INSTALLATION
Continued
NOTICE: Manual control heaters
may be used as a vented product.
If so, you must always run heater
with chimney flue damper open.
If running heater with damper
open, noncombustible material
above fireplace opening is not
needed. Go to
Installing Damper
Clamp Accessory for Vented
Operation
, page 12.
Minimum Noncombustible Material
Clearances
If Not Using Mantel
Note: If using a mantel proceed to If Using
Mantel. If not using a mantel, follow the infor-
mation on this page.
You must have noncombustible material(s)
above the fireplace opening. Noncombustible
materials (such as slate, marble, tile, etc.)
must be at least 1/2" thick. With sheet metal,
you must have noncombustible material be-
hind it. Noncombustible material must extend
at least 8" up. If noncombustible material is
less than 12", you must install the fireplace
hood accessory. See Figure 5 for minimum
clearances.
If Using Mantel
You must have noncombustible material(s)
above the fireplace opening. Noncombustible
materials (such as slate, marble, tile, etc.)
must be at least 1/2" thick. With sheet metal,
you must have noncombustible material be-
hind it. Noncombustible material must extend
at least 8" up. If noncombustible material is
less than 12", you must install the fireplace
hood accessory. Even if noncombustible
material is more than 12", you may need the
hood accessory to deflect heat away from
your mantel shelf. See Figure 5 and Figures 6
and 7, page 11, for minimum clearances.
IMPORTANT:
If you cannot meet these mini-
mum clearances, you must operate heater
with chimney flue damper open. Go to
Install-
ing Damper Clamp Accessory for Vented
Operation
, page 12.
Heat Resistant
Material
(A)
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
Noncombustible
Material Distance
(A)
Requirements for Safe
Installation
12" or more
Noncombustible mate-
rial OK.
Between 8" and 12"
Install fireplace hood
accessory (GA6050,
GA6052 or GA6053 see
Accessories
, page 30).
Less than 8"
Noncombustible material
must be extended to at
least 8".
See Between
8" and 12",
above. If you
cannot extend material,
you must operate heater
with flue damper open.
MANTEL CLEARANCES
In addition to meeting noncombustible mate-
rial clearances, you must also meet required
clearances between fireplace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between man
-
tel shelf and top of fireplace opening, a hood
is not required (see Figure 6, page 11).
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6, page 11,
are not met, you must have a hood. When
using a hood there are still certain minimum
mantel clearances required. Follow minimum
clearances shown in Figure 7, page 11, when
using hood.