VENT-FREE PROPANE/LP GAS COMPACT FIREPLACE

VMH10TPA

®

 WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space

or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the
methods described in the 

National Fuel Gas Code, ANS Z223.1, 1992, Section 5.3 or applicable local codes.

AIR FOR
COMBUSTION AND
VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install fireplace plus any adjoining rooms with doorless passageways or ventilation grills

between the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example:

 Space size 16 ft. (length) x 14 ft. (width) x 8 ft. (ceiling height) = 1792 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Multiply the space volume by 1000 Btu/Hr per 50 cubic feet to determine the maximum Btu/Hr the space can support.

_____________________ (volume of space) x (1000 Btu/Hr ÷ 50 cu. ft.) = (Maximum Btu/Hr the space can support)

Example:

 1792 cu. ft. (space volume) x (1000 Btu/Hr ÷ 50 cu. ft.) = 35,840 Btu/Hr. This is the maximum Btu/Hr the space can

support.

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free fireplace

______________________ Btu/Hr

Gas water heater*

______________________ Btu/Hr

Gas furnace

______________________ Btu/Hr

Vented gas heater

______________________ Btu/Hr

Gas fireplace logs

______________________ Btu/Hr

Other gas appliances* ______________________ Btu/Hr

Total

______________________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

35,840 Btu/Hr (maximum the space can support)

40,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining

room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 7.

C. Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

Example:

Gas water heater

30,000 Btu/Hr

Vent-free fir

10,000 Btu/Hr

Total

=

40,000 Btu/Hr

Summary of Contents for Vanguard VMH10TPA

Page 1: ...nt Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING Improper installa tion adjustment alteration ser vice or maintenance can cause injury...

Page 2: ...bris could fall into the control area of fireplace 8 You must operate this fireplace with the fireplace screen in place Make sure fireplace screen is in place before run ning fireplace 9 This fireplac...

Page 3: ...are packet 4 Checkfireplaceforanyshippingdamage If fireplace is damaged promptly inform dealer where you bought fireplace PRODUCT FEATURES SAFETY PILOT This fireplace has a pilot with an Oxygen Deplet...

Page 4: ...con tact flame If flame contacts branch soot will be created 7 Reattach screen by placing the notches in the screen frame over the shoulder screws and pushing down Figure 2 Assembling Fireplace WARNI...

Page 5: ...in buildings of unusually tight construction you must provide additional fresh air Unusually tight construction is de fined as construction where a walls and ceilings exposed to the outside atmosphere...

Page 6: ...an support 3 Add the Btu Hr of all fuel burning appliances in the space Vent free fireplace ______________________ Btu Hr Gas water heater ______________________ Btu Hr Gas furnace ___________________...

Page 7: ...n Grills into Adjoining Room Option 1 WARNING Rework work sheet adding the space of the adjoining unconfined space The combined spaces must have enough fresh air to supply all appliances in both space...

Page 8: ...the items listed below external regulator supplied by installer piping check local codes sealant resistant to propane LP gas manual shutoff valve test gauge connection ground joint union sediment trap...

Page 9: ...r instruc tions for power cord length Option two Have a licensed electri cian install a properly grounded three prong 120 volt electrical outlet at fire place location Locate outlet inside the framed...

Page 10: ...el above built in fireplace youmustmeetminimumclearancebetween mantel shelf and top of fireplace opening If your installation does not meet the below minimum clearances you must raise the mantel to an...

Page 11: ...er Louver As sembly Upper Louver Assembly Brass Screws Blower Bracket Mounting Holes 1 2 Remove Screw Valve Cover Shield Shoulder Screw Removing Valve Cover Shield 1 Open bottom louver assembly by swi...

Page 12: ...n the rear of the valve cover shield and through the rectangular hole in the front of shield see Figure 17 8 Reconnect red wire to switch position 3 Reconnect blue wire to switch posi tion 1 Reconnect...

Page 13: ...rd ware kit into one of the holes found on rear of valve cover shield The other hole is for a strain relief clamp not supplied to secure incoming electrical supply 2 Follow steps 2 through 6 in Instal...

Page 14: ...m going into fireplace controls If sediment trap is not installed or is installed wrong fireplace may not run properly Attaching Wood Base to Solid Floor For attaching base to solid floors concrete or...

Page 15: ...gas con nections A flexible gas line is provided to allow accessibility fromthefireplace seeFigure24 The flexible gas supply line con nection to the manual shutoff valve should be accessible INSTALLAT...

Page 16: ...Open Manual Shutoff Valve Figure 27 Checking Gas Joints Shown with Optional Mantel Figure 26 Manual Shutoff Valve Manual Shutoff Valve Propane LP Supply Tank Closed TestPressuresEqualToorLessThan 1 2...

Page 17: ...a qualified service technician or gas supplier Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified ser...

Page 18: ...it Turn control knob clockwise to the PILOT position THERMOSTAT CONTROL OPERATION 1 Follow steps 1 through 5 under Light ing Instructions page 17 2 With control knob pressed in strike match Hold match...

Page 19: ...ireplace off see To Turn Off Gas to Appliance page 18 see Troubleshooting pages 20 through 22 Thermocouple Pilot Burner Figure 32 Incorrect Pilot Flame Pattern Actual Pilot May Vary From Illustration...

Page 20: ...Control valve damaged REMEDY 1 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 2 Reconnect ignitor cable 3 Replace ignitor cable 4 Replace piezo ignitor 5 Replace ignitor 6...

Page 21: ...Dirty or partially clogged burner orifice 1 When heated vapors from furniture pol ish wax carpet cleaners etc turn into white powder residue REMEDY 1 Clean burner see Cleaning and Mainte nance page 23...

Page 22: ...statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak SeeWarning statement at top of page 1 Not enough combustion ventilation air OBSERVED PR...

Page 23: ...st thirty minutes 2 Inspect burner pilot and primary air inlet holes on injector holder for dust and dirt see Figure 35 3 Blow air through the ports slots and holes in the burner Figure 35 Injector Ho...

Page 24: ...GAS COMPACT FIREPLACE VMH10TPA 44 23 28 31 43 35 37 13 14 3 43 32 11 10 4 7 29 1 3 2 3 42 9 17 19 6 22 30 21 40 27 38 38 16 15 18 24 5 33 26 25 20 4 8 4 34 36 12 24 12 1 25 14 43 39 41 ILLUSTRATED PAR...

Page 25: ...87 01 Brass Screw 6 x 3 8 4 18 098303 02 Regulator Screw 2 19 104335 01CK Outer Shell Base 1 20 102649 02CJ Branch Support 1 21 099415 04 Gas Regulator 1 22 102875 01 Regulator Bracket 1 23 101381 01...

Page 26: ...pane LPornaturalgas purchase date Usually we will ask you to return the defec tive part to the factory PARTS NOT UNDER WARRANTY Contact authorized dealers of this product If they can t supply original...

Page 27: ...or paint Complete assembly instructions in cluded Three sided brass trim kit included MANUAL SHUTOFF VALVE GA5010 Manual shutoff valve with 1 8 NPT tap THERMOSTATICALLY CONTROLLED BLOWER KIT GA3400T P...

Page 28: ...efects caused by improper installation Travel diagnostic cost labor transportation and any and all such other costs related to repairing a defective fireplace will be the responsibility of the owner T...

Reviews: