aIr For CombustIoN 

aNd VeNtIlatIoN

Continued 

DETERMINING FRESH-AIR FLOW 
FOR HEATER LOCATION

Determining if You Have a Confined or 
Unconfined Space

Use this work sheet to determine if you have a con

-

fined or unconfined space.

Space:

 Includes the room in which you will install 

heater plus any adjoining rooms with doorless pas

-

sageways or ventilation grills between the rooms.

1.  Determine the volume of the space (length x 

width x height).

 

Length x Width x Height =__________cu. ft. 

(volume of space)

 

Example:

 Space size 20 ft. (6.1 m) (length) x 16 

ft. (4.88 m)(width) x 8 ft. (2.44 m) (ceiling height) 

= 2560 cu. ft. (72.49 m

3

) (volume of space)

 

If additional ventilation to adjoining room is 

supplied with grills or openings, add the volume 

of these rooms to the total volume of the space. 

2.  Multiply the space volume by 20 to determine 

the maximum Btu/Hr the space can support. 

 

 _______

(volume of space) x 20 = (Maximum 

Btu/Hr the space can support)

 

Example:

 2560 cu. ft. (72.49 m

3

) (volume of 

space) x 20 = 51,200 (maximum Btu/Hr the space 

can support)

3.  Add the Btu/Hr of all fuel burning appliances in 

the space.

 

Vent-free heater 

  ___________

Btu/Hr

 

Gas water heater* 

  ___________

Btu/Hr

 

Gas furnace 

  ___________

Btu/Hr

 

Vented gas heater 

  ___________

Btu/Hr

 

Gas fireplace logs 

  ___________

Btu/Hr

 

Other gas appliances*  +

 __________

Btu/Hr

 

Total 

= __________

Btu/Hr

 

* Do not include direct-vent gas appliances. Di

-

rect-vent draws combustion air from the outdoors 

and vents to the outdoors.

 

Example:

 

Gas water heater 

  ___________

Btu/Hr

 

Vent-free heater 

+

 __________

Btu/Hr

 

Total 

= __________

Btu/Hr

40,000

18,000

58,000

4.  Compare the maximum Btu/Hr the space can 

support with the actual amount of Btu/Hr used.

 

 _________

Btu/Hr (maximum the space can support) 

 

 _________

Btu/Hr (actual amount of Btu/Hr used)

 

Example:

  51,200 Btu/Hr (maximum the space 

can support) 

 

 

58,000  Btu/Hr  (actual  amount  of 

Btu/Hr used)

The space in the above example is a confined space 

because the actual Btu/Hr used is more than the maxi

-

mum Btu/Hr the space can support. You must provide 

additional fresh air. Your options are as follows:

A.  Rework worksheet, adding the space of an adjoin

-

ing room. If the extra space provides an unconfined 

space, remove door to adjoining room or add 

ventilation grills between rooms. See 

Ventilation 

Air From Inside Building

, page 7.

B.  Vent room directly to the outdoors. See 

Ventila-

tion Air From Outdoors

, page 7.

C.  Install a lower Btu/Hr heater, if lower Btu/Hr size 

makes room unconfined. 

If the actual Btu/Hr used is less than the maximum 

Btu/Hr the space can support,

 

the space is an uncon

-

fined space. You will need no additional fresh air 

ventilation.

 

  WARNING:  If  the  area  in 

which the heater may be oper

-

ated is smaller than that defined 

as an unconfined space or if the 

building  is  of  unusually  tight 

construction, provide adequate 

combustion and ventilation air 

by one of the methods described 

in the 

National Fuel Gas Code, 

ANSI Z223.1/NFPA 54 Section 5.3

 

or applicable local codes. 

Summary of Contents for VSL18NT

Page 1: ...asoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use...

Page 2: ...birth defects or other reproductive harm IMPORTANT Read this owner s manualcarefullyandcompletely before trying to assemble operate or service this heater Improper use of this heater can cause seriou...

Page 3: ...other gases 2 Do not place propane LP supply tank s in side any structure Locate propane LP supply tank s outdoors 3 This heater shall not be installed in a bathroom or a bedroom 4 If you smell gas sh...

Page 4: ...f 527 CMR 30 upon sale of the unit Vent free gas products are prohibited for bed room and bathroom installation in the Com monwealth of Massachusetts Unpacking 1 Remove heater from carton 2 Remove all...

Page 5: ...ir that leaks around doors and windows may provide enough fresh air for combustion and ventilation However in buildings of unusually tight construction you must provide additional fresh air Unusually...

Page 6: ...ct vent gas appliances Di rect vent draws combustion air from the outdoors and vents to the outdoors Example Gas water heater _ ___________ Btu Hr Vent free heater ___________ Btu Hr Total ___________...

Page 7: ...a centralheatingsystem youmay run system s circulating blower whileusingheater Thiswillhelp circulatetheheatthroughoutthe house In the event of a power outage you can use this heater as your primary...

Page 8: ...from hardware packet 1 Bushing 4 Black spacers 4 Retaining clips 4 1 5 long screws 4 Screw covers 1 Locate hardware packet and dark acrylic glass 2 Peel protective coating from both sides of glass 3...

Page 9: ...exist may discolor walls or cause odors IMPORTANT Vent free heaters add moisture to the air Although this is beneficial installing heater in rooms without enough ventilation air may cause mildew to fo...

Page 10: ...10 Mounting Bracket Clearances INSTALLING HEATER TO WALL Mounting Bracket Locate mounting bracket that has been taped to back panel of heater for shipping Remove mount ing bracket from back panel of h...

Page 11: ...c tions and checking for leaks INSTALLATION Continued Figure 13 Mounting Heater Onto Mounting Bracket Mounting Bracket attached to wall Horizontal Slots Stand Out Tab CONNECTING TO GAS SUPPLY WARNING...

Page 12: ...ur Typical Inlet Pipe Diameter 3 8 9 5 mm or greater Installation must include equipment shutoff valve union and plugged 1 8 NPT tap Locate NPT tap within reach for test gauge hook up NPT tap must be...

Page 13: ...quipment shutoff valve see Figure 17 2 Pressurize supply piping system by either opening propane LP supply tank valve for propane LP gas or opening main gas valve located on or near gas meter for natu...

Page 14: ...rt of the control system and any gas control which has been under water INSTALLATION Continued Connecting to electrical supply WARNING Fan accessory must be grounded Fan comes with a three prong groun...

Page 15: ...ostat models have a safety interlock system Wait one 1 minute before lighting pilot again 9 Turn control knob counterclockwise to desired heating level The main burner should light WARNING Always oper...

Page 16: ...e pattern The incorrect pilot flame is not touching the thermocouple This will cause the thermocouple to cool When the thermocouple cools the heater will shut down If pilot flame pattern is incorrect...

Page 17: ...be and pilot assembly clean and free of dust and dirt To clean these parts we recommend using compressed air no greater than 30 PSI Your local computer store hardware store or home center may carry co...

Page 18: ...sition 4 Air in gas lines when in stalled 5 Depleted gas supply propane LP gas only 6 ODS pilot is clogged 7 Gas regulator setting is not correct OBSERVED PROBLEM When ignitor button is pressed there...

Page 19: ...ane LP gas company 1 Contact local natural or pro pane LP gas company 2 Clean burner see Cleaning and Maintenance page 17 or replace burner orifice 1 Clean burner see Cleaning and Maintenance page 17...

Page 20: ...ime delay for thermal switch to warm up 4 Bad switch 5 Loose wire connection 1 Metal expanding while heat ing or contracting while cooling REMEDY 1 Check burner for dirt and debris If found clean burn...

Page 21: ...s partially clogged 1 Gas leak See Warning state ment above 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak See Warning state ment above 1 Not enough combustion...

Page 22: ...rams CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous opera tion Verify proper operation after servicing Thermostat Sensor Switch I...

Page 23: ...Heating Products Replacement Parts Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty Parts Under Warranty Contact authorized dealers...

Page 24: ...L18PT SL18NT SL18PT VSL18NT AND VSL18PT 2 4 1 5 6 8 9 10 11 12 13 14 17 18 19 20 15 7 21 22 32 23 28 29 30 31 16 33 24 3 25 26 27 AA Battery Positive UP AAA Battery Negative UP Install Battery Accordi...

Page 25: ...3 01 ODS Pilot Natural 1 110803 02 ODS Pilot Propane LP 1 18 098271 09 Ignitor Cable 1 098271 11 Ignitor Cable 1 19 116679 01 Pilot Bracket 1 20 101004 08 Injector Natural 1 101004 10 Injector Propane...

Page 26: ...KY 42103 3414 270 846 1199 1 800 654 8534 Fax 1 800 846 0090 franktalk aol com Master Parts Dist 1251 Mound Ave NW Grand Rapids MI 49504 2672 616 791 0505 1 800 446 1446 Fax 616 791 8270 www nbmc com...

Page 27: ...__ ______________________________________________________ ______________________________________________________ ______________________________________________________ ________________________________...

Page 28: ...of this product and or DESAHeating Products who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty The heater MUST be installed by a...

Page 29: ...ctrico no use ning n tel fono en el edificio Llame inmediatamente a su proveedor de gas desde el tel fono de alg n vecino Siga las instrucciones del proveedor de gas Si no puede localizar al proveedo...

Page 30: ...en el mercado de posventa siempre que no est prohibido por los c digos locales Mercado de posventa venta completada por parte del fabricante sin fines de reventa ADVERTENCIA este producto contiene y o...

Page 31: ...or Lasuperficiedelcalentadoralcanza temperaturasmuyaltascuando ste est funcionando Mantengaani os yadultosalejadosdelassuperficies calientes para evitar quemaduras o que la ropa se encienda El calenta...

Page 32: ...Inc 1430 Broadway New York NY 10018 EE UU National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 EE UU Estado de Massachusetts la instalaci n la debe realizar un plomero o un inst...

Page 33: ...spacio y procurar la ventilaci n adecuada Construcci n inusualmente sellada El aire que se filtra por los bordes de las puertas y ventanas puede proporcionar suficiente aire fresco para la combusti n...

Page 34: ...18 000 58 000 4 Compare la cantidad m xima de BTU h que el espacio puede admitir con la cantidad real de BTU h que se utiliza _ _________ BTU h cantidad m xima que el espa cio puede admitir _________...

Page 35: ...ste calentador como su fuente de calefacci n principal ADVERTENCIA una perso na de servicio capacitada debe instalarelcalentador Sigatodos los c digos locales VERIFIQUE EL TIPO DE GAS Use nicamente el...

Page 36: ...rior del calentador Tornillo Panel anterior Cable del encendedor Buje Instalaci n del panel de vidrio Los art culos del paquete de ferreter a que se ne cesitan son 1 Buje 4 Separadores negros 4 Clips...

Page 37: ...entes de aire fuertes Side View Figura 6 Instalaci n del encendedor piezoel ctrico Encendedor piezoel ctrico Lado derecho del calentador Figura 7 Instalaci n del encendedor electr nico Lado derecho de...

Page 38: ...e 1 3 cm 1 2 de ancho o paredes s lidas no abra las alas 5 Coloque el soporte de montaje en la pared Alinee el ltimo orificio de cada extremo del soporte con los anclajes de pared 6 Inserte los tornil...

Page 39: ...no coloque el panel anterior en este mo mento Ponga el panel anterior en su lugar hasta despu s de haber hecho las conexiones de gas y haber revisado que no haya fuga INSTALACI N Continuaci n Figura 1...

Page 40: ...e en trada 9 5 mm 3 8 o m s La instalaci n debe incluir la v lvula de cierre del equipo la uni n y el tap n con rosca de 1 8 tipo NPT Sit e la conexi n NPT a su alcance para la co nexi n del medidor d...

Page 41: ...stema de tuber a de su ministro ya sea abriendo la v lvula del tanque de suministrodepropanoogasLP encasoqueutilice estetipodegas obien abriendolav lvulaprincipal de gas que se localiza en el medidor...

Page 42: ...entaci n el ctrica ADVERTENCIA el ventilador debe estar conectado a tierra El ventilador tiene una clavija de tres patas con conexi n a tierra como se muestraenlafigura20 Laclavijaesla protecci ncontr...

Page 43: ...ulte el Procedimiento de encendido manual en la p gina 16 8 Una vez que haya encendido el piloto mantenga la perilla de control presionada durante 30 se gundos Despu s de los 30 segundos suelte la per...

Page 44: ...rol termost tico que se usa en estos modelos es distinto de los termostatos convencionales Los termostatos convencionales simplemente encienden y apagan el quemador El termostato que se usa en este ca...

Page 45: ...pios y libres de pol vo y tierra Para limpiar estas piezas se recomienda Figura 28 Entrada de aire del piloto se muestra el piloto para propano o gas LP el piloto real puede ser distinto que el que ap...

Page 46: ...aire en las l neas de gas cuando se instalaron 5 Se agot el suministro de gas s lo para propano o gas LP 6 El piloto con ODS est tapado 7 La posici n del regulador de gas no es la correcta PROBLEMA OB...

Page 47: ...o gas LP 1 Comun quese con la compa a local de gas natural o de propano o gas LP 2 Limpie el quemador consulte Limpieza y mantenimiento en la p gina 17 o reemplace el orificio del quemador 1 Limpie el...

Page 48: ...caliente el interruptor t rmico 4 Interruptor en mal estado 5 Cable suelto 1 Los metales se dilatan al calentarse y se contraen al enfriarse REMEDIO 1 Revise el quemador en busca de polvo y residuos S...

Page 49: ...cia anterio 2 La v lvula de control est defectuosa 1 Hay materiales extra os entre la v lvula de control y el quemador 2 Fugas de gas Consulte la declaraci n de adverten cia anterio 1 No hay suficien...

Page 50: ...marque todos los cables antes de desconectarlos Los errores en el cableado pueden ocasionar funcionamiento err tico y peligroso Despu s de dar servicio al calentador compruebe que ste funcione correct...

Page 51: ...s lo piezas de repuesto originales Esto proteger la cobertura de su garant a para partes reemplazadas con garant a Piezas con garant a P ngase en contacto con los distribuidores autoriza dos de este...

Page 52: ...VSL18PT 2 4 1 5 6 8 9 10 11 12 13 14 17 18 19 20 15 7 21 22 32 23 28 29 30 31 16 33 24 3 25 26 27 AA Battery Positive UP AAA Battery Negative UP Instale la bater a como se muestra en la ilustraci n V...

Page 53: ...loto ODS propano o gas LP 1 18 098271 09 Cable del encendedor 1 098271 11 Cable del encendedor 1 19 116679 01 Soporte del piloto 1 20 101004 08 Inyector natural 1 101004 10 Inyector propano o gas LP 1...

Page 54: ...42103 3414 EE UU 270 846 1199 1 800 654 8534 Fax 1 800 846 0090 franktalk aol com Master Parts Dist 1251 Mound Ave NW Grand Rapids MI 49504 2672 EE UU 616 791 0505 1 800 446 1446 Fax 616 791 8270 www...

Page 55: ...__ ______________________________________________________ ______________________________________________________ ______________________________________________________ ________________________________...

Page 56: ...e los distribuidores autorizados de este producto y de DESAHeating Products quienes proporcionar n las piezas de repuesto originales de f brica Si no se utilizan piezas de repuesto originales de f bri...

Reviews: