INSTALLATION

Continued 

The appliance gas inlet connection is 3/8" NPT at 

the regulator, located at the rear of the appliance.

IMPORTANT: 

Hold appliance regulator with a 

wrench to prevent movement when connecting 

to inlet piping.

  CAUTION:  Use  only  new, 

black  iron  or  steel  pipe.  Inter-

nally-tinned copper tubing may 

be used in certain areas. Check 

your  local  codes.  Use  pipe  of 

1/2" diameter or greater to allow 

proper gas volume to heater. If 

pipe is too small, undue loss of 

volume will occur.

Installation must include an equipment shutoff 

valve, union and plugged 1/8" NPT tap. Locate NPT 

tap within reach for test gauge hook up. NPT tap 

must be upstream from log set (see Figure 4).

IMPORTANT:

 Install equipment shutoff valve in an 

accessible location. The equipment shutoff valve is for 

turning on or shutting off the gas to the appliance.
Apply  pipe  joint  sealant  lightly  to  male  NPT 

threads. This  will  prevent  excess  sealant  from 

going into pipe. Excess sealant in pipe could result 

in clogged heater valves.

  WARNING:  Use  pipe  joint 

sealant that is resistant to liquid 

petroleum (LP) gas. 

Install a sediment trap where it is within reach for 

cleaning. Install in piping system between fuel 

supply and heater. Locate sediment trap where 

trapped matter is not likely to freeze. A sediment 

trap traps moisture and contaminants. This keeps 

them from going into heater controls. If sediment 

trap is not installed or is installed wrong, heater 
may not run properly.

Figure 4 - Gas Connection

* Purchase the optional CSA design-certified shutoff 

valve from your dealer. See 

Accessories

, page 18.

** Minimum inlet pressure for purpose of input 

adjustment.

Approved Flexible 
Gas Hose (If 
allowed by local 
codes)

CSA Design-Certified 
Equipment Shutoff Valve 
with 1/8" NPT Tap*

Natural

 

From Gas 
Meter (5" W.C.** 
to 10.5" W.C. 
Pressure)

Propane/LP

 

From External 
Regulator (11" 
W.C.** to 14" 
W.C. Pressure)

3" Minimum

Pipe  Cap  Tee
Nipple  

Joint

CHECKING GAS CONNECTIONS

 WARNING: Test all gas piping 

and connections for leaks after 

installing or servicing. Correct 

all leaks at once.

  WARNING:  Never  use  an 

open flame to check for a leak. 

Apply a noncorrosive leak detec-

tion fluid to all joints. Bubbles 

forming show a leak. Correct all 

leaks at once.

PRESSURE TESTING GAS SUPPLY 
PIPING SYSTEM 
Test Pressures In Excess Of 1/2 PSIG 
(3.5 kPa)

1.  Disconnect appliance with its appliance main 

gas  valve  (control  valve)  and  equipment 

shutoff valve from gas supply piping system. 

Pressures in excess of 1/2 psig will damage 

heater regulator.

2.  Cap off open end of gas pipe where equipment 

shutoff valve was connected.

3.  Pressurize  supply  piping  system  by  either 

opening propane/LP supply tank valve for 

propane/LP gas or opening main gas valve 

located on or near gas meter for natural gas 

or using compressed air.

Summary of Contents for Design Dynam

Page 1: ...ny appliance Do not touch any electrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach you...

Page 2: ...ANSI Z233 1 NFPA 54 Section 5 3 Air for Combustion and Ventilation This appliance may be installed in an aftermarket per manently located manufactured mobile home where not prohibited by local codes...

Page 3: ...ts Make certain you read and understand all warnings Keep this manual for reference It is your guide to safe and proper operation of this log set WARNING Any change to this log set or its controls can...

Page 4: ...he vents before operating heater 7 Toreducethecreationofsoot followtheinstruc tions in Cleaning and Maintenance page 12 8 Do not run heater where ammable liquids or vapors are used or stored under dus...

Page 5: ...f highly heated A dirtychimney uemaycreateand distribute soot within the house Inspectchimney uefordamage If damaged repair ue damper before operating appliance CAUTION Thisheatercreates warmaircurren...

Page 6: ...ated pro pane LP tank may cause an explosion Propane LP Supply Tank External Regulator Vent Pointing Down Figure 3 External Regulator with Vent Pointing Down Figure 2 Attaching Damper Clamp Manufactur...

Page 7: ...y to freeze A sediment trap traps moisture and contaminants This keeps them from going into heater controls If sediment trap is not installed or is installed wrong heater may not run properly Figure 4...

Page 8: ...detection fluid to all joints Bubbles forming show a leak 4 Correct all leaks at once Gas Pressure Check The appliance regulator controls the burner pres sure which should be checked at the pressure t...

Page 9: ...d OPERATING APPLIANCE The RF Millivolt valve control used on these appli ances allows you to turn the gas log set on or off use a timer to automatically operate the log set increase or decrease ame he...

Page 10: ...appliance and to replace any part of the control system and any gas control which has been under water OPERATING HEATER Continued LIGHTING INSTRUCTIONS NOTICE During initial operation the appliance wi...

Page 11: ...until mode is OFF Pilot stays lit Shut Off Main Burner Without Remote Turn PilotStat knob to PILOT Pilot stays lit Shut Off Main Burner and Pilot Turn PilotStat knob to OFF CAUTION During normal shutd...

Page 12: ...lide the battery compartment door off to expose old batteries Place new batteries into housing and reattach door See Figure 15 Figure 15 Bottom of Transmitter Showing Battery Compartment and Door TECH...

Page 13: ...ntrol system be sure external gas shut off valve located at gas supply inlet is in the ON position POSSIBLE CAUSE REMEDY OBSERVED PROBLEM 1 Defective ignitor no spark at electrode 2 Defective or misal...

Page 14: ...2 Check thermopile with mil livolt meter Take reading at thermopile terminals of gas valve It should read 325 mil livolts minimum with optional wall switch OFF Replace faulty thermopile if reading is...

Page 15: ...10 6 3 W C 3 5 1 6 W C 10 6 3 W C Inlet Gas Pressure in of water Maximum 10 5 W C 13 W C 10 5 W C 13 W C Minimum 5 0 W C 11 W C 5 0 W C 11 W C Valve Operation RF Millivolt RF Millivolt RF Millivolt RF...

Page 16: ...m 115481 01A 16 ILLUSTRATED PARTS BREAKDOWN HCA 24 RFN HCA 24 RFP HCA 18 RFN HCA 18 RFP HCM 24 RFN HCM 24 RFP HCM 18 RFN HCM 18 RFP HKE 24 RFN HKE 24 RFP HKE 18 RFN HKE 18 RFP 1 3 7 6 5 4 2 8 9 10 12...

Page 17: ...ket 1 9 115491 01 115492 01 115492 01 115493 01 Air Shutter 1 10 115454 01 115454 01 115454 01 115454 02 Venturi 1 11 115452 01 115452 01 115452 01 115452 01 Valve Bracket 1 12 115488 01 115488 01 115...

Page 18: ...on the back page of this manual EQUIPMENT SHUTOFF VALVE GA5010 Equipment shutoff valve with 1 8 NPT tap Fits 1 2 pipe FIREPLACE HOOD Black GA6050 Brass GA6052 Antique Brss GA6053 Helps de ect heat awa...

Page 19: ..._____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____...

Page 20: ...ostic cost labor transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner TOTHE FULLEXTENTALLOWED BYTHE LAWOFTHE JURISDICTIONTHAT...

Reviews: