DETERMINING FRESH-AIR FLOW FOR APPLIANCE LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space:

  Includes the room in which you will install appliance plus any adjoining rooms with doorless passageways or ventilation grills

between the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example:

 Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_____________ (volume of space) 

÷

 50 cu. ft. = (maximum Btu/Hr the space can support)

Example:

 2560 cu. ft. (volume of space) 

÷

 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Gas fireplace logs

_____________ Btu/Hr

Gas water heater*

_____________ Btu/Hr

Gas furnace

_____________ Btu/Hr

Vented gas heater

_____________ Btu/Hr

Vent-free heater

_____________ Btu/Hr

Other gas appliances* + _____________ Btu/Hr
Total                            = _____________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_____________ Btu/Hr (maximum the space can support)

_____________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

95,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-

ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

AIR FOR
COMBUSTION AND
VENTILATION

Continued

Example:

Gas water heater

40,000 Btu/Hr

Gas fireplace logs +

55,000 Btu/Hr

Total

=

95,000 Btu/Hr

Continued

 WARNING: If the area in which the appliance may be operated is smaller than that defined as an unconfined

space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one
of the methods described in the 

National Fuel Gas Code, ANS Z223.1, 1992, Section 5.3 or applicable local codes.

Summary of Contents for Comfort Glow CVTR18

Page 1: ...rect installation and operational procedures For assistance or additional information consult a qualified installer service agency or the gas supplier WARNING This appliance is for installation only i...

Page 2: ...d fire box must be cleaned of soot creosote ashes and loose paint by a qualified chimney cleaner Creosote will ignite if highly heated Inspect chimney flue for damage 5 You must operate this log set w...

Page 3: ...that can be purchased sepa rately for this log set You must use the millivolt valve safety pilot kit to use remote accessories with this appliance See Acces sories page 17 UNPACKING CAUTION Do not rem...

Page 4: ...heatlossinhomes Homeowners weather strip and caulk around windows and doorstokeepthecoldairoutandthewarmair in During heating months home owners want their homes as airtight as possible While it is go...

Page 5: ...combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used _____________ Btu Hr maximum the space can support...

Page 6: ...he two spaces see options 1 and 2 Figure 2 You can also remove door into adjoining room see op tion 3 Figure 2 Follow the National Fuel Gas Code NFPA 54 ANS Z223 1 Section 5 3 Air for Combustion and V...

Page 7: ...must be in stalled only in a solid fuel burning fireplace with a working flue and constructed of non combustible material The charts in Figure 4 indicate technical information regarding the installati...

Page 8: ...s Needed Before installing log set make sure you have the items listed below piping check local codes sealant resistant to LP gas manual shutoff valve test gauge connection adjustable crescent wrench...

Page 9: ...16 wrench 6 Slip the air restrictor over the 1 8 pipe nipple Apply thread sealant to the male threads and install the rear burner nozzle onto the fitting Tighten with a 9 16 wrench 7 Place the grate...

Page 10: ...alve Manifold Block Figure 11 Installing Gas Control Valve Control Rod INSTALLATION Continued rod to the front 9 Install valve cover to burner pan using screws provided 10 Install thermocouple pilot a...

Page 11: ...e immedi ately Tighten or reassemble the loose connection s using pipe joint com pound until burner system is leak free 4 When the burner is tested and leak free observe the individual tongues of flam...

Page 12: ...f you then smell gas STOP Fol low the safety information above If you don t smell gas go on to the next step 4 Light a match and lay it on top of the U shaped burner near the edge of the cover on the...

Page 13: ...essed in for five 5 seconds Note You may be running this log set for the first time after hooking up to gas supply If so the control knob may need to be pressed in for 30 sec onds This will allow air...

Page 14: ...king sooting excessively Note It is natural and unavoidable for vented gas log sets to produce moderate levels of carbon soot where flames contact the logs This is especially true with propane LP gas...

Page 15: ...ce page 17 or replace pilot assembly 5 Hand tighten until snug then tighten 1 4 turn more 6 Replace thermocouple 7 Replace control valve 1 Clean burner orifice 2 Contact local natural or propane LP ga...

Page 16: ...tatement at top of page OBSERVED PROBLEM Log Set produces a clicking ticking noise just after burner is lit or shut off Log Set produces unwanted odors Gas odor even when control knob is in OFF positi...

Page 17: ...onal sTechnicalServiceDe partment at 1 800 DESA LOG 1 800 337 2564 WhencallingDESAInternational haveready your name your address modelandserialnumbersofyourfireplace how fireplace was malfunctioning t...

Page 18: ...18 901049 VENTED NATURAL GAS LOGS ILLUSTRATED PARTS BREAKDOWN CVTR18 CVTR24 4 19 23 21 22 20 24 25 26 2 3 8 7 11 10 1 5 6 15 9 14 12 13 27 16 18 5 17...

Page 19: ...Natural Gas 1 12 901761 01 901761 01 1 8 Hex Nipple 1 13 901760 01 901760 01 Manifold Block 1 14 901751 01 901751 01 Air Restrictor 1 15 901756 01 901756 01 Valve Cover 1 16 901056 01 901056 01 Brass...

Page 20: ...s Parts and Service 2444 North 5th Street Hartsville SC 29550 7704 803 332 0191 Parts Department Cans Unlimited Inc P O Box 645 Taylor SC 29687 0013 All States 803 879 3009 1 800 845 5301 Parts Depar...

Page 21: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Page 22: ..._______________________ _______________________________________________________________________________________________ ________________________________________________________________________________...

Page 23: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Page 24: ...log set will be the responsibility of the owner TOTHEFULLEXTENTALLOWEDBYTHELAWOFTHEJURISDICTIONTHATGOVERNSTHESALEOFTHEPRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND...

Reviews: