heating mode. Verify the induction fan begins running. Verify the switch on the top
of the controller is switched to “ON” (not “TEST”). Allow the unit to reach steady state. Use a flue gas
analyzer in the flue gas duct and document O
2
(%), CO (ppm), Efficiency (%), CO
2
(%), and gas
temperature.