OWNER’S MANUAL

AIR FOR
COMBUSTION AND
VENTILATION

Today’s homes are built more energy effi-
cient than ever. New materials, increased
insulation, and new construction methods
help reduce heat loss in homes. Home owners
weather strip and caulk around windows and
doors to keep the cold air out and the warm air
in. During heating months, home owners
want their homes as airtight as possible.

While it is good to make your home energy
efficient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning
appliances need fresh air for proper com-
bustion and ventilation.

Exhaust fans, fireplaces, clothes dryers, and
fuel burning appliances draw air from the
house to operate. You must provide ad-
equate fresh air for these appliances. This
will insure proper venting of vented fuel-
burning appliances.

 WARNING: This heater shall

not be installed in a confined space
or unusually tight construction
unless provisions are provided
for adequate combustion and ven-
tilation air. Read the following in-
structions to insure proper fresh
air for this and other fuel-burning
appliances in your home.

PROVIDING ADEQUATE
VENTILATION

The following are excerpts from National
Fuel Gas Code. NFPA 54/ANS Z223.1, Sec-
tion 5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three
following ventilation classifications:

1. Unusually Tight Construction

2. Unconfined Space

3. Confined Space

The information on pages 5 through 7 will
help you classify your space and provide
adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and win-
dows may provide enough fresh air for
combustion and ventilation. However, in
buildings of unusually tight construction,
you must provide additional fresh air.

Unusually tight construction is de-
fined as construction where:

a.

walls and ceilings exposed to the
outside atmosphere have a con-
tinuous water vapor retarder with
a rating of one perm (6 x 10

-11

 kg

per pa-sec-m

2

) or less with open-

ings gasketed or sealed 

and

b. weather stripping has been

added on openable windows and
doors 

and

c.

caulking or sealants are applied
to areas such as joints around
window and door frames, be-
tween sole plates and floors, be-
tween wall-ceiling joints, be-
tween wall panels, at penetra-
tions for plumbing, electrical, and
gas lines, and at other openings.

If your home meets all of the three
criteria above, you must provide ad-
ditional fresh air. See 

Ventilation Air

From Outdoors, page 7.

If your home does not meet all of the
three criteria above, proceed to 

De-

termining Fresh-Air Flow For Fire-
place Location, page 6.

Confined and Unconfined Space

The National Fuel Gas Code (ANS Z223.1,
1992 Section 5.3)
 defines a confined space
as a space whose volume is less than 50
cubic feet per 1,000 Btu per hour (4.8 m

3

 per

kw) of the aggregate input rating of all
appliances installed in that space and an
unconfining space as a space whose volume
is not less than 50 cubic feet per 1,000 Btu
per hour (4.8 m

3

 per kw) of the aggregate

input rating of all appliances installed in that
space. Rooms communicating directly with
the space in which the appliances are in-
stalled*, through openings not furnished
with doors, are considered a part of the
unconfined space.

This heater shall not be installed in a con-
fined space or unusually tight construction
unless provisions are provided for adequate
combustion and ventilation air.

* Adjoining rooms are communicating only
if there are doorless passageways or ventila-
tion grills between them.

Continued

Summary of Contents for Vanguard VMH10TPA

Page 1: ...nt Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING Improper installa tion adjustment alteration ser vice or maintenance can cause injury...

Page 2: ...bris could fall into the control area of fireplace 8 You must operate this fireplace with the fireplace screen in place Make sure fireplace screen is in place before run ning fireplace 9 This fireplac...

Page 3: ...are packet 4 Checkfireplaceforanyshippingdamage If fireplace is damaged promptly inform dealer where you bought fireplace PRODUCT FEATURES SAFETY PILOT This fireplace has a pilot with an Oxygen Deplet...

Page 4: ...con tact flame If flame contacts branch soot will be created 7 Reattach screen by placing the notches in the screen frame over the shoulder screws and pushing down Figure 2 Assembling Fireplace WARNI...

Page 5: ...in buildings of unusually tight construction you must provide additional fresh air Unusually tight construction is de fined as construction where a walls and ceilings exposed to the outside atmosphere...

Page 6: ...an support 3 Add the Btu Hr of all fuel burning appliances in the space Vent free fireplace ______________________ Btu Hr Gas water heater ______________________ Btu Hr Gas furnace ___________________...

Page 7: ...n Grills into Adjoining Room Option 1 WARNING Rework work sheet adding the space of the adjoining unconfined space The combined spaces must have enough fresh air to supply all appliances in both space...

Page 8: ...the items listed below external regulator supplied by installer piping check local codes sealant resistant to propane LP gas manual shutoff valve test gauge connection ground joint union sediment trap...

Page 9: ...r instruc tions for power cord length Option two Have a licensed electri cian install a properly grounded three prong 120 volt electrical outlet at fire place location Locate outlet inside the framed...

Page 10: ...el above built in fireplace youmustmeetminimumclearancebetween mantel shelf and top of fireplace opening If your installation does not meet the below minimum clearances you must raise the mantel to an...

Page 11: ...er Louver As sembly Upper Louver Assembly Brass Screws Blower Bracket Mounting Holes 1 2 Remove Screw Valve Cover Shield Shoulder Screw Removing Valve Cover Shield 1 Open bottom louver assembly by swi...

Page 12: ...n the rear of the valve cover shield and through the rectangular hole in the front of shield see Figure 17 8 Reconnect red wire to switch position 3 Reconnect blue wire to switch posi tion 1 Reconnect...

Page 13: ...rd ware kit into one of the holes found on rear of valve cover shield The other hole is for a strain relief clamp not supplied to secure incoming electrical supply 2 Follow steps 2 through 6 in Instal...

Page 14: ...m going into fireplace controls If sediment trap is not installed or is installed wrong fireplace may not run properly Attaching Wood Base to Solid Floor For attaching base to solid floors concrete or...

Page 15: ...gas con nections A flexible gas line is provided to allow accessibility fromthefireplace seeFigure24 The flexible gas supply line con nection to the manual shutoff valve should be accessible INSTALLAT...

Page 16: ...Open Manual Shutoff Valve Figure 27 Checking Gas Joints Shown with Optional Mantel Figure 26 Manual Shutoff Valve Manual Shutoff Valve Propane LP Supply Tank Closed TestPressuresEqualToorLessThan 1 2...

Page 17: ...a qualified service technician or gas supplier Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified ser...

Page 18: ...it Turn control knob clockwise to the PILOT position THERMOSTAT CONTROL OPERATION 1 Follow steps 1 through 5 under Light ing Instructions page 17 2 With control knob pressed in strike match Hold match...

Page 19: ...ireplace off see To Turn Off Gas to Appliance page 18 see Troubleshooting pages 20 through 22 Thermocouple Pilot Burner Figure 32 Incorrect Pilot Flame Pattern Actual Pilot May Vary From Illustration...

Page 20: ...Control valve damaged REMEDY 1 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 2 Reconnect ignitor cable 3 Replace ignitor cable 4 Replace piezo ignitor 5 Replace ignitor 6...

Page 21: ...Dirty or partially clogged burner orifice 1 When heated vapors from furniture pol ish wax carpet cleaners etc turn into white powder residue REMEDY 1 Clean burner see Cleaning and Mainte nance page 23...

Page 22: ...statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak SeeWarning statement at top of page 1 Not enough combustion ventilation air OBSERVED PR...

Page 23: ...st thirty minutes 2 Inspect burner pilot and primary air inlet holes on injector holder for dust and dirt see Figure 35 3 Blow air through the ports slots and holes in the burner Figure 35 Injector Ho...

Page 24: ...GAS COMPACT FIREPLACE VMH10TPA 44 23 28 31 43 35 37 13 14 3 43 32 11 10 4 7 29 1 3 2 3 42 9 17 19 6 22 30 21 40 27 38 38 16 15 18 24 5 33 26 25 20 4 8 4 34 36 12 24 12 1 25 14 43 39 41 ILLUSTRATED PAR...

Page 25: ...87 01 Brass Screw 6 x 3 8 4 18 098303 02 Regulator Screw 2 19 104335 01CK Outer Shell Base 1 20 102649 02CJ Branch Support 1 21 099415 04 Gas Regulator 1 22 102875 01 Regulator Bracket 1 23 101381 01...

Page 26: ...pane LPornaturalgas purchase date Usually we will ask you to return the defec tive part to the factory PARTS NOT UNDER WARRANTY Contact authorized dealers of this product If they can t supply original...

Page 27: ...or paint Complete assembly instructions in cluded Three sided brass trim kit included MANUAL SHUTOFF VALVE GA5010 Manual shutoff valve with 1 8 NPT tap THERMOSTATICALLY CONTROLLED BLOWER KIT GA3400T P...

Page 28: ...efects caused by improper installation Travel diagnostic cost labor transportation and any and all such other costs related to repairing a defective fireplace will be the responsibility of the owner T...

Reviews: