47
3.4
Compressor Overload
This is a Manual Reset Alarm. The Compressor Overload alarm is activated when the
compressor motor overload device indicates an overload condition. In this state, the refrigerant
circuit will stop and not restart until the alarm condition is reset manually. Typically, the motor
starting hardware will need to be reset along with a control system reset. The red Alarm LED
on the display will stay lit until the alarm is reset.
3.5
Modbus Sensor Fault
This is an Automatic Reset Alarm. Check the communication wiring to the sensor when this
fault occurs. The red Alarm LED on the display will stay lit until the alarm is reset.
3.6
Blower Overload
This is a Manual Reset Alarm. The Blower Overload alarm is activated when the blower motor
overload devices indicates an overload condition. In this state, the dehumidifier will stop and
not restart until the alarm condition is reset manually. Typically, the motor starting hardware
will need to be reset along with a control system reset. The red Alarm LED on the display will
stay lit until the alarm is reset.
3.7
Smoke Alarm
This is an Automatic Reset Alarm. The Smoke Alarm is activated if the alarm contact wired to
digital input ID1 is opened. In this state, the unit will stop and not restart until the smoke alarm
contact closes. The red Alarm LED on the display will stay lit until the alarm is acknowledged,
even after the alarm condition is cleared, to alert the operator the alarm occurred.
3.8
c.pCOe Comm Fault
This is an Automatic Reset Alarm. The c.pCOe is the expansion module. Check the expansion
module power and communication link. The red Alarm LED on the display will stay lit until the
alarm is reset.
3.9
c.pCOe Cnfg Fault
This is an Automatic Reset Alarm. The c.pCOe is the expansion module. Check the expansion
module power and communication link. The red Alarm LED on the display will stay lit until the
alarm is reset.
3.10 Alarm Log (Figure 60)
The Alarm Data Logger screen is accessible from the Alarm Reset screen (Figure 60) by
pressing the
ENTER
key. This screen shows records of the alarm log. The bottom two lines
will show the pertinent data that was recorded when the alarm occurred. Use the
UP
and
DOWN
keys to view other records.
Desert Aire - CM3540 Manual
Summary of Contents for CM3540 Series
Page 2: ...2 ...
Page 5: ...5 Product Warning for the State of California Desert Aire CM3540 Manual ...
Page 6: ...6 Desert Aire CM3540 Manual ...
Page 12: ...12 Desert Aire CM3540 Manual ...
Page 29: ...29 Figure 28 Figure 29 Figure 30 Desert Aire CM3540 Manual ...
Page 44: ...44 Desert Aire CM3540 Manual ...
Page 48: ...48 Figure 60 To return to the Home screen press the Esc key Desert Aire CM3540 Manual ...