background image

6

104433

VENT-FREE NATURAL GAS HEATER

 15,000 TO 30,000 BTU/HR

 WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space

or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of
the methods described in the 

National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.

AIR FOR
COMBUSTION AND
VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between

the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example:

 Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

______________ (volume of space) 

÷

 50 cu. ft. = (Maximum Btu/Hr

the space can support)

Example:

 2560 cu. ft. (volume of space) 

÷

 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

__________________ Btu/Hr

Gas water heater*

__________________ Btu/Hr

Gas furnace

__________________ Btu/Hr

Vented gas heater

__________________ Btu/Hr

Gas fireplace logs

__________________ Btu/Hr

Other gas appliances*

__________________ Btu/Hr

Total

__________________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

___________________ Btu/Hr (maximum the space can support)

___________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

60,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-

ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 7.

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

Example:

Gas water heater

30,000

Btu/Hr

Vent-free heater +

30,000

Btu/Hr

Total

=

60,000

Btu/Hr

Summary of Contents for Comfort Glow RFN30T

Page 1: ...tallation and service must be performed by a qualified installer service agency or the gas supplier WARNING Improper installa tion adjustment alteration ser vice or maintenance can cause injury or pro...

Page 2: ...ges 5 through 7 5 If heater shuts off do not relight until you provide fresh outside air If heater keeps shutting off have it serviced 6 To prevent the creation of soot follow the instructions in Clea...

Page 3: ...I GL FJ I als kd idk oe m kg o dk irln fg pd fA SD FK IG LF JI als kd idk oe m kg o dk irln fg pd f AS DF KI GL FJ I als kd idk oe m kg o dk irln fg pd fA SD FK IG LF JI als kd idk oe m kg o dk irln f...

Page 4: ...uts from inside of front panel Tighten with wrench Truss Head Screw Nut Front Panel Figure 5 Attaching Brass Front Trim to Front Panel Brass Front Trim ASSEMBLY ASSEMBLING HEATER Tools Required Philli...

Page 5: ...uction 2 Unconfined Space 3 Confined Space The information on pages 5 through 7 will help you classify your space and provide adequate ventilation Unusually Tight Construction The air that leaks aroun...

Page 6: ...of all fuel burning appliances in the space Vent free heater __________________ Btu Hr Gas water heater __________________ Btu Hr Gas furnace __________________ Btu Hr Vented gas heater _____________...

Page 7: ...d size of ventilation grills or ducts WARNING Rework work sheet adding the space of the adjoining unconfined space The combined spaces must have enough fresh air to supply all appliances in both space...

Page 8: ...can locate heater on floor The optional hearth base is needed You can also install the optional decorative mantel on the heater some mantels require hearth base IMPORTANT Only use optional mantel and...

Page 9: ...of heater It has been taped there for shipping Remove mounting bracket from back panel 20 3 4 Min 11 Min 16 Adjoining Wall Only Insert Mounting Screws Through Last Hole On Each End Floor Figure13 Moun...

Page 10: ...are in hardware package The hard ware package is provided with heater Attaching To Wall Stud Method Forattachingmountingbrackettowallstuds 1 Drill holes at marked locations using 9 64 drill bit 2 Plac...

Page 11: ...th base as shown in Figure 19 7 Assemble brass trim see steps 1 through 7 under Assembling and At taching Brass Trim page 5 8 Slide base trim on heater base Attach brass trim to base with two brass sc...

Page 12: ...ING TO GAS SUPPLY WARNING A qualified service personmustconnectheatertogas supply Follow all local codes IMPORTANT Check gas line pressure be fore connecting heater to gas line Gas line pressure must...

Page 13: ...ing show a leak Correct all leaks at once Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff valve see Fig ure 21 2 Pressurize supply piping system by either usingcompress...

Page 14: ...ervice person or gas supplier for repairs Note If pilot goes out repeat steps 3 through 7 This heater has a safety interlock system Wait one 1 minute before lighting pilot again 8 Turn control knob co...

Page 15: ...djusts the amount of gas flow to the burner This increases or de creases the burner flame height At times the room may exceed the set temperature If so the burner will shut off The burner willcyclebac...

Page 16: ...or gas quality is bad If so contact your local natural gas supplier CLEANING BURNER INJECTOR HOLDER AND PILOT AIR INLET HOLE The primary air inlet holes allow the proper amount of air to mix with the...

Page 17: ...e to cool causing pilot flame to go out This prob lem could be caused by one or both of the following A Low gas pressure B Dirty or partially clogged ODS pilot 7 Thermocouple damaged 8 Control valve d...

Page 18: ...regulator 1 Problem will stop after a few hours of operation 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by l...

Page 19: ...for Combustion and Venti lation requirements page 5 POSSIBLE CAUSE 1 Metal expanding while heating or con tracting while cooling 1 Heater burning vapors from paint hair spray glues etc see IMPORTANT s...

Page 20: ...so IN 46383 9704 All States 219 462 7441 1 800 362 6951 sales portableheaterparts com techservice portableheaterparts com FBD 1349 Adams Street Bowling Green KY 42103 3414 270 846 1199 1 800 654 8534...

Page 21: ...the floor Includes brass trim Complete installation instruc tions included PRESTIGE MANTEL WITH BUILT IN BASE Unfinished GMC27U Series Finished GMC26F Series Finished Oak GMC28F For use with heater F...

Page 22: ...22 104433 VENT FREE NATURAL GAS HEATER 15 000 TO 30 000 BTU HR 12 1 12 2 1 2 9 10 11 12 17 18 19 21 22 23 8 20 7 1 3 5 16 4 25 24 1 6 13 14 15 26 10 ILLUSTRATED PARTS BREAKDOWN RFN30T...

Page 23: ...099440 05 ODS Pilot Assembly 1 12 1 098514 01 Thermocouple 1 12 2 098594 01 Ignitor Electrode 1 13 103447 01 Burner 1 14 098517 01 3 16 Pilot Tubing 1 15 103845 07 Injector 1 16 103408 01 Burner Brack...

Page 24: ...artsthatarenotinoriginalconditionbecauseofnormalwearandtear orpartsthatfailorbecome damaged as a result of misuse accidents lack of proper maintenance or defects caused by improper installation Travel...

Reviews: