background image

www.desatech.com

115481-01A

8

INSTALLATION

Continued 

Figure 5 - Equipment Shutoff Valve

Equipment 
Shutoff 
Valve

Open

Closed

Figure 7 - Checking Gas Joints  

(Natural Gas Only)

Control Valve 
Location

Equipment
Shutoff Valve

Propane/LP
Supply Tank

Equipment 
Shutoff Valve

Gas Meter

Figure 6 - Checking Gas Joints  

(Propane/LP Gas Only)

Control Valve 
Location

4.  Check all joints of gas supply piping system. 

Apply noncorrosive leak detection fluid to all 

joints. Bubbles forming show a leak. 

5.  Correct all leaks at once.
6.  Reconnect  heater  and  equipment  shutoff 

valve to gas supply. Check reconnected fit-

tings for leaks. 

Test Pressures Equal To or Less Than 
1/2 PSIG (3.5 kPa)

1.  Close equipment shutoff valve (see Figure 5).
2.  Pressurize  supply  piping  system  by  either 

opening propane/LP supply tank valve for 

propane/LP gas or opening main gas valve 

located on or near gas meter for natural gas 

or using compressed air.

3.  Check all joints from gas meter to equipment 

shutoff valve for natural gas or propane/LP 

supply to equipment shutoff valve for propane/

LP (see Figure 6 or 7). Apply noncorrosive 

leak  detection  fluid  to  all  joints.  Bubbles 

forming show a leak. 

4.  Correct all leaks at once.

Gas Pressure Check

The appliance regulator controls the burner pres-

sure which should be checked at the pressure test 

point (1/8" NPT plugged tap) located near the on 

the control valve identified OUT for the manifold 

side and IN for inlet pressure. Make sure operating 

pressures are within the limits shown in 

Specifica-

tions

, page 15.

The  pressure  should  be  checked  with  the  unit 

burning and set to High. Replace test point plug 

or tighten test screw after pressure measurement 

ensuring no gas leaks.

PLACEMENT OF FLOOR MEDIA

 WARNING: Do not add ex-

tra logs or ornaments such as 

pine cones, vermiculite or rock 

wool. Using these added items 

can cause sooting. Use only the 

material included in the kits.

 WARNING: Do not place lava 

rock, embers or fiber log pieces on 

logs or burners. This may cause 

sooting. Place floor media material 

only on the fireplace floor.

1.  Place lava rock around base of unit making sure 

the burner ports and valve access are not blocked 

(see Figure 8, page 9). Retain a small amount of 

lava rock to be used in step 4, page 9.

2.  Place ember material around front and sides 

of unit close to (but NOT on) the burner (see 

Figure 9, page 9). Embers will "glow" when 

heated to enhance the realistic look of your 

log set.

Summary of Contents for Design Dynam

Page 1: ...ny appliance Do not touch any electrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach you...

Page 2: ...ANSI Z233 1 NFPA 54 Section 5 3 Air for Combustion and Ventilation This appliance may be installed in an aftermarket per manently located manufactured mobile home where not prohibited by local codes...

Page 3: ...ts Make certain you read and understand all warnings Keep this manual for reference It is your guide to safe and proper operation of this log set WARNING Any change to this log set or its controls can...

Page 4: ...he vents before operating heater 7 Toreducethecreationofsoot followtheinstruc tions in Cleaning and Maintenance page 12 8 Do not run heater where ammable liquids or vapors are used or stored under dus...

Page 5: ...f highly heated A dirtychimney uemaycreateand distribute soot within the house Inspectchimney uefordamage If damaged repair ue damper before operating appliance CAUTION Thisheatercreates warmaircurren...

Page 6: ...ated pro pane LP tank may cause an explosion Propane LP Supply Tank External Regulator Vent Pointing Down Figure 3 External Regulator with Vent Pointing Down Figure 2 Attaching Damper Clamp Manufactur...

Page 7: ...y to freeze A sediment trap traps moisture and contaminants This keeps them from going into heater controls If sediment trap is not installed or is installed wrong heater may not run properly Figure 4...

Page 8: ...detection fluid to all joints Bubbles forming show a leak 4 Correct all leaks at once Gas Pressure Check The appliance regulator controls the burner pres sure which should be checked at the pressure t...

Page 9: ...d OPERATING APPLIANCE The RF Millivolt valve control used on these appli ances allows you to turn the gas log set on or off use a timer to automatically operate the log set increase or decrease ame he...

Page 10: ...appliance and to replace any part of the control system and any gas control which has been under water OPERATING HEATER Continued LIGHTING INSTRUCTIONS NOTICE During initial operation the appliance wi...

Page 11: ...until mode is OFF Pilot stays lit Shut Off Main Burner Without Remote Turn PilotStat knob to PILOT Pilot stays lit Shut Off Main Burner and Pilot Turn PilotStat knob to OFF CAUTION During normal shutd...

Page 12: ...lide the battery compartment door off to expose old batteries Place new batteries into housing and reattach door See Figure 15 Figure 15 Bottom of Transmitter Showing Battery Compartment and Door TECH...

Page 13: ...ntrol system be sure external gas shut off valve located at gas supply inlet is in the ON position POSSIBLE CAUSE REMEDY OBSERVED PROBLEM 1 Defective ignitor no spark at electrode 2 Defective or misal...

Page 14: ...2 Check thermopile with mil livolt meter Take reading at thermopile terminals of gas valve It should read 325 mil livolts minimum with optional wall switch OFF Replace faulty thermopile if reading is...

Page 15: ...10 6 3 W C 3 5 1 6 W C 10 6 3 W C Inlet Gas Pressure in of water Maximum 10 5 W C 13 W C 10 5 W C 13 W C Minimum 5 0 W C 11 W C 5 0 W C 11 W C Valve Operation RF Millivolt RF Millivolt RF Millivolt RF...

Page 16: ...m 115481 01A 16 ILLUSTRATED PARTS BREAKDOWN HCA 24 RFN HCA 24 RFP HCA 18 RFN HCA 18 RFP HCM 24 RFN HCM 24 RFP HCM 18 RFN HCM 18 RFP HKE 24 RFN HKE 24 RFP HKE 18 RFN HKE 18 RFP 1 3 7 6 5 4 2 8 9 10 12...

Page 17: ...ket 1 9 115491 01 115492 01 115492 01 115493 01 Air Shutter 1 10 115454 01 115454 01 115454 01 115454 02 Venturi 1 11 115452 01 115452 01 115452 01 115452 01 Valve Bracket 1 12 115488 01 115488 01 115...

Page 18: ...on the back page of this manual EQUIPMENT SHUTOFF VALVE GA5010 Equipment shutoff valve with 1 8 NPT tap Fits 1 2 pipe FIREPLACE HOOD Black GA6050 Brass GA6052 Antique Brss GA6053 Helps de ect heat awa...

Page 19: ..._____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____...

Page 20: ...ostic cost labor transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner TOTHE FULLEXTENTALLOWED BYTHE LAWOFTHE JURISDICTIONTHAT...

Reviews: