background image

www.desatech.com

113900-01D

6

AIR FOR COMBUSTION 

AND VENTILATION

Continued

  WARNING:  If  the  area  in 

which  the  firebox  and  gas  log 

heater  may  be  operated  is 

smaller  than  that  defined  as 

an  unconfined  space  or  if  the 

building  is  of  unusually  tight 

construction, provide adequate 

combustion and ventilation air 

by one of the methods described 

in the 

National Fuel Gas Code, 

ANSI Z223.1/NFPA 54 Section 5.3 

or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building 

This  fresh  air  would  come  from  an  adjoin-
ing  unconfined  space.  When  ventilating  to 
an  adjoining  unconfined  space,  you  must 
provide two permanent openings: one within 
1" of the ceiling and one within 1" of the 
floor on the wall connecting the two spaces 
(see options 1 and , Figure 4). You can also 
remove door into adjoining room (see option 
3,  Figure  4).  Follow  the 

National  Fuel  Gas 

Code ANSI Z223.1/NFPA 54, Section 5.3, Air 
for Combustion and Ventilation

 for required 

size of ventilation grills or ducts. 

Figure 4 - Ventilation Air from Inside 

Building

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills 

Into Adjoining Room,

Option 2

Ventilation

Grills 

Into Adjoining 

Room,

Option 1

12"

12"

3.  Add the Btu/Hr of all fuel burning appliances 

in the space.

 

Vent-free heater 

 __________ Btu/Hr

 

Gas water heater* 

 __________ Btu/Hr

 

Gas furnace 

 __________ Btu/Hr

 

Vented gas heater 

 __________ Btu/Hr

 

Gas fireplace logs 

 __________ Btu/Hr

 

Other gas appliances* + ________ Btu/Hr

 

Total                            =  ________ Btu/Hr

 

* Do not include direct-vent gas appliances. 
Direct-vent  draws  combustion  air  from  the 
outdoors and vents to the outdoors.

 

Example:

 

Gas water heater 

 _________ Btu/Hr

 

Vent-free fireplace   

+ ________ Btu/Hr

 

Total                              = ________ Btu/Hr

4.  Compare  the  maximum  Btu/Hr  the  space 

can support with the actual amount of Btu/Hr 
used.

 

  _______ Btu/Hr (maximum the space can 
support)

 

  _______ Btu/Hr (actual amount of Btu/Hr 
used)

 

Example:

  51,00  Btu/Hr  (maximum  the 

space can support) 

 

 

79,000 Btu/Hr (actual amount of 
Btu/Hr used)

The space in the above example is a confined 
space because the actual Btu/Hr used is more 
than  the  maximum  Btu/Hr  the  space  can  sup-
port. You must provide additional fresh air. Your 
options are as follows:

A.  Rework worksheet, adding the space of an 

adjoining room. If the extra space provides 
an unconfined space, remove door to adjoin-
ing  room  or  add  ventilation  grills  between 
rooms.  See 

Ventilation  Air  From  Inside 

Building

 below.

B.  Vent room directly to the outdoors. See 

Ventilation Air From Outdoors

.

C.  Install  a  lower  Btu/Hr  heater,  if  lower 

Btu/Hr size makes room unconfined. 

If  the  actual  Btu/Hr  used  is  less  than  the 
maximum Btu/Hr the space can support, the 
space is an unconfined space. You will need 
no additional fresh air ventilation. 

  40,000
  39,000
  79,000

Summary of Contents for HDFB32C

Page 1: ...y ANSI Z21 11 2 ap proved gas logs This appliance may be installed in an aftermarket per manently located manufactured mobile home where not prohibited by local codes This appliance is only for use wi...

Page 2: ...ith this heater WARNING Donotallowfans to blow directly into the firebox Avoidanydraftsthatalterburner flame patterns Ceiling fans can create drafts that alter burner flame patterns Altered burner pat...

Page 3: ...o not use the firebox if it has been un der water due to the shock hazard that could result with the blower accessary if installed in place 11 Provide adequate clearances around air openings SAFETY IN...

Page 4: ...nsureproperfresh air for this and other fuel burning appliances in your home Today s homes are built more energy efficient than ever New materials increased insulation and new construction methods hel...

Page 5: ...ome meets all of the three criteria above you must provide additional fresh air See Ventilation Air From Outdoors page 6 If your home does not meet all of the three criteria above proceed to Determini...

Page 6: ...s water heater ___________ Btu Hr Gas furnace ___________ Btu Hr Vented gas heater ___________ Btu Hr Gas fireplace logs ___________ Btu Hr Other gas appliances _________ Btu Hr Total _ ________ Btu H...

Page 7: ...ge 12 Ventilation Air From Outdoors Provide extra fresh air by using ventilation grills or ducts You must provide two perma nent openings one within 12 of the ceiling and one within 12 of the floor Co...

Page 8: ...uchorextendbeyond the fireplace screen If your installation does not meet the mini mum clearances in Figure 7 you must raise the mantel to an acceptable height OR remove the mantel Example Figure 6 Mi...

Page 9: ...front panel pushing the plastic control shaft forward through the opening see Figure 10 INSTALLation Continued 3 While supporting speed control secure control shaft with lock nut by pushing and turnin...

Page 10: ...pickuplog base assembly by burners This could damage burners Only handle base by grates CAUTION Donotremovethe dataplatesattachedtotheheater base assembly The data plates contain important warranty an...

Page 11: ...d with mantel As sembly instructions are included with each accessory 2 If using a blower install a properly grounded 120 volt three prong electrical outlet at firebox location if an outlet is not the...

Page 12: ...ll 39 3 8 27 7 8 55 5 8 34 3 4 Figure 19 Rough Opening for Installing in Corner 34 3 4 17 3 4 33 1 Frame in rough opening Use dimensions shown in Figure 18 for the rough opening If installing in a cor...

Page 13: ...lappingthefront facing with noncombustible facing material Technical Service You may have further questions about instal lation operation or troubleshooting If so contact DESA Heating Products Technic...

Page 14: ...ings fluted sides and medallion Accessories Purchase these fireplace accessories from your local dealer If they can not supply these accessories call DESAHeating Products Sales Department at 1 866 672...

Page 15: ...and Rapids MI 49504 2672 616 791 0505 1 800 446 1446 www nbmc com Parts Centrals These Parts Centrals are privately owned businesses They have agreed to support our customer s needs by providing origi...

Page 16: ...www desatech com 113900 01D 16 5 14 14 21 13 14 6 1 14 7 14 18 12 12 20 8 16 11 15 17 9 4 2 3 2 14 10 15 19 Illustrated Parts Breakdown HDFB32C...

Page 17: ...rick Retainer 3 3 114042 01 Rear Firebrick 1 4 114042 02 Side Firebrick 2 5 103207 01 Outer Casing 1 6 Outer Shell Base 1 7 Firebox Wrapper 1 8 103297 01 Assembly Screen 2 9 103773 05 Front Assembly 1...

Page 18: ..._____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____...

Page 19: ..._____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____...

Page 20: ...inal condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects caused by improper installation Travel diagnos...

Reviews: