background image

                                                                                                       - 5 -                                           

For more information, visit www.desatech.com

 

 
 
 
 

INSTRUCTIONS WHEN ELBOW OFFSET (30E-8DM) 

OF CHIMNEY IS NEEDED 

1.  To achieve desired offset, you may install combinations of                                                                             
12”, 18”, 24”, 36” and 48” length of double wall pipe (SEE 
SINGLE OFFSET CHARTAND FIGURE 6). 
2.    Chimney  weight  above  offset  rests  on  return  elbow.              
Straps must be securely nailed to rafters or joists (see figure 7, 
details a & b). 
3.    Maximum length of pipe between supports (return elbow 
or 12S-8DM) is 6’ of angle run.  Maximum of two (2) 6’ angle 
run sections per chimney system (see figure 6). 

OFFSET CHART (22-50 FT. SYSTEM HEIGHT) 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
FIRESTOP SPACERS (FS-8DM) 

Firestop spacers are required at each point where the chimney 
penetrates a floor space.  Their purpose is to establish and 
maintain the required clearance between the chimney and the 
combustible materials. 

 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 

When the pipe passes through a framed opening into a living 
space above, the firestop must be placed onto the ceiling from 
below as shown in figure 9.  
 
They also provide complete separation from one floor space to 
another or attic space as required by most codes.  When the 
double wall pipe passes through a framed opening into an attic 
space, the firestop must be placed into an attic floor as shown 
in figure 10. 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

OFFSET

RISE

A

B

48"

36"

24"

18"

12"

4 - 3/8

16 -3/8

9 - 3/4

25 - 1/2

1

12 - 3/4

30 - 3/4

1

15

34 - 3/4

1

18

40

1

1

21 - 1/4

46 - 1/4

1

23 - 3/4

49 - 1/4

1

1

27 - 3/4

56 - 3/4

1

30

60 - 3/4

1

1

33

66 1

1

36

71

1

1

38 - 1/4

75

2

41 - 1/4

80 - 1/4

1

1

1

45

86 - 3/4

2

46 - 3/4

89 - 1/2

1

1

1

51

97

1

1

53 - 1/4

101

2

1

56 - 1/4

106 - 1/4

2

59 - 1/4

111 - 1/2

1

1

1

61 - 3/4

115 - 1/2

2

1

64 - 3/4

120 - 3/4

2

1

68 - 1/4

127

1

2

70

130

2

1

1

74 - 1/4

137 - 1/2

1

2

1

76 - 3/4

141 - 1/2

1

2

1

79 - 3/4

146 - 3/4

4

ELBOW  SET ONLY

CHIMNEY LENGTH

 

Figure 7         CEILING SUPPORT PIPE 

 

 

 

Figure 8      ELBOW OFFSET 

All pipe connections between the offset and return
must be secured with two screws, only on the outer
pipe, and shall not penetrate the inner stainless. 

 

Figure 9              FIRESTOP SPACER 

Figure 10              FIRESTOP SPACER  

WARNING

: The opening in the collar around the

chimney at the top of the fireplace must not be obstructed.
Never use blown insulation to fill the chimney enclosure.

Summary of Contents for VS42 Series

Page 1: ... RGA 2 72 standards or for use with a vent free gas log heater approved to ANS Z21 11 2 standard A DESA hood must be installed when using a vent free gas log heater see Accessories p 12 WARNING Always leave glass doors fully opened or fully closed when operating this fireplace S42 42 textured white refractory brick S42H 42 textured white herringbone refractory brick S42R 42 textured red refractory...

Page 2: ...TION PG 3 6 OUTSIDE AIR KIT INSTALLATION PG 3 7 CHIMNEY PIPE AND OFFSET INSTALLATION PG 4 5 8 FIRESTOP SPACERS PG 5 9 FLASHING AND TERMINATION PG 6 7 10 FINISHING YOUR FIREPLACE PG 7 11 MANTELS PG 8 12 GLASS DOORS PG 8 13 GAS LINE INSTALLATIONS PG 9 14 DAMPER OPERATION PG 10 15 TECHNICAL SERVICE PG 10 16 ILLUSTRATED PARTS PG 11 11a 17 REPLACEMENT AND TECHNICAL PARTS PG 12 ...

Page 3: ...TIAL INSTALLATION The minimum height of the chimney measured from the base of the fireplace to the flue gas outlet of the termination is 14 5 feet for straight flue or a flue with one elbow set The maximum distance between elbows is 6 feet For systems with two elbow sets the minimum height is 22 feet The maximum height of any system is 50 feet This measurement includes the fireplace chimney sectio...

Page 4: ...rough flanges located on the sides of the fireplace HEARTH EXTENSION A hearth extension projecting a minimum of 16 in front of and a minimum of 8 beyond each side of the fireplace opening is required to protect combustible floor construction in front of the fireplace Fabricate a hearth extension using a material which meets the following specifications a layer of non combustible inorganic material...

Page 5: ...dependently as the chimney is installed When connecting chimney directly to For Canada use chimney parts designated HT the fireplace the inner flue pipe section must be installed first with the lanced side up The outer pipe section can then be installed over the flue pipe section with the hemmed end up Press down on each pipe section until the lances securely engage the hem on the fireplace starte...

Page 6: ...re 9 They also provide complete separation from one floor space to another or attic space as required by most codes When the double wall pipe passes through a framed opening into an attic space the firestop must be placed into an attic floor as shown in figure 10 OFFSET RISE A B 48 36 24 18 12 4 3 8 16 3 8 9 3 4 25 1 2 1 12 3 4 30 3 4 1 15 34 3 4 1 18 40 1 1 21 1 4 46 1 4 1 23 3 4 49 1 4 1 1 27 3 ...

Page 7: ...LASHING INSTALLATION V6F 8DM or V12F 8DM Determine the flashing to be used with the roof opening chart Slide flashing over pipe until base is flat against roof Replace as many shingles as needed to cover exposed area and flashing base Secure in position by nailing through shingles see figure 13 DO NOT NAIL THROUGH FLASHING CONE INSTALLING FLASHING ON A METAL ROOF When installing the flashing on a ...

Page 8: ... prevent smoke spillage from one termination to another We suggest that terminations be separated at least 24 inches center to center and stacked at vertical height difference of 18 inches see figure 15 NOTE If a decorative shroud is to be installed contact the manufacturer for specifications 10 FOOT RULE All flue gas outlet of chimney termination must extend a minimum of 3 feet in height above th...

Page 9: ...he combustion air gate is not completely open The following tips should be followed to assure that both the fireplace and the glass door retain their beauty and function properly Both the flue damper and the glass doors must be fully opened before starting the fire This will provide sufficient combustion air and maintain safe temperatures in the firebox IMPORTANT The glass must be allowed to warm ...

Page 10: ...framing to provide rigidity for threaded end STEP 4 Repack insulation around gas line and into sleeve opening Seal any gaps between gas line and refractory knockout hole with refractory cement or commercial furnace cement Install the gas appliance or cap off gas line if desired NOTE A DESA hood must be installed when using an unvented gas log set see accessories on page 12 If you install a decorat...

Page 11: ...gure 21 Pulling the handle out will free the outside air door to open Pushing the handle in will lock the door close FOR FURTHER OPERATING GUIDELINES INSTRUCTIONS AND WARRANTY INFORMATION PLEASE REFER TO YOUR HOMEOWNERS GUIDE OR CONTACT YOUR AUTHORIZED DEALER TECHNICAL SERVICE You may have questions about installation operations or troubleshooting If so contact the Technical Service Department at ...

Page 12: ...7839 01 107839 01 107839 01 18 FIREBOX TOP ASSEMBLY 1 106694 02 106694 02 106694 02 106694 02 106694 02 106694 02 19 AIR KIT DOOR ASSEMBLY 1 106703 01 106703 01 106703 01 106703 01 106703 01 106703 01 20 FACE WELDMENT 1 111093 01 111093 01 111093 01 111093 01 111093 01 111093 01 21 AIR DEFLECTOR 1 110892 02 110892 02 110892 02 110892 02 110892 02 110892 02 22 FIREPLACE TOP INSULATION 1 107824 01 1...

Page 13: ... 11a For more information visit www desatech com ILLUSTRATED PARTS ...

Page 14: ... 12 For more information visit www desatech com REPLACEMENT PARTS ACCESSORY PARTS SEE PARTS LIST ON PAGE 11 FOR PART NUMBERS ...

Reviews: