background image

www.desatech.com

123551-01D

12

INSTALLATION

Continued

INSTALLING HEATER BASE 
ASSEMBLY

 CAUTION: Do not remove the 

data plates attached to the heater 

base assembly. The data plates 

contain important warranty and 

safety information.

 WARNING: If installing in a 

sunken  fireplace,  special  care 

is  needed.  You  must  raise  the 

fireplace  floor  to  allow  access 

to  heater  control  panel.  This 

will  insure  adequate  air  flow 

and guard against sooting and 

controls being damaged. Raise 

fireplace floor with noncombus-

tible material. Make sure material 

is secure.

  CAUTION:  Do  not  pick  up 

heater  base  assembly  by  the 

burner.  This  could  damage 

heater.  Only  handle  base  as-

sembly by grates.

Hearth

5"

Min.

Combustible 

Material 

14"

Min.

Combustible 

Material 

Noncombustible Material 

Figure 8 - Minimum Fireplace Clearances 

If Installed at Floor Level

Figure 9 - Minimum Fireplace Clearances 

Above Combustible Flooring

MANTEL CLEARANCES

In addition to meeting noncombustible mate-

rial clearances, you must also meet required 
clearances  between  fireplace  opening  and 

mantel shelf. If you do not meet the clearances 

listed below, you will need a hood.

Determining Minimum Mantel Clearance

If you meet minimum clearance between man-

tel shelf and top of fireplace opening, a hood 
is not required (see Figure 6, page 11).

Determining Minimum Mantel Clearance 
when Using a Hood

If minimum clearances in Figure 6, page 11, 
are  not  met,  you  must  have  a  hood.  When 

using a hood there are still certain minimum 

mantel clearances required. Follow minimum 
clearances shown in Figure 7, page 11, when 

using a hood.

NOTICE: Surface temperatures 

of  adjacent  walls  and  mantels 

become  hot  during  operation. 

Walls  and  mantels  above  the 

firebox  may  become  hot  to 

the touch. If installed properly, 

these  temperatures  meet  the 

requirement  of  the  national 

product  standard.  Follow  all 

minimum clearances shown in 

this manual.

NOTICE: If your installation does 

not  meet  the  minimum  clear-

ances shown, you must do one 

of the following:

•  raise the mantel to an accept-

able height

•  remove the mantel

FLOOR CLEARANCES

A.  If  installing  appliance  on  the  floor  level, 

you must maintain the minimum distance 
of 14" to combustibles (see Figure 8).

B.  If combustible materials are less than 14" 

to the fireplace, you must install appliance 
at least 5" above the combustible flooring 

(see Figure 9).

Summary of Contents for CSG3924NTA

Page 1: ...y appliance Do not touch any electrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your...

Page 2: ...or these installations in accordance with ANSI Z21 11 2 Exception Do not install this appliance in a factory built fireplace that includes instructions stating it has not been test ed or should not be...

Page 3: ...However the odor added to the gas can fade Gas may be present even though no odor exists Make certain you read and understand all warnings Keep this manual for reference It is your guide to safe and p...

Page 4: ...k of less than 100 lb capacity 18 Provide adequate clearances around air openings You must operate this heater with a fireplace screen in place Make sure fireplace screen is closed before running heat...

Page 5: ...he Commonwealth of Massachusetts Sellers of unvented propane or natural gas fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale of the unit Vent free gas pro...

Page 6: ...home needs to breathe Fresh air must enter your home All fuel burning ap pliances need fresh air for proper combustion and ventilation Exhaust fans fireplaces clothes dryers and fuel burning applianc...

Page 7: ...etermine the maximum Btu Hr the space can support _________ volume of space x 20 Maxi mum Btu Hr the space can support Example 2 560 cu ft volume of space x 20 51 200 maximum Btu Hr the space can supp...

Page 8: ...an adjoining unconfined space you must provide two permanent openings one within 12 of the ceiling and one within 12 of the floor on the wall connecting the two spaces see options 1 and 2 Figure 2 You...

Page 9: ...eated Adirtychimneyfluemay createanddistributesootwithin the house Inspect chimney flue and firebox for damage If dam aged repair flue before operat ing heater WARNING Seal any fresh air vents or ash...

Page 10: ...tinued Note When installing your gas logs into a manufactured firebox follow firebox manufacturer s instructions for minimum clearances to combustible materials B Clearances from top of fireplace open...

Page 11: ...al Slate Marble Tile etc Above Fireplace Figure 6 Minimum Mantel Clearances Without Using Hood Minimum Noncombustible Material Minimum Noncombustible Material Height Distances to Underside of Mantel T...

Page 12: ...t meet the clearances listed below you will need a hood Determining Minimum Mantel Clearance If you meet minimum clearance between man tel shelf and top of fireplace opening a hood is not required see...

Page 13: ...r base and logs front to back and side to side in fireplace 6 Carefully remove logs without moving heater base 7 Mark screw locations through one hole on each side of the mounting bracket see Figure 1...

Page 14: ...gas is commonly known as wellhead gas Installation Items Needed Before installing heater make sure you have the items listed below external regulator supplied by installer piping check local codes se...

Page 15: ...ing Gas Supply Piping System Test Pressures In Excess Of 1 2 PSIG 3 5 kPa 1 Disconnect appliance with its appliance main gas valve control valve and equip ment shutoff valve from gas supply piping Pre...

Page 16: ...tion INSTALLING LOGS WARNING Failure to posi tion the parts in accordance with these diagrams or failure to use only parts specifically approved with this heater may result in property damage or perso...

Page 17: ...n log 1 ember bed and rest back of log 6 on back log 4 see Figure 20 Figure 18 Installing Log 2 Right and Log 3 Left Figure 19 Installing Log 4 Figure 20 Installing Log 5 Right and Log 6 Left Log 5 Lo...

Page 18: ...Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information in column 1 If you don t smell gas go to the next step Operation FOR YOUR SAFETY READ BEFORE LIGHTI...

Page 19: ...tor Electrode Figure 24 Pilot Natural Ignitor Electrode Pilot Burner Thermocouple Thermocouple 9 To light the rear yellow flame burner push in and turn rear burner control knob coun terclockwise to th...

Page 20: ...r flame pat ternsshowyellowtipping follow instructionsbelow Yellowflame on rear burner is normal NOTICE Do not mistake orange flames with yellow tipping Dirt orotherfineparticlesareburned by heater ca...

Page 21: ...ted at the end of burner tubes again Remove any large particles of dust dirt lint or pet hair with a soft cloth or vacuum cleaner nozzle 5 Blow air into the primary air holes on the injector holders 6...

Page 22: ...en in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct OBSERVED PROBLEM Whenignitorbuttonispressed there is no spark at ODS pilot Whenignito...

Page 23: ...qualified service person 1 Contact local natural or propane LP gas company 2 Clean burner s see Clean ing and Maintenance page 20 or replace burner orifice s 3 Contact qualified service person 1 Clea...

Page 24: ...removed from line Have gas line checked by local natural or propane LP gas company 3 Observeminimuminstallation clearances see page 8 4 Clean burners see Clean ing and Maintenance page 20 1 Turn heat...

Page 25: ...Locate and correct all leaks see Checking Gas Con nections page 16 1 Open window and or door for ventilation 2 Contact local natural or propane LP gas company 3 Clean ODS pilot see Cleaning and Mainte...

Page 26: ...he mounting bracket This location allows the thermostat to keep the room temperature at an ideal comfort level for most fireplace applications For positioning the thermostat sensing bulb elsewhere an...

Page 27: ...Piezo Manifold Pressure 3 W C Inlet Gas Pressure in of water Maximum 10 5 W C Minimum 5 W C Shipping Weight 30 lbs Certified Standards Z21 11 2 2000 For purpose of input adjustment Parts Log Models C...

Page 28: ...www desatech com 123551 01D 28 PARTS Thermostat Controlled Models CSG3924NTA AND CSG3924PTA 1 16 17 2 18 12 28 24 27 27 27 27 27 27 8 8 7 9 13 5 6 19 20 4 14 10 25 3 26 22 15 21 11 23...

Page 29: ...097159 04 Piezo Ignitor 1 15 098271 10 Ignitor Cable 1 16 099056 18 Burner Orifice Injector Back 1 099056 21 Burner Orifice Injector Back 1 17 101004 02 Burner Orifice Injector Front 1 101004 18 Burn...

Page 30: ...r was malfunctioning purchase date Service Hints When Gas Pressure Is Too Low pilot will not stay lit burners will have delayed ignition fireplace will not produce specified heat for propane LP units...

Page 31: ...__ ______________________________________________________ ______________________________________________________ ______________________________________________________ ________________________________...

Page 32: ...proved by DESA Heating LLC Warranty parts must be obtained through authorized dealers of this prod uct and or DESA Heating LLC who will provide original factory replacement parts Failure to use origin...

Reviews: