39
If the unit is equipped with the Outdoor Air Option a second
Analog Output screen will be displayed (Figure 47). This screen
displays the outputs of the Expansion Board Module.
• The first line of this screen displays the output status of
U1, the Outdoor Air Damper Command, 0.0% to 100.0%.
•
The second line of this screen displays the output status of
U2, the Evaporator Bypass Damper Command, 0.0% to 100.0%.
To return to the I/O STATUS screen, press the
Esc
key.
Figure 47
2.3.4.4 Sensor Offsets (Figures 48 - 49)
These screens allow the control values of the analog input points to be
adjusted if calibration shows these devices to be inaccurate. The range of
these offsets is -9.9 to 9.9. Care must be used when applying an offset to an
analog value as erratic operation can result. To modify the offsets, press the
ENTER
key until the desired offset is selected and use the arrow keys until
the desired setting is shown. Press the
ENTER
key to accept the offset value.
To return to the SERVICE MENU, press the
Esc
key.
Figure 48
Desert Aire - CM3540 Manual