background image

www.desatech.com

111099-01C

13

Figure 22 - Damper and Air Kit Handle

A fireplace equipped with glass doors operates 

mush differently than a fireplace with an open 

front. A fireplace with glass doors has a limited 

amount  of  air  for  combustion.  Excessive  heat 

within the fireplace can result if too large a fire 

is built or if the combustion air gate is not com-

pletely open. 
The following tips should be followed to assure 

that both the fireplace and the glass door retain 

their beauty and function properly. Both the flue 

damper and the glass doors must be fully opened 

before starting the fire. This will provide sufficient 

combustion air and maintain safe temperatures in 

the firebox.

IMPORTANT:

 The  glass  must  be  allowed  to 

warm slowly and evenly. The tempered glass will 

withstand a gradual temperature rise to 550° F, 

which is more than a normal fire will generate. 

Such materials as pitch/wax laden logs, very dry 

mill end lumber and large amounts of paper or 

cardboard boxes can create an excessively hot fire 

and should not be burned in this fireplace. Always 

keep the fire well back from the doors and never 

allow flames to contact the glass.

  WARNING:  Fireplaces 

equipped  with  glass  doors 

should  be  operated  only  with 

doors fully opened or doors fully 

closed. Doors, if left partly open, 

may draw gas and flame out of 

the  fireplace  opening  creating 

risks of both fire and smoke.

Cleaning the Glass

Clean the glass with any commercial glass cleaner 

or soap and water. Do not use any abrasive mate-

rial to clean the glass. Do not clean the glass with 

any cool water is the glass is still hot from the 

fire and smoke.
A gas line or gas log lighter may be installed for the 

purpose of installing a vented or vent-free decorative 

gas appliance incorporating an automatic shutoff de-

vice and complying with the S

tandard for Decorative 

Gas Appliances for Installation in Vented Fireplaces, 

ANSI Z21.60

 or 

American Gas Association draft re-

quirements for Gas Fired Log Lighters for Wood Burn-

ing Fireplaces, Draft NO. 4

 dated August, 1993.

OPERATION AND 

MAINTENANCE 

GUIDELINES

Continued

If you wish to install an unvented (vent-free) gas 

log set, only unvented gas log sets which have been 

found to comply with the standard for unvented 

room heaters, ANSI Z21.11.2 are to be installed 

in this fireplace.

OUTSIDE AIR AND DAMPER 
HANDLE OPERATION

The damper handle, which opens and closes the 

damper blade, is located in the upper front face of 

the fireplace. Pushing the handle into the left of the 

keyway slot will free the damper blade to automati-

cally open. Pushing the handle in to the right will 

lock the damper blade closed (see Figure 22).
The outside air kit handle is located at the left hand 

side of the fireplace (see Figure 22). Pulling the 

handle out will free the outside air door to open. 

Pushing the handle in will lock the door closed. 

 WARNING: Risk of fire! Replace 

grate with DESA model 111100-01 

only. This grate has been designed 

to keep the operation of your fire-

place safe and efficient.

For further operating guidelines, instructions and 

warranty information, please refer to your home-

owner's guide or contact your authorized dealer.

TECHNICAL SERVICE

You may have further questions about installation, 

operation, or troubleshooting. If so, contact DESAʼs 

Technical Service Department at 1-866-672-6040. 

When calling please have your model and serial 

numbers of your heater ready.
You can also visit DESAʼs technical services web 

site at 

www.desatech.com.

OPE

N

CLOS

E

Damper 
Handle

Outside Air 
Kit Handle

Keyway 
Slot

Handle 
Retainer

Summary of Contents for VS42 Series

Page 1: ...g approved to ANS Z21 60 Z21 84 or RGA 2 72 standards or for use with a vent free gas log heater approved toANS Z21 11 2 standard A DESA hood must be installed when using a vent free log heater see Accessories page 16 This wood burning fireplace complies with UL127 CAN ULS S610 M87 standard as a FACTORY BUILT APPLIANCE FOR CANADA The authority having jurisdiction such as the municipal building depa...

Page 2: ...f any component part not manufac tured or approved by DESAin combination with a DESA fireplace system Proper installation is the most important step in ensuring safe and continuous operation of the fireplace Consult the local building codes as to the particular requirements concerned with the installation of all factory built fireplaces WARNING Do not install a fireplaceinsertinthisboxunless the manuf...

Page 3: ...NOT LESS THAN 12 1 AIRSPACE TO COMBUSTIBLE COMBUSTIBLE WALL BOARD 0 TO MATERIAL NO COMBUSTIBLE MATERIAL ON FACE SIDEWALL TERMINATION SQUARE CHASE TOP GAS LINE KNOCK OUT AIR KIT KNOCK OUTS ROUND TOP TERMINATION GAS LINE KNOCK OUTS ELECTRICAL OUTLET LEFT SIDE RIGHT SIDE 8 125 12 625 14 25 45 25 41 48 42 24 8 39 16 25 29 5 2 5 10 625 1 12 2 5 8 125 6 75 10 625 12 25 48 0 625 36 22 5 ...

Page 4: ...inimum Maximum Chimney Height for Outdoor Installation The minimum height of the chimney measured from the base of the fireplace to the flue gas outlet of the termination is 8 feet minimum of 4 feet of chimney pipe sections required for outdoor installation FRAMING 1 Frame the opening for the fireplace using the dimensions shown in Figures 1 and 2 2 If the fireplace is to be installed directly on carp...

Page 5: ...tension from shifting and seal gap between the fireplace frame and hearth extension with a non combustible material see Figure 3 WARNING Hearthextension is to be installed only as shown in Figure 3 FIREPLACE INSTALLATION Continued Figure 3 Hearth Extension Seal Gap Fireplace Front Ember Protector Fireplace Front Raised Hearth Fireplace Front Elevated Ember Protector Ember Protector Seal Gap Hearth ...

Page 6: ...ed end up Press down on each pipe section until the lances securely engage the hem on the fire placestarter Thewirewillassuretheproperspacing between the inner and outer pipe sections VENTING INSTALLATION OPTIONAL OUTSIDE AIR KIT MODEL AK4 AK4F The installation of an outside air kit should be per formed during the rough framing of the fireplace due to the nature of it s location Outside combus tion ...

Page 7: ...pipe between supports return elbow or 12S 8DM is 6 of angle run Maximum of two 6 angle run sections per chimney system see Figure 7 4 All pipe connections between the offset and return must be secured with two screws on the outer pipe only see Figure 9 page 8 Do not penetrate the inner stainless OFFSET RISE CHIMNEY LENGTH A B 48 36 24 18 12 4 3 8 16 3 8 ELBOW SET ONLY 9 3 4 25 1 2 1 12 3 4 30 3 4 ...

Page 8: ...of 8 PENETRATING THE ROOF To maintain a 1 clearance to the pipe on a roof with a pitch a rectangular opening must be cut 1 Determine the center point through which the pipe will penetrate the roof 2 Determine the center point of the roof Pitch is the distance the roof drops over a given span usually 12 A 6 12 pitch means that the roof drops 6 for each 12 one measure horizontally down from the roof...

Page 9: ...hing Cone Underlap Shingles at Bottom Overlap Shingles Top and Sides Only Figure 13 Flashing Installation Storm Collar Installation SC1 or SC2 Place storm collar over pipe and slide down until it is snug against the open edge of the flashing see Figure 14 Use SC1 for all round terminations and SC2 for all terminations with slip sections Apply waterproof caulk around the perimeter of the collar to p...

Page 10: ...re 16 Note If a decorative shroud is to be installed contact the manufacturer for specifications 10 FOOT RULE All flue gas outlet chimney terminations must extend a minimum of 3 feet in height above the highest point where it passes through the roof and must be at least 2 feet above the highest point of the roof that is within a horizontal distance of 10 feet see Figure 17 24 Min 24 Min 18 Min Typ F...

Page 11: ...add height Provide sufficient gas line into fireplace chamber for fitting connection see Figure 20 page 12 Note Secure incoming gas line to wood framing to provide rigidity for threaded end Figure 19 Gas Line Knockout Side Firebrick Finished Side Refractory Knockout Plug Outside of Fireplace Gas Line Conduit Insulation Gas Conduit Cover 1 2 Dowel 4 Repack insulation around gas line and into sleeve op...

Page 12: ...in accordance with the National Fuel Gas Code ANSI 7223NFPA 54 latest edition Seal Opening with Refractory Cement Outside of Fireplace Gas Line Conduit Repack Insulation Incoming 1 2 Black Iron Pipe Side Firebrick Finished Side Provide Enough Threaded End for Fitting Connection Figure 20 Gas Line Installation WARNING Toavoidtheriskof damagingthefireplacematerials andincreasingtheriskofspread ingafir...

Page 13: ...for the purpose of installing a vented or vent free decorative gas appliance incorporating an automatic shutoff de viceandcomplyingwiththeStandardforDecorative GasAppliances for Installation in Vented Fireplaces ANSI Z21 60 or American Gas Association draft re quirementsforGasFiredLogLightersforWoodBurn ing Fireplaces Draft NO 4 dated August 1993 OPERATION AND MAINTENANCE GUIDELINES Continued If y...

Page 14: ...11099 01C 14 ILLUSTRATED PARTS BREAKDOWN WOODBURNING FIREPLACE MODELS S42 S42H S42R S42RH VS42 1 AND VS42H 1 9 26 16 33 27 16 27 4 32 34 19 12 25 20 30 17 8 1 5 21 2 35 18 11 14 3 13 22 10 6 31 7 37 38 36 28 29 24 23 15 ...

Page 15: ...Pivot Clip 2 34 20090 Spring Clip 2 35 20280 Top Spacer 4 36 21171 Conduit Plate Cover 4 37 21379 Gas Conduit 2 38 21380 Gas Conduit 2 PARTS AVAILABLE NOT SHOWN 106625 01 Home Owner s Guide 1 Not a field replaceable part KEY NO PART NO DESCRIPTION QTY 9 107812 03 Left Refractory Textured White Brick 1 108169 03 Left Refractory Textured White Herringbone Brick 1 107812 02 Left Refractory Textured Re...

Page 16: ... 30 OFFSET AND RETURN ANTI DRAFT SHIELD ROUND TOP TERMINATION ONLY 30E 8DM STORM COLLAR ROOF FLASHING BI FOLD GLASS DOOR 0 TO 6 12 PITCH V6F 8DM 6 12 TO 12 12 PITCH V12F 8DM ANTIQUE BRASS FINISH GA6053 POLISHED BRASS FINISH GA6052 BLACK PAINTED FINISH GA6050 BDO42 BLACK FINISH BDO42B BRUSHED BRASS FINISH BDO42P PLATINUM FINISH ADJUSTABLE HOOD REQUIRED WHEN INSTALLING A VENT FREE GAS LOG IN THIS FI...

Page 17: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _______________________________________...

Page 18: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _______________________________________...

Page 19: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _______________________________________...

Page 20: ...2701 Industrial Drive P O Box 90004 Bowling Green KY 42102 9004 www desatech com NOT A UPC 111099 01 Rev C 09 05 111099 01 ...

Reviews: