CHASE INSTALLATIONS

Instructions for chase installations are included 

with  the  chase  style  termination  chosen.  In  a 

multiple chase installation, be sure to provide 

adequate distance between terminations to prevent 

smoke spillage from one termination to another. 

We suggest that terminations be separated at least 

24", center to center and stacked at a vertical height 

difference of 18" (see Figure 16).

Note:

 If a decorative shroud is to be installed, 

contact the manufacturer for specifications.

Venting inStallatiOn

Continued

10 FOOT RULE

All flue gas outlet chimney terminations must 

extend a minimum of 3 feet in height above the 

highest point where it passes through the roof and 

must be at least 2 feet above the highest point of 

the roof that is within a horizontal distance of 10 

feet (see Figure 17).

FINISHING THE FIREPLACE

Combustible materials, such as wallboard, gypsum 

board, sheet rock, drywall, plywood, etc. may make 

direct contact with sides and top around the fireplace 

face. It is important that combustible materials do 

not overlap the face itself. Brick, glass, tile or other 

noncombustible materials may overlap the front 

face provided they do not obstruct essential open

-

ings like louvered slots or any other opening. When 

overlapping with a noncombustible facing material, 

use only noncombustible mortar or adhesive.

OptiOnal gaS line 

inStallatiOn

Gas line hook up should be done by your supplier 

or a qualified service person.

Note

: Before you proceed, make sure your gas 

supply is turned off.

Use only a 1/2" black iron pipe and appropriate 

fittings. 

1.  Remove knockout indentation on refractory or 

firebrick wall located above the refractory hearth 

floor. The knockout indentation must be firmly 

tapped with any solid object such as a 1/2" dowel 

until it is released. Remove fragmented portions 

of refractory (see Figure 18, page 13).

2.  Remove gas line cover plate located on either 

side of fireplace and pull out insulation from gas 

line conduit sleeve. Save insulation for reuse. 

Replace screws.

3.  Run a 1/2" black iron gas line into the fireplace 

through the rear at gas line conduit sleeve (if 

using a raised platform, add height). Provide 

sufficient gas line into fireplace chamber for 

fitting connection (see Figure 19, page 13). 

Note

:  Secure  incoming  gas  line  to  wood 

framing to provide rigidity for threaded end.

4.  Repack insulation around gas line and into 

sleeve opening. Seal any gaps between gas line 

and refractory knockout hole with refractory ce

-

ment or commercial furnace cement, Install the 

gas appliance or cap-off gas line if desired.

4" Min.

4" Min.

18" 

Min.
Typ.

Figure 16 - Multiple Chase Installation

10'

' Min.

10'

3' Min.

' Min.

3' Min.

Level of 
Flue Gas 

Outlet

Figure 17 - 10 Foot Rule

Summary of Contents for JM36 Series

Page 1: ...for use with a vented gas log approved to ANS Z21 60 Z21 84 or RGA 2 72 standards or for use with a vent free gas log heater approved toANS Z21 11 2 standard This wood burning fireplace complies with...

Page 2: ...e of any component part not manufac tured or approved by DESAin combination with a DESA fireplace system Proper installation is the most important step in ensuring safe and continuous operation of the...

Page 3: ...2 AIR SPACE BACK AND SIDES 0 TO BOTTOM GAS LINE KNOCKOUTS 12 EACH SIDE COMBUSTIBLE WALL BOARD NO COMBUSTIBLE MATERIAL ON FACE MINIMUM 12 TO PERPENDICULAR SIDEWALL HEARTH EXTENSION 60 X 20 1 CHIMNEY AI...

Page 4: ...67 11 GAS LINE KNOCK OUTS AIR KIT KNOCK OUT LEFT SIDE OUTSIDE AIR 11 2 AIR SPACE BACK AND SIDES 0 TO BOTTOM GAS LINE KNOCKOUTS 12 EACH SIDE COMBUSTIBLE WALL BOARD NO COMBUSTIBLE MATERIAL ON FACE MINI...

Page 5: ...RIAL TERMINATION SQUARE CHASE TOP ROUND TOP TERMINATION COMBUSTIBLE WALL BOARD NO COMBUSTIBLE MATERIAL ON FACE 0 TO BOTTOM OUTSIDE AIR 11 2 AIR SPACE BACK AND SIDES GAS LINE KNOCKOUTS 12 EACH SIDE MIN...

Page 6: ...allation The minimum height of the chimney measured from the base of the fireplace to the flue gas outlet of the termination is 9 5 feet minimum of 4 feet of chimney pipe sections required for outdoor...

Page 7: ...hearth extension with a non combustible material see Figure 3 WARNING Hearthextension is to be installed only as shown in Figure 3 Fireplace Installation Continued Figure 3 Hearth Extension Seal Gap...

Page 8: ...imney together it is important to assure the joint between the chimney sections is locked Check by pulling chimney upward after locking The chimney will not come apart if properly locked It is not nec...

Page 9: ...3 4 4 OFFSET CHART 22 50 FT SYSTEM HEIGHT Figure 7 Typical Offset Terminations Return Elbow Offset Elbow Return Elbow Offset Elbow 6 Max 6 Max 6 Max 6 Max 6 Max 6 Max Return Elbow Offset Elbow Offset...

Page 10: ...ling Frame Firestop Spacer Screws or Staples Min of 8 Firestop Spacer Screws or Staples Min of 8 Penetrating the roof To maintain a 1 JM36 or 2 JM42 JM50 clear ance to the pipe on a roof with a pitch...

Page 11: ...f using 8 x 3 4 screws and then sealed with roof coating to prevent leakage through the screw holes A roof coating must also be applied around the perimeter of the flashing to provide a proper seal Na...

Page 12: ...her opening When overlapping with a noncombustible facing material use only noncombustible mortar or adhesive Optional Gas Line Installation Gas line hook up should be done by your supplier or a quali...

Page 13: ...s log the damper must be removed or permanently locked in the fully open position and the glass doors must be in the fully open position Figure 18 Gas Line Knockout Side Firebrick Finished Side Refrac...

Page 14: ...RIGHT PANEL HEARTH PANEL AH Q P AG AC AE AF FULL AF AF AP AC AG AT AG Q AI Q AI C C D D FULL C D C G FULL FULL G FULL FULL FULL FULL FULL H H I I M M AB L FULL D C AS C FULL FULL FULL FULL FULL FULL...

Page 15: ...Installation for Model V JM42 Brick Installation Continued See instruction on page 14 before installing brick AO REAR PANEL RIGHT PANEL HEARTH PANEL R FULL FULL FULL FULL FULL FULL FULL B D C A B C A...

Page 16: ...A AB AC AD Box 1 Hearth 36 2 Box 2 Rear 36 2 Box 3 Left or Right 36 1 2 Box 4 Left or Right 36 1 2 TOTAL 4 0 0 0 0 0 0 0 0 0 0 2 4 0 brick matrix for model V JM36 Continued Brick Matrix AE AF AG AH AI...

Page 17: ...W X Y Z AA AB AC AD Box 1 Hearth 42 2 2 2 2 2 2 Box 2 Rear 42 1 Box 3 Left or Right 42 1 1 Box 4 Left or Right 42 1 1 TOTAL 3 2 0 0 2 2 2 2 2 0 2 0 0 0 Brick Matrix V JM42 brick matrix for model V JM4...

Page 18: ...ix Q R S T U V W X Y Z AA AB AC AD Box 1 Hearth 50 Box 2 Rear 50 3 Box 3 Left or Right 50 1 1 Box 4 Left or Right 50 1 1 TOTAL 5 2 0 0 0 0 0 0 0 0 0 0 0 0 Brick Matrix V JM50 brick matrix for model V...

Page 19: ...of grout mixture This will keep the mixture moist and it will not dry out before use 5 Begin grouting by first doing a Filler Pass This is done by filling the joint about 3 4 full with grout mixture...

Page 20: ...door frame into face opening and tighten screws see Figure 25 door frame MODELS BDMO36E G C BDMO42E G C AND BDMO50E G C Installation 1 Remove screws from smoke shelf see Figure 26 2 Mount top door fra...

Page 21: ...he glass must be allowed to warm slowly and evenly The tempered glass will withstand a gradual temperature rise to 550 F which is more than a normal fire will generate Such materials as pitch wax lade...

Page 22: ...tallation in Vented Fireplaces ANSI Z21 60 or American Gas Association draft requirements for Gas Fired Log Lighters for Wood Burning Fireplaces Draft NO 4 dated August 1993 If you wish to install an...

Page 23: ...BDM42E 42 Ebony BDM42G 42 Pewter BDM42C 42 Oiled Bronze BDM50E 50 Ebony BDM50G 50 Pewter BDM50C 50 Oiled Bronze BDMO36E 36 Ebony BDMO36G 36 Pewter BDMO36C 36 Oiled Bronze BDMO42E 42 Ebony BDMO42G 42...

Page 24: ...OT A UPC 117541 01 Rev B 11 05 117541 01 Firestop Spacer FS 10 1100EFS 10DM for model GM36 Roof Flashing V6F 10DM 0 to 6 12 Pitch V12F 10DM 6 12 to 12 12 Pitch Replacement and Accessory Parts Continue...

Reviews: