background image

5

107340

OWNER’S MANUAL

AIR FOR
COMBUSTION AND
VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between

the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example:

 Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) 

÷

 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example:

 2560 cu. ft. (volume of space) 

÷

 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

___________________ Btu/Hr

Gas water heater*

___________________ Btu/Hr

Gas furnace

___________________ Btu/Hr

Vented gas heater

___________________ Btu/Hr

Gas fireplace logs

___________________ Btu/Hr

Other gas appliances* ___________________ Btu/Hr

Total

___________________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

70,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-

ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

Continued

Example:

Gas water heater

40,000

Btu/Hr

Vent-free heater +

30,000

Btu/Hr

Total

=

70,000

Btu/Hr

 WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space,

or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of
the methods described in the 

National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.

Summary of Contents for Glo-Warm FGHS30NGB

Page 1: ...rformed by a qualified installer service agency or the gas supplier Aftermarket Completion of sale not for purpose of resale from the manufacturer WARNING This is an unvented gas fired heater It uses...

Page 2: ...ilation to run properly This heater has an Oxygen Depletion Sensing ODS safety shutoff system The ODS shuts down the heater if not enough fresh air is available See Air for Combustion and Ventilation...

Page 3: ...If heater is damaged promptly inform dealer where you bought heater Figure 1 Vent Free Natural Gas Heater Ignitor Button Control Knob Heater Cabinet Front Panel PRODUCT FEATURES SAFETY DEVICE This he...

Page 4: ...ion and ventilation However in buildings of unusually tight construction you must provide additional fresh air Unusually tight construction is de fined as construction where a walls and ceilings expos...

Page 5: ...include direct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr use...

Page 6: ...atticwillactivatethepowervent AIR FOR COMBUSTION AND VENTILATION Continued Or Remove Door into Adjoining Room Option 3 Ventilation Grills Into Adjoining Room Option 2 12 12 Ventilation Grills into Adj...

Page 7: ...n and Ventilation pages 4 through 6 CAUTION This heater cre ates warm air currents These currents move heat to wall sur faces next to heater Installing heater next to vinyl or cloth wall coverings or...

Page 8: ...et Removing Front Panel Of Heater 1 Remove two screws near bottom cor ners of front panel 2 Liftstraightupongrillguarduntilitstops Grill guard will slide up about 1 4 3 Pull bottom of front panel forw...

Page 9: ...acket and into wall anchors 7 Tighten screws until mounting bracket is firmly fastened to wall Figure 12 Installing Bottom Mounting Screws Figure 10 Popping Open Anchor Wings For Thin Walls Figure 11...

Page 10: ...alled wrong heater may not run properly IMPORTANT Holdpressureregulatorwith wrench when connecting it to gas piping and or fittings CAUTION Use only new black iron or steel pipe Inter nally tinned cop...

Page 11: ...ent shutoff valve see Figure 14 2 Open main gas valve located on or near gas meter 3 Make sure control knob of heater is in the OFF position 4 Check all joints from equipment shutoff valve to thermost...

Page 12: ...theequip ment shutoff valve Figure 17 Pilot LIGHTING INSTRUCTIONS 1 STOP Read the safety information column 3 page 11 2 Make sure equipment shutoff valve is fully open 3 Turn control knob clockwise Cl...

Page 13: ...ol areas burner and circu lating air passageways of heater clean Inspect these areas of heater before each use Have heaterinspectedyearlybyaquali fied service person Heater may need more frequent clea...

Page 14: ...llowing A Low gas pressure B Dirty or partially clogged ODS pilot 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Replace ignitor 2 Replace ignitor 3 Reconnect ignitor cable 4 Free ignitor cab...

Page 15: ...em will stop after a few hours of operation 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local natural gas c...

Page 16: ...g statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak SeeWarning statement at top of page 1 Not enough combustion ventilation air OBSERVED P...

Page 17: ...2 0724 www tarantin com Heater and Fireplace Store 58 Halbe Lane Cape May Court NJ 08210 1110 609 390 9774 Parts Department Dayton Hardware P O Box 275 North Dayton Station Dayton OH 45404 0275 All St...

Page 18: ...BLUE FLAME NATURAL GAS HEATER ILLUSTRATED PARTS BREAKDOWN THERMOSTAT MODEL FGHS30NGB 7 7 5 2 5 27 22 26 23 19 17 24 25 12 26 21 20 18 9 8 18 16 10 16 13 1 14 14 15 7 6 11 3 7 4 7 7 24 1 24 2 ODS Pilot...

Page 19: ...1 097159 04 Ignitor 1 12 L98411 01 Ignitor Line 1 13 L99029 03 Pressure Regulator 1 14 L98801 01 Washer 2 15 L98806 01 Self Tapping Screw 2 16 L98115 03 Main Inlet Tube Assembly 1 17 L98123 06 ODS Lin...

Page 20: ...produce specified heat When Gas Quality Is Bad pilot will not stay lit burner will produce flames and soot heater will backfire when lit Youmayfeelyourgaspressureistoolowor gas quality is bad If so c...

Page 21: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Page 22: ...oids this warranty The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit This warranty does not apply to parts that are not...

Reviews: