Selecting the SERVICE MENU will display the Login Screen. Enter the service 

 

 

password, 1234, and press ENTER. The SERVICE MENU allows service related 

 

 

information to be viewed and modifi ed. Screens that could be available include the Unit 

 

 

Status, I/O Status, Pressure Cutouts, Sensor Offsets, O/A RH and Temperature 

 

 

Setpoints and other unit parameters. If PID loops are included for heating or cooling 

 

 

control, these will be accessible from the SERVICE MENU. The password is bypassed 

 

 

for 5 minutes after it is fi rst entered. This is displayed on the Login Screen with the text, 

 

 

“Still Logged In, Press PRG to Enter.” To re-enter the SERVICE MENU without entering 

 

 

the password, just press the Prg key. 

 3.8 

Unit 

Status

 

 

Selecting the UNIT STATUS MENU allows unit specifi c data to be viewed. These could 

 

 

include air/water priority, system mode, occupancy state, event state and compressor 

   requirements.

 3.9 

Factory 

Confi guration

 

 

The Factory Confi guration is preset at the factory before the unit is shipped. Changes 

 

 

to the confi guration could cause damage to the unit. Modifi cation to these settings 

 

 

should only be done by a factory trained technician.

 3.10 

I/O 

Status

 

 

Selecting the I/O Status Screen displays the four types of I/O devices wired to the unit. 

 

 

These include the digital inputs, analog inputs, digital outputs and analog outputs. The 

 

 

Digital Input Screen will display the state of any switch wired to a digital input on the 

 

 

wiring diagram. The digital inputs are designated as ID on the controller and include 

 

 

switches or contacts. The Analog Input Screen displays the status of any sensors wired 

 

 

to the analog inputs on the wiring diagram. The analog inputs are designated as B 

 

 

in the controller and include devices such as air pressure transducers, refrigerant 

 

 

transducers, RH sensors and temperature sensors. The Digital Output Screen displays 

 

 

the state of devices wired to the digital outputs on the wiring diagram. The digital 

 

 

outputs are designated as NO or NC on the controller and include devices such as 

 

 

relays, contactors or solenoid coils. The Analog Output Screen displays the value of 

 

 

devices driven by the output. The analog outputs are designated as Y on the 

 

 

controller and include devices such as damper actuators and positioning valves. 

 

 

Please note that the analog outputs from any CM35xx controller are only 0-10 VDC. 

 

 

A 4–20 mA output is not available.

 

 3.11 

Pressure 

Cutouts

 

 

This screen simply displays the Refrigerant Selection, High Discharge Pressure and 

 

 

Low Suction Pressure cutout values for the appropriate refrigerant selected. The 

 

 

operator cannot change these settings. The Cooling Mode Low Pressure Trip is shown 

 

 

because if the unit is an IAQ heat pump, and the compressor is used for heating, the 

Desert Aire - CM35xx Quick Start Guide

Summary of Contents for CM35xx

Page 1: ......

Page 2: ...2 ...

Page 3: ...8 3 5 Occupancy Schedule 8 3 5 1 Schedule Options 9 3 5 2 Current Schedule 9 3 5 3 Temporary Holidays 9 3 5 4 Annual Holidays 9 3 5 5 Set Time 9 3 6 Unit Revision 9 3 7 Service Menu 10 3 8 Unit Status 10 3 9 Factory Configuration 10 3 10 I O Status 10 3 11 Pressure Cutouts 10 3 12 Sensor Offsets 11 3 13 Building Management Communication 11 4 Alarm Menu 11 4 1 Alarm History Screen 11 Desert Aire CM3...

Page 4: ...4 Desert Aire CM35xx Quick Start Guide ...

Page 5: ...ote display terminal RDT Although the placement of the keys for these two options is different the key functions are exactly the same Figure 1 shows an RDT and Figure 2 shows an IDT The ND SA and LC products will use the RDT and the QM will use the IDT The IAQ products will use a combination of RDTs and IDTs typically depending on the physical placement of the controller in the unit If the control...

Page 6: ...ontroller is pre programmed and configured at the factory for use in the application you have specified The RDT Figure 1 allows the operator to monitor the operation and adjust the setpoints of the Desert Aire dehumidifier The RDT has an LCD screen and 6 keys The keys on the left hand side of the RDT top to bottom are the ALARM key shown as an alarm bell PROGRAM key abbreviated Prg and the ESCAPE key...

Page 7: ...y is pressed To cycle through the selections on a menu screen use the UP and DOWN keys If setpoints or selections can be altered on a screen the ENTER key will cycle through those items Once the cursor is over an item the UP and DOWN arrow keys will modify the setting Numeric values will require that the ENTER key be pressed to accept the value An on or off selection will be altered as soon as the...

Page 8: ...efer to Section 3 for setpoint modification instructions 3 4 Temporary Occupancy This screen allows the operator to set the unit into occupied mode for a preset amount of time Press the ENTER key and enter in the hours and minutes you would like the unit to be temporarily in the occupied mode When the cursor is blinking over the Press Prg to set message pressing the Prg key will override the schedu...

Page 9: ...idays can be set from this screen Select the number to assign to the Annual Holiday and then select the Start Date and the End Date for that holiday 3 5 4 Annual Holidays The Annual Holiday settings are for holidays with dates that remain constant year to year such as New Years Day and the 4th of July Up to 10 different annual holidays can be set from this screen Select the number to assign to the...

Page 10: ...puts analog inputs digital outputs and analog outputs The Digital Input Screen will display the state of any switch wired to a digital input on the wiring diagram The digital inputs are designated as ID on the controller and include switches or contacts The Analog Input Screen displays the status of any sensors wired to the analog inputs on the wiring diagram The analog inputs are designated as B ...

Page 11: ...he ModBus network 4 Alarm Menu The ALARM MENU can be accessed anytime by pressing the ALARM key The main Alarm Screen includes the instructions for viewing and resetting the alarms as well as a means to access the Alarm History Screen Pressing the ENTER key while viewing the main Alarm Screen will reset any alarm that has returned to its safe state Please note that active alarms can only be reset ...

Page 12: ...12 N120 W18485 Freistadt Road Germantown WI 53022 E mail info desert aire com Ph 262 946 7400 Fax 262 946 7401 Website www desert aire com 56 5 10 ...

Reviews: